2007-02-07 18:55:53 | *****DENIED***** |
| |
| |
| 1.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK |
| WILL BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH |
| SUBMITTED PLAN SHEET. |
| |
| 2.ON SHEET A0.00, MAKE THE FOLLOWING CHANGES TO THE |
| CODE ANALYSIS SECTION:I.AUTHORITIES CONSTRUCTION |
| SERVICES DEPARTMENT - CITY OF WEST PALM BEACH |
| 561-805-6700;FIRE MARSHAL - MIKE CARSILLO |
| 561-804-4724II. APPLICABLE BUILDING CODES |
| ELIMINATE NFPA 2003 CODES W/FLORIDA AMENDMENTS, INSERT |
| FLORIDA FIRE PREVENTION CODE 2004 |
| |
| 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD |
| TO GENERAL DEMOLITION NOTES, SHEET AD1.03 |
| |
| 4.DO THE TENANT ENTRY DOORS (AS REFERRED TO ON SHEET |
| A9.032) LEAD TO AN EXIT ACCESS CORRIDOR?IF SO, THESE |
| DOORS SHALL BE FIRE RATED AS PER NFPA 80. |
| |
| 5.ON SHEET FA0.1, FIRE ALARM NOTE #17, DELETE |
| SUPERVISORY SIGNAL ONLY - INSERT GENERAL FIRE ALARM |
| |
| 6.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM. WILL |
| THEY NEED TO BE ALTERED OR MODIFIED DUE TO THE SCOPE OF |
| WORK? |
| |
| 7.BUILDINGS OR PORTIONS OF BUILDINGS SHALL BE |
| PERMITTED TO BE OCCUPIED DURING CONSTRUCTION, REPAIR, |
| ALTERATIONS, OR ADDITIONS ONLY WHERE REQUIRED MEANS OF |
| EGRESS AND REQUIRED FIRE PROTECTION |
| FEATURES ARE IN PLACE AND CONTINUOUSLY MAINTAINED FOR |
| THE PORTION OCCUPIED OR WHERE ALTERNATIVE LIFE SAFETY |
| MEASURES ACCEPTABLE TO THE AUTHORITY HAVING |
| JURISDICTION ARE IN PLACE. |
| |
| 8.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF |
| NEW BUILDING MATERIALS & SUPPLIES SHALL NOT HINDER OR |
| INTERFERE WITH ACCESS TO OR EXIT FROM FLOOR AND/OR |
| BUILDING (INCLUDING FIRE LANES). |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. |
| |
| |
| CAPT. MICHAEL A. WILLIAMS |
| FIRE PLAN REVIEW |
| 561-805-6722 |