Plan Review Notes
Plan Review Notes For Permit 06120320
Permit Number 06120320
Review Stop E
Sequence Number 2
Notes
Date Text
2007-03-11 11:02:59** UNSAT 2ND REVIEW **
  
 222 LAKEVIEW
 3RD FLOOR BUILD-OUT
  
  
 1) NOTE: PLEASE SEE MISSING ADDRESS INFORMATION FROM
 TITLE BLOCKS. PLEASE SEE THE SUITE/UNIT NUMBER IS NOT
 BEING SHOWN. PLEASE SEE NOW THE ADDRESS OF 222 IS ON
 PLANS HOWEVER THE SUITE NUMBER IS NOT? 61G1-16.004,
 FAC61G15-23.002
  
 2) NOTE: PLEASE SEE MISSING COMPLETE INFORMATION FOR A
 TITLE BLOCK FOR THE ARCHITECT OF RECORD AND FIRM.
 PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION NUMBER
 ALSO KNOW AS FIRM LICENSE NUMBER.
 FLORIDA ADMINISTRATIVE CODE 61G1-16.004, FLORIDA
 STATUTES 481.219
 **THIS IS NOT A COMMENT RELATED TO KAMM CONSULTING,
 HOWEVER TITLE BLOCKS ARE REQUIRED FOR ALL SHEETS PER
 ABOVE AND WHETHER OR NOT COMMENT IS MADE BY ANY OTHER
 TRADE.
  
 3) NOTE: PLEASE SEE MISSING LIGHTING CONTROL FOR ALL
 PER 13-415.1.ABC.1.1, .1.2, AND .1.3.PLEASE SEE ROOMS
 03-002, AND 03-003.
 PLEASE SEE THE SYMBOL LEGEND FOR ALL DEVICES SHALL
 INDICATE ALL MAXIMUM TIMES FOR DEVICES. (30MINS FOR
 OCCUPANCY SENSOR TYPE AND 4HRS MAX FOR TIMER TYPE)
 PLEASE SEE 13-415.2, 13-415.2.ABC.1 FOR MISSING MAXIMUM
 PERMITTED LIGHTING POWER DENSITIES.
 PLEASE ALSO SEE 13-415.AB.1 FOR MISSING ENERGY
 CALCULATIONS REQUIRED FOR NEW TENANT BUILD-OUT.
 ** PLEASE SUBMIT THE ABOVE. AS THERE ARE ITEMS NOT YET
 SUBMITTED, A REVIEW OF SAID SYSTEM/DEVICES ETC CAN NOT
 BE FULLY ACCOMPLISHED AT THIS TIME.
  
 4) NOTE: PLEASE KNOW THAT NOW THAT THE SUITE/UNITS ARE
 CLEARER, PLEASE SEE IT APPEARS ANOTHER SERVICE FOR THE
 SAME TENANT SPACE IS BEING ADDED? PLEASE KNOW AS THERE
 IS ONLY ONE TENANT AND ONE OCCUPANCY; ONLY ONE METER
 WILL BE PERMITTED. PLEASE ADJUST RISER AS SHOWN.
 PLEASE CALL TO GO OVER IF NEEDED.
 PLEASE SEE THIS MAY ALSO BE COMMENTED ON FROM
 ZONING/BUILDING FOR SINGLE OCCUPANCY.
 FBC ADMIN SECTION 104.6
  
 5) NOTE:** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDEDSHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.PLEASE KNOW ONLY
 ONE SET OF THE OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved