Plan Review Notes For Permit 06120320
Permit Number 06120320
Review Stop B
Sequence Number 2
Notes
Date Text
2007-03-30 16:23:35BUILDING PLAN REVIEW
 PERMIT: 06120320
 ADD: 222 LAKEVIEW AVE 3RD FLOOR
 CONT: PASS INTERNATIONAL
 TEL: (561)706-7201
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID.
 NOTE: 713.13(6)THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3A)2ND REQUEST, THE MEP, FA AND FS SHEETS ARE STILL
 MISSING THE CERTIFICATE OF AUTHORIZATION FOR ASSOCIATED
 SPACE DESIGN.
 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 3 B-C)OK
  
 3D) 2ND REQUEST, BUILDING FEATURES, TYPE OF
 CONSTRUCTION, TYPE I UNPROTECTED, SPRINKLERED. PLEASE
 SEE
 TABLE 503, TYPE I BUILDINGS ARE EITHER AOR B FOR
 ALLOWABLE STORIES. RESPONCE WAS WE ARE NOT ADDING ANY
 STORIES.
 WHILE THIS IS TRUE NO STORIES ARE BEING ADDED THE
 AMOUNT OF FIRE SAFING BUILT INTO THE BUILDING IS
 DETERMINED IF THE BUILDING EXCEEDS A CERTIAN LIMIT IN
 FT. TABLE 503
 WHILW A TYPE IB BUILDING IS LIMITED TO 160' A TYPE IA
 BUILDING IS UNLIMITED IN HEIGTH. TABLE 601 PROVIDES THE
 DIFFERENCE IN FIRE RATINGS BETWEEN A TYPE IA OR A IB.
 PLEASE PROVIDE FOOTAGE IN HEIGTH, SO THE CORRECT FIRE
 SAFING REQUIREMENTS WILL BE MEET IN THE NEW FLOOR DECK
 AREA.
  
 4)2ND REQUEST,A7.041 DETAIL# 1 PANTRY, THE
 ELEVATIONS FAIL TO SHOW COMPLIANCE
 FOR A FORWARD APPROACH. THE DOORS FLOORAND SHELVING
 WOULD NEED TO BE REMOVED
 TO ALLOW FOR THE FORWARD APPROACH USAGE.
 T SINKS:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH
 SECTION 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A SINK
 TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK.
  
 5) 2ND REQUEST NUMBER (7) FROM THE PREVIOUS REVIEW, THE
 WORK TO BE INCLUDED IN THIS PERMIT , ADDITIONAL JOIST
 4TH FLOOR WILL REQUIRE A THRESHOLD INSPECTOR ONSITE
 DURING THIS PORTION OF WORK.
 WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 6) THE THRESHOLD INSPECTION PLAN HAS A STAMPED
 SIGNATURE NOT AH ORIGINAL. PLANS, SPECIFICATIONS,
 REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 NOTE: 3 SETS OF THE THRESHOLD INSPECTION PLAN WILL BE
 RQUIRED AS WELL ASSETS OF PLANS, "THRESHOLD
 BUILDING".
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
 .