Plan Review Notes For Permit 06120319 |
Permit Number |
06120319 |
|
Review Stop |
P |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2007-08-20 18:09:01 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 BUILDING | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | FROM PREVIOUS REVIEW: | | (COMMENT NUMBERS TO REMAIN THE SAME) | | ********FROM PREVIOUS REVIEWS: | | | | 1. OK | | 2. OK | | 3. OK | | 4. OK | | 5. OK | | 6. OK | | A. OK | | B. OK | | C. OK | | D. OK | | E. OK | | | | 7. SHOW THE FIXTURES REQUIRED BY SECTION 1004.1.3 | | (BLDG) & 403.1 MINIMUM FACILITIES. INDICATE ON THE | | FLOOR PLAN THE DRINKING FOUNTAINS. SECTION 106.1.1. | | ****NO RESPONSE. NOT ADDRESSED. | | ******RESPONSE NOTED, BUT TABLE 403.1 REQUIRES 3 | | DRINKING FOUNTAINS, AND ONLY ONE IS INDICATED. PLEASE | | SHOW ALL 3 DRINKING FOUNTAINS REQUIRED. | | *********RESPONSE NOTED, BUT 3 DRINKING FOUNTAINS ARE | | REQUIRED AND ONLY ONE WAS ADDED. AS THERE WAS ONLY ONE | | DRINKING FOUNTAIN INDICATED TO BEGIN WITH, THE ADDED | | ONE ONLY BRINGS THE TOTAL UP TO TWO. PLEASE INDICATE | | THREE DRINKING FOUNTAINS AS REQUIRED. | | | | 8. OK | | | | ********NEW COMMENT******** | | | | 1B. SHT P2.1 THE WATER HAMMER ARRESTOR AT THE DRINKING | | FOUNTAIN SHALL BE LOCATED NEAR THE FIXTURE IN AN | | "EFFECTIVE RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH | | 201 AND MANUF. INSTALLATION INSTRUCTIONS. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|