Plan Review Notes
Plan Review Notes For Permit 06120320
Permit Number 06120320
Review Stop E
Sequence Number 1
Notes
Date Text
2007-01-07 19:04:59** UNSAT **
  
  
 222 LAKEVIEW
 3RD FLOOR BUILD-OUT
  
  
 1) NOTE: PLEASE SEE MISSING ADDRESS INFORMATION FROM
 TITLE BLOCKS. PLEASE SEE THE SUITE/UNIT NUMBER IS BEING
 SHOWN, HOWEVER NOT THE ADDRESS/ LOCATION.
 FAC 61G1-16.004, FAC61G15-23.002
  
 2) NOTE: PLEASE SEE MISSING COMPLETE INFORMATION FOR A
 TITLE BLOCK FOR THE ARCHITECT OF RECORD AND FIRM.
 PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION NUMBER
 ALSO KNOW AS FIRM LICENSE NUMBER.
 PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER
 FOR ARCHITECT.
 FLORIDA ADMINISTRATIVE CODE 61G1-16.004, FLORIDA
 STATUTES 481.219
 **THIS IS NOT A COMMENT RELATED TO KAMM CONSULTING,
 HOWEVER TITLE BLOCKS ARE REQUIRED FOR ALL SHEETS PER
 ABOVE AND WHETHER OR NOT COMMENT IS MADE BY ANY OTHER
 TRADE.
  
 3) NOTE: PLEASE LIST THE FOLLOWING MINIMUM CODES
 RELEVANT TO THIS PROJECT AND DESIGN.
 2005 NFPA-72, 2005 NFPA-70, 2003 NFPA-101
 PLEASE ADJUST THE ARCHITECTURAL SHEETS AS WELL AS THE
 ELECTRICAL SHEETS.
 PLEASE SEE AS THE PERMIT WAS APPLIED FOR AFTER DECEMBER
 8TH, 2006 THE 2006 REVISIONS TO THE 2004 FBC AND THE
 2005 NATIONAL ELECTRICAL CODE WAS ADOPTED BY THE STATE
 OF FLORIDA.
 PLEASE ADJUST CODES ON PLANS.
  
 4) NOTE: PLEASE SEE MISSING LIGHTING CONTROL FOR ALL
 PER 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE
 MISSING CONTROLS FOR COMMON AREAS. PLEASE SEE OVER
 RIDES DEVICES FOR THESE AREAS ALSO DEPENDING ON
 "SYSTEM" OR DEVICES CHOSEN. PLEASE SEE THE SYMBOL
 LEGEND FOR ALL DEVICES SHALL INDICATE ALL MAXIMUM TIMES
 FOR DEVICES. (30MINS FOR OCCUPANCY SENSOR TYPE AND 4HRS
 MAX FOR TIMER TYPE)
 PLEASE SEE ROOMS AND AREAS WHICH DO NOT INDICATE ANY OF
 THE DEVICES FOR AUTOMATED CONTROL.
 PLEASE PROVIDE SCHEDULING FOR ANY PROPOSED SYSTEM.
 PLEASE SEE ALL AREAS CONTAIN FLOOR TO CEILING HEIGHT
 PARTITIONS SHALL CONTAIN DEVICE(S) FOR CONTROL. (PLEASE
 SEE STORAGE)
 PLEASE SEE 13-415.2, 13-415.2.ABC.1 FOR MISSING MAXIMUM
 PERMITTED LIGHTING POWER DENSITIES.
 PLEASE ALSO SEE 13-415.AB.1 FOR MISSING ENERGY
 CALCULATIONS REQUIRED FOR NEW TENANT BUILD-OUT.
 ** PLEASE SUBMIT THE ABOVE. AS THERE ARE ITEMS NOT YET
 SUBMITTED, A REVIEW OF SAID SYSTEM/DEVICES ETC CAN NOT
 BE FULLY ACCOMPLISHED AT THIS TIME.
  
 5) NOTE: PLEASE PROVIDE A DETAIL ON ALL EMERGENCY
 AND/OR EXIT LIGHTING WIRED AHEAD OF ANY OVER RIDE
 CONTROL DEVICES PER 700.12E. PLEASE SEE A
 CLOUDED/HIGHLIGHTED NOTE MAY ALSO BE DONE. THIS AHJ HAS
 BEEN HAVING MANY INSTANCES WHERE EMERGENCY AND EXIT
 LIGHTS ARE BEING WIRED ON THE LOAD SIDE OF OC/ TIMER
 DEVICES.
  
 6) NOTE: PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%.
 215.3, 230.42 ETC.
 FBC 106.1.2 ADMIN SECTION.
  
 7) NOTE: PLEASE KNOW EITHER AT THIS POINT OR BEFORE
 FINAL, A REVISION FOR ALL CIRCUITS TO SPECIFIC ROOMS
 AND AREAS WILL BE REQUIRED. (LIGHTING CIRCUITS ETC.)
 408.4.
  
  
 8) NOTE: PLEASE SEE THE PANELS H3B AND L3B ARE BEING
 SHOWN IN A STORAGE ROOM WHICH IS NOT PERMITTED. 110.26,
 408.7, 240.24D
  
 9) NOTE: PLEASE INDICATE A FLOATING NEUTRAL IN NEW
 METER AS THIS IS AFTER THE FIRST MEANS OF DISCONNECT.
 250.6, 250.24B.
  
 10) NOTE: PLEASE SEE "S" SHEET IN BOTH SETS ARE NOT
 SIGNED AND DATED BY THE ENGINEER OF RECORD. SHEETS DO
 CONTAIN THE RAISED SEAL.
 PLEASE SEE FS 471.025, FAC 61G15-23.002
 THIS IS ONLY NOTED AND SHOULD ALSO BE IN NOTES FROM THE
 BUILDING REVIEWER.
  
 11) NOTE: PLEASE SEE THE LOW VOLTAGE AUDIO/VISUAL PLANS
 SUBMITTED MAY ONLY BE PART OF THE PERMITTED RECORD SET
 OF PLANS IF BEING DONE BY THE ELECTRICAL SUB
 CONTRACTOR. AS THESE SHEETS SEEM TO INDICATE A SEPARATE
 LV SOUND/AUDIO VISUAL CONTRACTOR, THESE SHALL BE
 SUBMITTED UNDER A SEPARATE PERMIT APPLICATION. PLEASE
 KNOW IN EITHER CASE ALL PLANS ARE REQUIRED TO BE
 SIGNED, DATED PRINTED NAME ETC FOR THE PERSON TAKING
 RESPONSIBILITY OF SUCH PLANS.
  
 12) NOTE:** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDEDSHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.PLEASE KNOW ONLY
 ONE SET OF THE OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]