2007-01-17 09:31:33BUILDING PLAN REVIEW
 PERMIT: 06120355
 ADD: 900 S OLIVE AVE
 CONT: ROBLING ARCHITECTURE
 TEL: (561)662-0000
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1SSTREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.NOTE: 713.13(2) IF THE WORK DESCRIBED IN
 THE NOTICE OFCOMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL
 & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) PLEASE CORRECT THE ADDRESS AND PROPERTY CONTROL
 NUMBER ON THE PERMIT APPLICATION.
 PLANS INDICATE WORK TO BE ACCOMPLISHED ON JEFFERSON RD.
 PLEASE CONTACT LILI URSA AT 822-1239
 FOR A NEW ADDRESS AND PLEASE CORRECR THE PROPERTY
 CONTROL NUMBER TO REFLECT THE CORRECT LOT. 106.1.2.*
 ADDITIONAL INFORMATION REQUIRED.
  
 4) PLEASE PROVIDE ENERGY CALCS. CHAPTER 13 FBC.
  
 5) PLEASE PROVIDE SOILS REPORTS,FBC 1802.2.1
 QUESTIONABLE SOILS,
 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING
 POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING
 VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE.
 SUCH INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 6) PLEASE PROVIDE A SITE PLAN PROVIDING THE FOLLOWING:
 11-4.1.2 ACCESSIBLE SITE AND EXTERIOR FACILITIES: NEW
 CONSTRUCTION.
 THIS EDITION OF THE CODE DOES NOT APPLY TO BUILDINGS,
 STRUCTURES, OR FACILITIES WHICH WERE EITHER UNDER
 CONSTRUCTION OR UNDER CONTRACT FOR CONSTRUCTION ON
 OCTOBER 1, 1997.
 NOTHING IN THIS CODE SHALL BE CONSTRUED TO RELIEVE THE
 OWNER OF ANY BUILDING, STRUCTURE OR FACILITY FROM THE
 DUTY TO PROVIDE VERTICAL ACCESSIBILITY TO ALL LEVELS
 ABOVE AND BELOW THE OCCUPIABLE GRADE LEVEL, REGARDLESS
 OF WHETHER THE CODE REQUIRES AN ELEVATOR TO BE
 INSTALLED IN SUCH BUILDING, STRUCTURE OR FACILITY,
 EXCEPT: (1) ELEVATOR PITS, ELEVATOR PENTHOUSES,
 MECHANICAL ROOMS, PIPING OR EQUIPMENT CATWALKS, AND
 AUTOMOBILE LUBRICATION AND MAINTENANCE PITS AND
 PLATFORMS; (2) UNOCCUPIABLE SPACES, SUCH AS ROOMS,
 ENCLOSED SPACES, AND STORAGE SPACES THAT ARE NOT
 DESIGNED FOR HUMAN OCCUPANCY, FOR PUBLIC
 ACCOMMODATIONS, OR FOR WORK AREAS; AND (3) OCCUPIABLE
 SPACES AND ROOMS THAT ARE NOT OPEN TO THE PUBLIC AND
 THAT HOUSE NO MORE THAN FIVE PERSONS INCLUDING, BUT NOT
 LIMITED TO, EQUIPMENT CONTROL ROOMS AND PROJECTION
 BOOTHS. HOWEVER AS PROVIDED IN SECTION 553.509, FLORIDA
 STATUTES, BUILDINGS, STRUCTURES, AND FACILITIES MUST,
 AT A MINIMUM, COMPLY WITH THE REQUIREMENTS OF THE
 ADAAG. THEREFORE, FACILITIES SUBJECT TO THE ADAAG MAY
 BE REQUIRED TO PROVIDE VERTICAL ACCESS TO AREAS
 OTHERWISE EXEMPT UNDER SECTION 11-4.1.3 (5) OF THIS
 CODE.
 AN ACCESSIBLE SITE SHALL MEET THE FOLLOWING MINIMUM
 REQUIREMENTS:
 (1)AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH
 SECTION 11-4.3 SHALL BE PROVIDED WITHIN THE BOUNDARY OF
 THE SITE FROM PUBLIC TRANSPORTATION STOPS, ACCESSIBLE
 PARKING SPACES, PASSENGER LOADING ZONES IF PROVIDED,
 AND PUBLIC STREETS OR SIDEWALKS, TO AN ACCESSIBLE
 BUILDING ENTRANCE.
 (2)AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH
 SECTION 11-4.3 SHALL CONNECT ACCESSIBLE BUILDINGS,
 ACCESSIBLE FACILITIES, ACCESSIBLE ELEMENTS, AND
 ACCESSIBLE SPACES THAT ARE ON THE SAME SITE.
 (3)ALL OBJECTS THAT PROTRUDE FROM SURFACES OR
 POSTS INTO CIRCULATION PATHS SHALL COMPLY WITH SECTION
 11-4.4 .
 (4)GROUND SURFACES ALONG ACCESSIBLE ROUTES AND IN
 ACCESSIBLE SPACES SHALL COMPLY WITH SECTION 11-4.5 .
  
