Plan Review Notes For Permit 06120338 |
Permit Number |
06120338 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-01-12 16:48:38 | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | 1} 700.8 SIGNS. | | (A) EMERGENCY SOURCES. A SIGN SHALL BE PLACED AT THE | | SERVICE ENTRANCE EQUIPMENT INDICATING TYPE AND LOCATION | | OF ON-SITE EMERGENCY POWER SOURCES. | | | | 2} PROVIDE A PANEL SCHEDULE FOR THE CIRCUITS IN THE | | ATS. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW. | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|