Plan Review Notes
Plan Review Notes For Permit 06120355
Permit Number 06120355
Review Stop M
Sequence Number 1
Notes
Date Text
2007-01-09 10:33:22*** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC
 13-101.1.1.
  
 2) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR A/C
 SYSTEMS, A/C EQUIPMENT LISTING IS CALLING FOR 10.5 SEER
 EQUIPMENT BUT THE MINIMUM IS 13 SEER, PER 2004/ 06 REV.
 FBC 13-607.1.ABC.3.2.1.
  
 3) SEE PLANS PAGE M-1 A/C UNIT MOUNTING DETAIL,
 CONDENSER DRAIN NEEDS TO DISCHARGE A MINIMUM OF 12"
 FROM THE BUILDING, PER 2004 FBC 1503.6.
  
 4) SEE PLANS PAGE M-1 RETURN AIR TRANSFER DUCTS, 10"
 FROM ROOM 102 TO 103 NEEDS TO BE 14", 10" FROM ROOM 112
 TO 107 NEEDS TO BE 14", AND 10" FROM ROOM 107 TO 109
 NEEDS TO BE 18",
 BALANCED RETURN AIR MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.