 7) PLANS DO NOT PROVIDE DETAILS TO THE ENTRY OF ANY
 EXTERIOR DOORS.
 1003.5.2
 WHERE CHANGE IN ELEVATION OF 12 INCHES (305 MM) OR LESS
 OCCURS IN EXIT ACCESS CORRIDORS, EXITS AND EXIT
 DISCHARGE, RAMPS COMPLYING WITH SECTION 1010 SHALL BE
 PROVIDED.
 1003.5.2
 WHERE CHANGE IN ELEVATION OF 12 INCHES (305 MM) OR LESS
 OCCURS IN EXIT ACCESS CORRIDORS, EXITS AND EXIT
 DISCHARGE, RAMPS COMPLYING WITH SECTION 1010 SHALL BE
 PROVIDED.
  
 8)SHEET A-3 INDICATES THE USE OF 2 SINKS PLANS
 INDICATE A CLEAR FLOOR SPACE FOR FRONT APPROACH BUT
 THERE IS NO
 ELEVATION INDICATING THE FRONT OF THE CABINET
 CONFIGURATION. PLEASE PROVIDE.
 SINKS:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4
 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD
 APPROACH.
 THE CLEAR FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE
 AND
 SHALL EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH
 THE SINK.
  
 9) PLANS DO NOT INDICATE THE USE OF A VAPOR RETARDER.
 1816.1.4
 IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE
 PREVENTION, CHEMICALLY TREATED SOIL SHALL BE PROTECTED
 WITH A MINIMUM 6 MILLIMETER VAPOR RETARDER TO PROTECT
 AGAINST RAINFALL DILUTION. IF RAINFALL OCCURS BEFORE
 VAPOR RETARDER PLACEMENT, RETREATMENT IS REQUIRED. ANY
 WORK, INCLUDING PLACEMENT OF REINFORCING STEEL, DONE
 AFTER CHEMICAL TREATMENT UNTIL THE CONCRETE FLOOR IS
 POURED, SHALL BE DONE IN SUCH MANNER AS TO AVOID
 PENETRATING OR DISTURBING TREATED SOIL.
  
 10)PLANS DO NOT INDICATE THE USE OF TERMITE
 PROTECTION, PLEASE INDICATE WHICH METHOD OF PROVIDING
 SUBTERRANEAN TERMITE PROTECTION SHALL BE USED. 1816.1
 TERMITE PROTECTION.
 TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED
 TERMITICIDES, INCLUDING SOIL APPLIED PESTICIDES,
 BAITING SYSTEMS, AND PESTICIDES APPLIED TO WOOD, OR
 OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED
 FOR USE AS A PREVENTATIVE TREATMENT TO NEW
 CONSTRUCTION. SEE SECTION 202 , REGISTERED TERMITICIDE.
 UPON COMPLETION OF THE APPLICATION OF THE TERMITE
 PROTECTIVE TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL
 BE ISSUED TO THE BUILDING DEPARTMENT BY THE LICENSED
 PEST CONTROL COMPANY THAT CONTAINS THE FOLLOWING
 STATEMENT: ?THE BUILDING HAS RECEIVED A COMPLETE
 TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES.
 TREATMENT IS IN ACCORDANCE WITH RULES AND LAWS
 ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE
 AND CONSUMER SERVICES.?
  
 11) SHEET F-1 STRUCTURAL NOTE# 4, PLANS INDICATE
 ANCHORING HARDWARE TO MEET THE MINIMUM STANDARDS FOR
 ACI 318-05. PLEASE PROVIDE HOW THE
 PREFAB WILL BE ATTACHED TO THE FOUNDATION. 106.1.2*.
  
