Plan Review Notes
Plan Review Notes For Permit 06120319
Permit Number 06120319
Review Stop E
Sequence Number 3
Notes
Date Text
2007-06-08 09:56:28*** UNSAT 3RD ***
  
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEWS STILL
 ARE IN NEED OF ADDRESSING ALONE WITH SOME NEW COMMENTS
 DUE TO CHANGES MADE ON PLANS AND DOCUMENTS SUBMITTED.
  
 1) NOTE: PLEASE SEE THE PERMIT APPLICATION STILL
 INDICATES SCOPE OF WORK WHICH IS NOT THE SAME AS PLANS.
 THE PERMIT APPLICATION STATES *DESCRIBE PROJECT IN
 DETAIL* IF THE PERMIT APPLICATION STATES THE ENTIRE 4TH
 FLOOR IS BEING BUILD OUT FOR TENANT, THEN PLANS WILL BE
 REQUIRED TO BE REVISED TO SHOW CODE COMPLIANCE FOR THE
 ENTIRE FLOOR.
 PLEASE COORDINATE WITH ONE OR THE OTHER.
 PLEASE SEE THE PERMIT APPLICATION PACKAGE AS SUBMITTED
 DOES CONTAIN PAPERWORK AND DOCUMENTATION WHICH IS FROM
 THE THIRD FLOOR BUILD OUT WORK AND ANOTHER PERMIT.
 PLEASE COORDINATE ALL DOCUMENTS, PLANS, AND PAPERWORK.
 FBC 106.3.5.1.2
  
 2) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS NOW
 SUBMITTED DO NOT COORDINATE WITH THE SUBMITTED PLANS.
 PLEASE SEE THE NUMBER OF LIGHTING FIXTURES, THE
 WATTAGE, TYPES AND CONTROLS FOR SUCH FIXTURES DOES NOT
 MATCH WITH PLANS.
 PLEASE ADJUST.
 PLEASE SEE LEGEND AS THIS DOES NOT INDICATE ANY
 AUTOMATED TYPE DEVICE. THE TIMES ARE NOT STATED. THE
 PLANS DO NOT INDICATE DEVICES FOR NEW.
 PLEASE SEE13-101, 13-415.1.ABC.1.1, .1.2,
 13-415.1.AB.1.1, 13-415.2 HOW IS METHOD A ABLE TO BE
 SUED FOR THE SQ FT AS SHOWN AND FOR SCOPE OF WORK,
 PLEASE
 PLEASE SEE THE ENERGY CALCULATIONS WILL REQUIRE TO BE
 SIGNED BY *OWNER AGENT* AS INDICATED ON SHEET
 2.
  
 3) NOTE: PLEASE SEE SHEET E0.1 WHICH INDICATES A 2005
 FBC?
 PLEASE SEE NO YEARS INDICATE FOR ELECTRICAL CODE
 NFPA-70 OR LIFE SAFETY CODE NFPA-101. THESE SHOULD BE:
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70 (NEC).
 2003 NFPA-101
  
 4) NOTE: PLEASE SEE THE NEW DISCONNECTS ADDED FOR THE
 TAPPED CONDUCTORS TO PANEL L AND L1 DO NOT APPEAR ON
 PLANS AND LOCATIONS OF THESE CAN NOT BE VERIFIED FOR
 CODE COMPLIANCE OF 240.21, 110.26, 240.24 ETC
 PLEASE SHOW.
 FBC106.1.21
  
 5) NOTE: PLEASE SEE NO CHANGES OR NOTES HAVE BEEN ADDED
 FOR EXISTING AS SHOWN ELECTRICAL EQUIPMENT WHICH DOES
 NOT MEET 110.26,408.7, 240.24, 450.9,450.11,450.13 ETC
 ** PERMIT WILL NOT BE ISSUED.
 THE LOCATION OF THESE PANELS AND TRANSFORMER(S) WILL BE
 REQUIRED TO MEET CODE. IF PLANS AND PERMIT FOR SCOPE OF
 WORK DOES NOT COMMENCE WITHIN 60 DAYS FROM THIS REVIEW
 DATE FOR CORRECTION, A NOTICE WILL BE ISSUED ON-SITE
 FOR VIOLATIONS AND SCOPE OF WORK WILL BE REQUIRED ON A
 SEPARATE PERMIT WHETHER OR NOT BUILD OUT IS DONE TO
 ALLEVIATE ANY FURTHER ACTION FOR DISCONNECT OF SERVICE
 UTILITIES.
 ** AN ELECTRICAL CONTRACTOR MAY APPLY FOR THIS WORK
 SEPARATELY TO BEGIN. PLEASE CONTACT THIS OFFICE IF THIS
 OPTION IS TAKEN.
 AS THIS IS NOT ONLY A LIFE SAFETY HAZARD BUT AS WELL AS
 A FIRE HAZARD FOR LIFE AND PROPERTY, NO EXCEPTIONS TO
 ANY EXISTING NON-CODE COMPLIANCE WILL BE GRANTED.
 THIS IS FOR ANY OF THE TRANSFORMER(S), PANEL(S), AND
 DISCONNECT(S) LOCATIONS.
  
 ** PLEASE KNOW AT THIS TIME AS SOME OF THE INSTALLATION
 IS NOT CLEAR, THERE MAY BE COMMENTS IF THE INSTALLATION
 CHANGES AND/OR PERMIT APPLICATION CHANGES.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]