2007-01-16 11:04:56 | BUILDING PLAN REVIEW |
| PERMIT: 06120320 |
| ADD: 222LAKEVIEW |
| CONT: PASS INTERNATIONAL |
| TEL: (954)421-9000X113 |
| |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1STREVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2 ) FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| THE COURT. |
| NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE |
| RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: |
| 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT |
| THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| |
| 3) SHEET A0.00 |
| |
| 3A)ARCHITECTURAL SHEETS ASD, AKERMAN SENTERFITTARE |
| MISSING THE CERTIFICATE OF AUTHORIZATION. 481.219 F.S. |
| CERTIFICATE OF |
| AUTHORIZATION.THE TITLE BLOCK FOR ANY |
| SHEET BEARING THE NAME OF AN ARCHITECT |
| PRACTICING UNDER A FICTITIOUS NAME, A |
| CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL |
| SERVICES, SHALL INCLUDE |
| THE CERTIFICATE OF AUTHORIZATION |
| NUMBER.ADD THE NUMBER TO EACH SHEET. |
| THIS MAY BE ADDED BY HAND. |
| |
| |
| 3B) ARCHITECT STEVEN D. YANCEY IS MISSING PRINTED |
| NAME: |
| ) 61G1-16.004FL. ADMIN. CODE.PLANS |
| PREPARED BY A REGISTERED ARCHITECT SHALL |
| INCLUDE A TITLE BLOCK WHICH MUST: |
| - STATE THE FIRM NAME, ADDRESS AND |
| TELEPHONE NUMBER |
| - STATE THE FIRM LICENSE NUMBER |
| - STATE PROJECT NAME OR IDENTIFICATION |
| - STATE DATE PREPARED |
| - INCLUDE AN ORIGINAL SIGNATURE AND |
| DATED SEAL |
| X - INCLUDE THE PRINTED NAME OF THE |
| ARCHITECT SEALING THE PLANS |
| |
| 3C) APPLICABLE BUILDING CODE: PLANS INDICATE PBC |
| AMENDMENTS PLEASE DELETE, |
| INTHE 2004 FBC THE ONLY LOCAL AMENDMENTS ARE CHAPTER |
| (1) ADMINISTRATION- CITY OF WEST PALM BEACH . |
| |
| 3D) BUILDING FEATURES, TYPE OF CONSTRUCTION, TYPE I |
| UNPROTECTED, SPRINKLERED. PLEASE SEE TABLE 503 TYPE I |
| BUILDING COLUMN A & B FOR ALLOWABLE STORIES. |
| |
| 4) A7.031 DETAIL# 8 PANTRY, THE ELEVATIONS FAIL TO SHOW |
| COMPLIANCE FOR A FORWARD APPROACH. SINKS: |
| 11-4.24.2 SINKS, HEIGHT. SINKS SHALL |
| BE MOUNTED WITH THE COUNTER NO HIGHER |
| THAN 34" ABOVE THE FINISH FLOOR. |
| 11-4.24.3 KNEE CLEARANCE THAT IS AT |
| LEAST 27" HIGH 30" WIDE, AND 19" DEEP |
| SHALL BE PROVIDED UNDERNEATH SINKS. |
| 11-4.24.5 CLEAR FLOOR SPACE. |
| A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES |
| (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4 |
| SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD |
| APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN |
| ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19 |
| INCHES (485 MM) UNDERNEATH THE SINK |
| |
| 5) SHEET A9.032 INDICATES THEUSE OF A DOOR TYPE "D" |
| WHICH HAS A VIEW PANEL , PLEASE NOTE REQUIREMENTS FOR |
| SAFETY GLAZING. |
| 2406.3 HAZARDOUS LOCATIONS. |
| THE FOLLOWING SHALL BE CONSIDERED SPECIFIC HAZARDOUS |
| LOCATIONS REQUIRING SAFETY GLAZING MATERIALS: |
| 1.GLAZING IN SWINGING DOORS . |
| |
| 6)SHEET S-1; |
| 6A)PLANS ARE SEALED BUT NOT SIGNED. |
| PLANS, SPECIFICATIONS, REPORTS OR |
| OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND |
| BEING FILED FOR PUBLIC |
| RECORD SHALL HAVE THE SIGNATURE AND |
| SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| TO THE DOCUMENT. |
| FL STATE STAT: 61G15-23.002 ENGINEERS |
| FL ATATE STAT: 61G16.003 ARCHITECTS |
| |
| 6B)CODES AND STANDARDS: INDICATE DESIGNED TO THE 2001 |
| FBC, PLEASE CORRECT. |
| |
| 7) THE WORK TO BE INCLUDED IN THIS PERMIT , REMOVAL OF |
| ELEVATOR WALLS AND NEW FLOOR FRAMING ANDINFILL OF |
| FLOOR SLABS ON THE THIRD FLOOR AND ADDITIONAL JOIST 4TH |
| FLOOR WILL REQUIRE A THRESHOLD INSPECTOR ONSITE DURING |
| THIS PORTION OF WORK. |
| WPB AMENDMENT 105.13.6. W.P.B. |
| CONSTRUCTION SERVICES DEPARTMENT |
| REQUEST FOR THRESHOLD BUILDINGS A |
| SPECIAL INSPECTOR AS REQUIRED BY S. |
| 553.79(5) FLORIDA STATUTES TO THE MIN- |
| IMUM INSPECTIONS REQUIRED BY THIS CODE. |
| CONTACT HAROLD PISKURA MANAGER OF THE |
| SPECIAL INSPECTOR PROGRAM AT (561) |
| 805-6711 FOR FURTHER INFORMATION BEFORE |
| THE PERMIT MAY BE ISSUED. |
| |
| FL S. S. 553.71(7) " THRESHOLD |
| BUILDING" MEANING ANY BUILDING WHICH IS |
| GREATER THAN (3) STORIES OR 50 FT IN |
| HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN |
| CY CLASSIFICATION AS DEINED IN THE |
| FLORIDA BUILDING CODE WHICH EXCEEDS |
| 5,000 SQ FT IN AREA AND AN OCCUPANT |
| CONTENT OF GREATER THAN 500 PERSONS. |
| 105.13.1 THE ENFORCING AGENCY SHALL |
| REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| STRUCTURAL INSPECTIONS ON A THRESHOLD |
| BUILDING PURSUANT TO A STRUCTURAL |
| INSPECTION PLAN PREPARED BY THE |
| ENGINEER OF RECORD. THE STRUCTURAL |
| INSPECTION PLAN MUST BE SUBMITTED TO THE |
| ENFORCING AGENCY PRIOR TO THE ISSUANCE |
| OF A BUILDING PERMIT FOR THE |
| CONSTRUCTION OF A THRESHOLD BUILDING. |
| THE PURPOSE OF THE STRUCTURL INSPECTION |
| PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| PROCEDURES AND SCHEDULES SO THAT THE |
| BUILDING CAN BE ADEQUATELY INSPECTED FORCOMPLIANCE |
| WITH THE PERMITTED DOCUMENTS. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER C. B. O. |
| |