 12)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 12A) WINDOWS- SINGLE HUNG
 12B) WINDOWS- GLASS BLOCK
 12C) EXTERIOR DOORS SOLID OR GLAZED
 12D) ROLL UP DOORS
 12E) ROOFING ASSEMBLIES
  
 13)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 14) SPEAKING WITH ARCHITECT STEVEN BRUH THE
 MANUFACTURING COMPANY HAS APPLIED FOR DCA APPROVAL BUT
 HAS NOT RECEIVED SUCH APPROVAL AT THIS TIME. THE CITY
 HAS REVIEWED WHAT THEY WILL REQUIRE FOR A SITE SPECIFIC
 REQUIREMENTS FOR ROYAL CONCRETE CONCEPTS, INC. REQUIRED
 SUBMITTALS:
  
 1) ALL REQUIRED SUBMITTALS FOR THE STRUCTURE ALONG WITH
 ENGINEERED PLANS, SHOP DRAWINGS INCLUDING ENGINEERING
 CALCULATIONS.
 2) LETTER FROM A LICENSED THRESHOLD INSPECTOR STATING
 THAT AN INSPECTION WILL BE MADE AT THE MANUFACTURES
 SITE OF THE JOB SPECIFIC COMPONENTS TO VERIFY
 CONSTRUCTION COMPLIANCE OF THE COMPONENTS WITH THE
 ENGINEERED DESIGN.
  
 DURING CONSTRUCTION SUBMITTALS:
 THREE SETS OF PLANS, DOCUMENTS, REPORTS , PRODUCT
 APPROVALS AND SUBMITTALS.
 1) CERTIFICATE OF COMPLIANCE AFFADAVIT FROM THE
 THRESHOLD INSPECTOR THAT, TO THE BEST OF HIS/ HER
 KNOWLEDGE AND BELIEF, THE OFF-SITE CONSTRUCTION
 COMPONENTS OUTLINED HEREIN AND INSPECTED UNDER HIS/ HER
 AUTHORITY HAVE BEEN COMPLETED IN CONFORMANCE WITH THE
 APPROVED PLANS, SHOP DRAWINGS AND ENGINEERING.ALSO,
 PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION SERVICES
 MANAGER - TEL:
 561 805 6711), A MEETING INVOLVING THE
 THRESHOLD INSPECTOR, JOB INSPECTOR, CONTRACTOR AND
 ENGINEER.
  
 15A) TABLE 602 REQUIREMENTS FOR EXTERIOR WALLS BASED ON
 FIRE SEPERATION DISTANCE, PLEASE PROVIDE THE DISTANCES
 FROM THE EXISTING STRUCTURES ALSO ON THIS SAME LOT. IT
 APPEARS THE STRUCTURES MAY BE CLOSER THAN 20'-0", THIS
 WILL AFFECT AN ASSUMED PROPERTY LINE BETWEEN BUILDINGS
 ON THE SAME LOT.503.1.3, TABLE 601,602,704.8. 715.3 AND
 715.4. IF ASSUMING NO FIRE SEPERATION IS REQUIRED
 BETWEEN BUILDINGS, (ASSUMED ONE LARGE BUILDING) PROVIDE
 THE TOTAL SQUARE FOOTAGE OF ADJACENT BUILDINGS
 FOOTPRINT.
  
 15B) PLANS INDICATE THE CONCRETE THICKNESSOF THE
 WALLS LTO BE 2" THICK, IF FIRE RESISTANCE WILL BE
 REQUIRED BETWEEN BUILDINGS PLEASE PROVIDE THE
 EQUIVALENT THICKNESS OF PRECAST CONCRETE WALL, SEE
 TABLE 721.2.1.1 OR 721.2.1.1.4.(RIBBED OR UNDULATING
 SURFACES).
  
 16) SHEET S-3 INDICATES A STEEL BEAM IN SECTIONS A-A NO
 MENTION AS TO SIZE OR WEIGHT OF BEAM? 106.1.2.*
 ADMINISTRATIVE CODE.
  
 17) THERE IS NO DBA OR CERTIFICATE OF AUTHORIZATION FOR
 BRUH-HOSEIN-RUPP AT DPBR.) 481.219 F.S.CERTIFICATE
 OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 18) SHEET S-3 VARIOUS SECTIONS SHOW A 3/4" =1'-0",
 WRONG SCALE DETAIL# 3 AND SECTION A-A.BEFORE A
 PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 .NOTE : ADDITIONAL COMMENTS MAY APPEAR ON THE NEXT
 REVIEW DUE TO COMMENT RESPONSE OR ADDITIONAL NEW
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  