Plan Review Notes
Plan Review Notes For Permit 06120319
Permit Number 06120319
Review Stop P
Sequence Number 3
Notes
Date Text
2007-06-18 08:25:25DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 (COMMENT NUMBERS TO REMAIN THE SAME)
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
  
 7. SHOW THE FIXTURES REQUIRED BY SECTION 1004.1.3
 (BLDG) & 403.1 MINIMUM FACILITIES. INDICATE ON THE
 FLOOR PLAN THE DRINKING FOUNTAINS. SECTION 106.1.1.
 ****NO RESPONSE. NOT ADDRESSED.
 ******RESPONSE NOTED, BUT TABLE 403.1 REQUIRES 3
 DRINKING FOUNTAINS, AND ONLY ONE IS INDICATED. PLEASE
 SHOW ALL 3 DRINKING FOUNTAINS REQUIRED.
  
 8. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]