Plan Review Notes
Plan Review Notes For Permit 06120319
Permit Number 06120319
Review Stop E
Sequence Number 5
Notes
Date Text
2007-08-29 10:51:252007-08-29 10:51:25
 SPOKE TO GORDAN SCOTT AND MR. LON CARTER (ENGINEER OF
 RECORD).
 NEW PLANS ARE BEING BROUGHT UP FOR INSERTTING INTO THE
 SETS.
 WALLS WILL NEED TO BE MOVED WHICH WILL REQUIRE NEW *A*
 SHEETS.
  
 ON HOLD.
2007-08-29 07:41:422007-08-29 07:41:42
 ** DENIED 5TH REVIEW **
  
 1) NOTE: PLEASE SEE PREVIOUS NOTE #2 WHICH REQUESTED TO
 MEET SEVERAL SECTIONS OF THE CODE FOR CLEARANCES OF THE
 TRANSFORMER(S) AND DISCONNECTS. BY SIMPLY PLACING A
 NOTE ON THE PLANS WHICH STATES *DISCONNECTS AND
 TRANSFORMER(S) WILL BE RELOCATED* DOES NOT SHOW CODE
 COMPLIANCE AS REQUIRED ON PLANS.
 PLEASE SUBMIT PLANS SHOWING NEW LOCATION(S) MEETING THE
 *MINIMUM* CODE. THIS OFFICE HAS ONLY REQUESTED THE
 MINIMUM CODE FROM THE FIRST REVIEW FOR THIESE SAME
 ITEMS. FBC 106.1.1, 106.1.2, 106.3.5.1.2.
 FLORIDA ADMINISTRATIVE CODE 61G15-33.003 (2)(D) PLEASE
 KNOW THAT ONCE THE LOCATION(S) MEETS 110.26, 240.24,
 240.21, 450.9, 450.13 ETC THE PERMIT CAN BE ISSUED.
  
 ** A CALL WILL BE PLACED TO THE ENGINEER'S OFFICE ONE
 UNDER NORMAL BUSINESS HOURS TO TRY AND RESOLVE THE
 ISSUE.
  
 ** PLANS ARE BEING ROUTED TO THE BUILDING REVIEWER AS A
 NEW ARCHITECTURAL SHEET WAS INSERTED INTO PLANS.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]