Plan Review Notes
Plan Review Notes For Permit 06120319
Permit Number 06120319
Review Stop E
Sequence Number 4
Notes
Date Text
2007-07-31 18:37:51*** UNSAT 4TH REVIEW ***
  
 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED
 DO NOT CORRELATE WITH THE PLANS FOR THE METHOD OF
 CONTROL. PLEASE SEE THESE ARE STILL BEING ENTERED AS
 *MANUAL ON/OFF* WHEN THEY ARE AUTOMATED/OCCUPANCY TYPE
 DEVICES ON PLANS.
 PLEASE COORDINATE. 13-415.1.AB.1.1, 13-415.1.A,
 13-415.2.
 PLEASE CLARIFY METHOD AND HOW THIS CAN BE USED FOR
 SCOPE OF WORK AS SHOWN. PLEASE CLARIFY LIGHTING POWER
 DENSITIES AS REQUESTED ON THE PREVIOUS THREE REVIEWS.
 THE RESPONSE LETTER DOES NOT ADDRESS OR MENTION THESE
 ITEMS???
 PLEASE SEE THESE ARE TO BE SIGNED BY THE ENGINEER OF
 RECORD WITH SIGNATURE AS ON FILE AND RECOGNIZED BY THIS
 OFFICE. PLEASE SEE THESE ARE NOT THE SAME AS THE PLANS
 OR PREVIOUS SUBMITTED ENERGY CALCULATIONS.
 13-103.1.1.1, FS471.025
  
 2) NOTE: PLEASE SEE THE PLANS HAVE NOT CHANGED FOR THE
 LOCATIONS OF DISCONNECTS. PLEASE SEE THE TRANSFORMER
 T1A WHICH IS BEING SHOWN IN SOME KIND OF CLOSET. THIS
 SAME CLOSET CONTAINS TWO SMALL RECTANGLES WHICH ARE NOT
 LABELED AS DISCONNECTS. AS THESE COULD NOT BE LOCATED
 AT ANY OTHER LOCATION ON PLANS, IT IS BEING ASSUMED
 THESE ARE THE SAME DISCONNECTS IN THIS SAME *CLOSET*.
 PLEASE SEE THESE DO NOT MEET 110.26, 240.24, 408.7 ETC
 AS PREVIOUSLY STATED IN PREVIOUS REVIEWS.
 ** ALL SERVICE EQUIPMENT NEW OR EXISTING WILL BE
 REQUIRED TO MEET THE MINIMUM REQUIRED BY CODE**
  
 **DOCUMENTATION HAS BEEN SENT TO THE CHIEF ELECTRICAL
 INSPECTOR FOR FIELD INSPECTION AND CORRECTION NOTICED
 TO BE ISSUED TO OWNER/JOBSITE AS/IF NEEDED.
  
 3) NOTE: PLANS AND SUPPORTING DOCUMENTS ARE BEING
 RETAINED BY THIS OFFICE DUE TO REPEAT CODE COMPLIANT
 COMMENTS PER FS 553.80(2)(B). AT THIS TIME A FEE OF
 $9,732.00 MAY BE ASSESSED DUE TO THE REPEAT COMMENTS
 FOR CODE COMPLIANCE. THE CODE COMMENTS WILL GO UNDER
 PIER REVIEW.
 THE FEE IS REQUIRED UNDER FLORIDA STATUTESAND WILL BE
 DUE BEFORE NEXT RESUB OF PLANS MAY BE DONE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  