Plan Review Notes
Plan Review Notes For Permit 06120320
Permit Number 06120320
Review Stop P
Sequence Number 2
Notes
Date Text
2007-03-19 11:45:44DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW****
 COMMENT NUMBER SHALL REMAIN THE SAME.
  
 1. OK
 2. OK
  
 3. ALL ARCHITECTURAL SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING:THE FIRM LICENSE
 NUMBER & THE PRINTED NAME OF THE PERSON SEALING THE
 DOCUMENT. FAC 61G1-16.004(2)(6) & FS 481.219,
 481.2055.
 ****NO RESPONSE SHEET SUBMITTED FOR PLUMBING COMMENTS.
 THE BUSINESS NUMBER GIVEN ON THE PLANS DOES NOT REFLECT
 THE FLORIDA DBPR WEBSITE. (SEE ATTACHED SHEET).
  
 4. OK
 5. OK
  
 6. SHTS A1.03 & A7.031 DETAIL 8. THE PANTRY SINK SHALL
 COMPLY WITH SECTION 11-4.24 AND ALL SUBSECTIONS. SHOW
 THE FOLLOWING:
 A. OK
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD APPROACH
 EXTENDING A MAXIMUM 19" UNDERNEATH THE SINK IS
 REQUIRED. CABINET DOORS ARE NOT APPROVED.
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 E. 11-4.24.7 FAUCET.
 ****THE SINK DEPTH IS NOT SHOWN, - THE CABINET DOORS
 ARE STILL SHOWN. - EXPOSED PIPES & SURFACES NOT
 ADDRESSED. - ADA COMPLIANT FAUCET NOT SUFFICIENT
 INFORMATION. INDICATE BRAND AND MODEL NUMBER AND
 INDICATE FAUCET HANDLE TYPE TO SHOW COMPLIANCE.
  
 7. OK
 8. OK
  
 ************NEW COMMENT************
  
 1B. THE DATE THAT THE SEAL AND SIGNATURE ARE AFFIXED TO
 EACH SHEET SHALL BE INDICATED. MANY ARCHITECTURAL
 SHEETS ARE NOT DATED. FAC 61G1-16.003, 61G1-16.004(5)
 AND FS 481.2055. PLEASE CHECK ALL SHEETS PRIOR TO
 RESUBMITTING.
  