Plan Review Notes
Plan Review Notes For Permit 06120320
Permit Number 06120320
Review Stop E
Sequence Number 3
Notes
Date Text
2007-06-07 07:31:20** UNSAT **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEWS STILL
 ARE IN NEED OF ADDRESSING ALONE WITH SOME NEW COMMENTS
 DUE TO CHANGES MADE ON PLANS AND DOCUMENTS SUBMITTED.
  
 1) NOTE: PLEASE THE PERMIT APPLICATION AND PLANS NEED
 TO COORDINATE FOR SUITE/UNIT NUMBER. THE PERMIT
 APPLICATION STILL ONLY INDICATES *3RD FLOOR*. THE TITLE
 BLOCKS NOW INDICATE SUITE 300, YET THE ELECTRICAL RISER
 SHOWS SUITE #360 FOR THIS NEW SPACE. ???
 PLEASE ALSO SEEBOTH THE *RISER* AND THE * SCHEDULE OF
 SERVICE BLOCK* DONE ON E5.1 WHICH INDICATE SUITES. THIS
 INFORMATION HAS ALSO BEEN FORWARDED TO THE ADDRESSING
 REVIEWER AS AN ADDRESS FOR SUITE/UNIT MOST LIKELY CAN
 NOT BE ASSESSED.
 ** PLEASE KNOW PLANS NEED TO CORRELATE ALL WITH THE
 APPLIED LOCATION.
 FAC 61G1-16.004
 FBC ADMINSECTION 106.1.2
  
 2) NOTE: PLEASE SEE THE ENERGY CALCULATIONS NOW
 SUBMITTED DO NOT COORDINATE WITH THE SUBMITTED PLANS.
 PLEASE SEE THE NUMBER OF LIGHTING FIXTURES, THE
 WATTAGE, TYPES AND CONTROLS FOR SUCH FIXTURES DOES NOT
 MATCH WITH PLANS.
 PLEASE ADJUST.
 PLEASE SEE LEGEND AS THE OVER RIDE/AUTOMATED CONTROL
 TIME IS NOW STATED FOR SMS.
 PLEASE SEE THE ROOM WHICH APPEARS TO BE RIGHT NEXT TO
 PANTRY INDICATES A STANDARD S DEVICE.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, 13-415.1.AB.1.1,
 13-415.2
 PLEASE SEE THE ENERGY CALCULATIONS WILL REQUIRE TO BE
 SIGNED BY *OWNER AGENT* AS INDICATED ON SHEET
 2.
  
 3) NOTE: PLEASE SEE SHEET E0.1 WHICH INDICATES A 2005
 FBC?
 PLEASE SEE NO YEARS INDICATE FOR ELECTRICAL CODE
 NFPA-70 OR LIFE SAFETY CODE NFPA-101. THESE SHOULD BE:
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70 (NEC).
 2003 NFPA-101
  
 4) NOTE: ** PLEASE KNOW THE PANEL SCHEDULE WILL BE
 REQUIRED TO BE REVISED ON PLANS TO INDICATE EACH
 ROOM/AREA FOR CIRCUITING TO BE SPECIFIC AS REQUIRED IN
 408.4. THIS DOES NOT HAVE TO BE DONE AT TIME DUE TO
 MANY OF THE CIRCUITS NOT KNOWN IN THE EXISTING AREA AT
 THIS TIME. THIS WILL DONE AS A *PROVISO* (CONDITION OF
 ISSUANCE) AFTER OTHER COMMENTS ARE ADDRESSED.
 THIS IS ONLY BEING DONE FOR THIS PROJECT ALL OTHERS FOR
 NEW CONSTRUCTION WILL REQUIRE ALL ROOMS AND AREAS TO BE
 SPECIFIC ON SCHEDULE.
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-06-06 21:08:16REVIEW TO CONTINUE ON 6/7
2007-06-06 20:49:45IN ELEC FOR REVIEW