2007-02-08 12:08:16*****DENIED*****
  
  
 1.THE COMPLETE AND/OR ACTUAL ADDRESS OF WHERE THE
 SCOPE OF WORK IS TO BE CONDUCTED SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 2.THE NFPA 101, 2003 EDITION AND THE FLORIDA FIRE
 PREVENTION CODE 2004 SHALL BE REFERENCED.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, AND
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE
 PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES).
  
 5.WHAT IS THE OCCUPANCY CLASSIFICATION FOR THIS
 STRUCTURE?
  
 6.INDICATE THE NEAREST FIRE HYDRANT(S) IN THE
 VICINITY OF THE STRUCTURE.PLEASE BE ADVISED THAT IF
 THE DISTANCE IS GREATER THAN 500 FEET, AN ADDITIONAL
 HYDRANT MAY BE REQUIRED.
  
 7.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE EXTERIOR
 ELEVATION THAT FRONTS JEFFERSON ROAD.AS PER WEST PALM
 BEACH CODE, THE ADDRESS NUMBERS SHALL BE NO LESS THAN
 6" IN HEIGHT NAND 1" IN WIDTH.
  
 8.ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN AREA
 HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PROVIDED WITH PANIC HARDWARE OR FIRE EXIT HARDWARE,
 UNLESS OTHERWISE THEY ARE DELAYED-EGRESS LOCKS OR
 ACCESS-CONTROLLED EGRESS LOCKS PERMITTED AND APPROVED
 BY THE AHJ.
  
 9.SINCE THE STRUCTURE WILL HAVE A FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEM, A LAYOUT OF EACH OF THESE FIRE
 PROTECTION SYSTEMS WILL BE SUBMITTED FOR REVIEW.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  