2007-07-31 18:37:51 | *** UNSAT 4TH REVIEW *** |
| |
| 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED |
| DO NOT CORRELATE WITH THE PLANS FOR THE METHOD OF |
| CONTROL. PLEASE SEE THESE ARE STILL BEING ENTERED AS |
| *MANUAL ON/OFF* WHEN THEY ARE AUTOMATED/OCCUPANCY TYPE |
| DEVICES ON PLANS. |
| PLEASE COORDINATE. 13-415.1.AB.1.1, 13-415.1.A, |
| 13-415.2. |
| PLEASE CLARIFY METHOD AND HOW THIS CAN BE USED FOR |
| SCOPE OF WORK AS SHOWN. PLEASE CLARIFY LIGHTING POWER |
| DENSITIES AS REQUESTED ON THE PREVIOUS THREE REVIEWS. |
| THE RESPONSE LETTER DOES NOT ADDRESS OR MENTION THESE |
| ITEMS??? |
| PLEASE SEE THESE ARE TO BE SIGNED BY THE ENGINEER OF |
| RECORD WITH SIGNATURE AS ON FILE AND RECOGNIZED BY THIS |
| OFFICE. PLEASE SEE THESE ARE NOT THE SAME AS THE PLANS |
| OR PREVIOUS SUBMITTED ENERGY CALCULATIONS. |
| 13-103.1.1.1, FS471.025 |
| |
| 2) NOTE: PLEASE SEE THE PLANS HAVE NOT CHANGED FOR THE |
| LOCATIONS OF DISCONNECTS. PLEASE SEE THE TRANSFORMER |
| T1A WHICH IS BEING SHOWN IN SOME KIND OF CLOSET. THIS |
| SAME CLOSET CONTAINS TWO SMALL RECTANGLES WHICH ARE NOT |
| LABELED AS DISCONNECTS. AS THESE COULD NOT BE LOCATED |
| AT ANY OTHER LOCATION ON PLANS, IT IS BEING ASSUMED |
| THESE ARE THE SAME DISCONNECTS IN THIS SAME *CLOSET*. |
| PLEASE SEE THESE DO NOT MEET 110.26, 240.24, 408.7 ETC |
| AS PREVIOUSLY STATED IN PREVIOUS REVIEWS. |
| ** ALL SERVICE EQUIPMENT NEW OR EXISTING WILL BE |
| REQUIRED TO MEET THE MINIMUM REQUIRED BY CODE** |
| |
| **DOCUMENTATION HAS BEEN SENT TO THE CHIEF ELECTRICAL |
| INSPECTOR FOR FIELD INSPECTION AND CORRECTION NOTICED |
| TO BE ISSUED TO OWNER/JOBSITE AS/IF NEEDED. |
| |
| 3) NOTE: PLANS AND SUPPORTING DOCUMENTS ARE BEING |
| RETAINED BY THIS OFFICE DUE TO REPEAT CODE COMPLIANT |
| COMMENTS PER FS 553.80(2)(B). AT THIS TIME A FEE OF |
| $9,732.00 MAY BE ASSESSED DUE TO THE REPEAT COMMENTS |
| FOR CODE COMPLIANCE. THE CODE COMMENTS WILL GO UNDER |
| PIER REVIEW. |
| THE FEE IS REQUIRED UNDER FLORIDA STATUTESAND WILL BE |
| DUE BEFORE NEXT RESUB OF PLANS MAY BE DONE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |