2007-06-08 09:56:28 | *** UNSAT 3RD *** |
| |
| |
| ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEWS STILL |
| ARE IN NEED OF ADDRESSING ALONE WITH SOME NEW COMMENTS |
| DUE TO CHANGES MADE ON PLANS AND DOCUMENTS SUBMITTED. |
| |
| 1) NOTE: PLEASE SEE THE PERMIT APPLICATION STILL |
| INDICATES SCOPE OF WORK WHICH IS NOT THE SAME AS PLANS. |
| THE PERMIT APPLICATION STATES *DESCRIBE PROJECT IN |
| DETAIL* IF THE PERMIT APPLICATION STATES THE ENTIRE 4TH |
| FLOOR IS BEING BUILD OUT FOR TENANT, THEN PLANS WILL BE |
| REQUIRED TO BE REVISED TO SHOW CODE COMPLIANCE FOR THE |
| ENTIRE FLOOR. |
| PLEASE COORDINATE WITH ONE OR THE OTHER. |
| PLEASE SEE THE PERMIT APPLICATION PACKAGE AS SUBMITTED |
| DOES CONTAIN PAPERWORK AND DOCUMENTATION WHICH IS FROM |
| THE THIRD FLOOR BUILD OUT WORK AND ANOTHER PERMIT. |
| PLEASE COORDINATE ALL DOCUMENTS, PLANS, AND PAPERWORK. |
| FBC 106.3.5.1.2 |
| |
| 2) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS NOW |
| SUBMITTED DO NOT COORDINATE WITH THE SUBMITTED PLANS. |
| PLEASE SEE THE NUMBER OF LIGHTING FIXTURES, THE |
| WATTAGE, TYPES AND CONTROLS FOR SUCH FIXTURES DOES NOT |
| MATCH WITH PLANS. |
| PLEASE ADJUST. |
| PLEASE SEE LEGEND AS THIS DOES NOT INDICATE ANY |
| AUTOMATED TYPE DEVICE. THE TIMES ARE NOT STATED. THE |
| PLANS DO NOT INDICATE DEVICES FOR NEW. |
| PLEASE SEE13-101, 13-415.1.ABC.1.1, .1.2, |
| 13-415.1.AB.1.1, 13-415.2 HOW IS METHOD A ABLE TO BE |
| SUED FOR THE SQ FT AS SHOWN AND FOR SCOPE OF WORK, |
| PLEASE |
| PLEASE SEE THE ENERGY CALCULATIONS WILL REQUIRE TO BE |
| SIGNED BY *OWNER AGENT* AS INDICATED ON SHEET |
| 2. |
| |
| 3) NOTE: PLEASE SEE SHEET E0.1 WHICH INDICATES A 2005 |
| FBC? |
| PLEASE SEE NO YEARS INDICATE FOR ELECTRICAL CODE |
| NFPA-70 OR LIFE SAFETY CODE NFPA-101. THESE SHOULD BE: |
| 2004 FBC W/ 2006 REVISIONS. |
| 2005 NFPA-70 (NEC). |
| 2003 NFPA-101 |
| |
| 4) NOTE: PLEASE SEE THE NEW DISCONNECTS ADDED FOR THE |
| TAPPED CONDUCTORS TO PANEL L AND L1 DO NOT APPEAR ON |
| PLANS AND LOCATIONS OF THESE CAN NOT BE VERIFIED FOR |
| CODE COMPLIANCE OF 240.21, 110.26, 240.24 ETC |
| PLEASE SHOW. |
| FBC106.1.21 |
| |
| 5) NOTE: PLEASE SEE NO CHANGES OR NOTES HAVE BEEN ADDED |
| FOR EXISTING AS SHOWN ELECTRICAL EQUIPMENT WHICH DOES |
| NOT MEET 110.26,408.7, 240.24, 450.9,450.11,450.13 ETC |
| ** PERMIT WILL NOT BE ISSUED. |
| THE LOCATION OF THESE PANELS AND TRANSFORMER(S) WILL BE |
| REQUIRED TO MEET CODE. IF PLANS AND PERMIT FOR SCOPE OF |
| WORK DOES NOT COMMENCE WITHIN 60 DAYS FROM THIS REVIEW |
| DATE FOR CORRECTION, A NOTICE WILL BE ISSUED ON-SITE |
| FOR VIOLATIONS AND SCOPE OF WORK WILL BE REQUIRED ON A |
| SEPARATE PERMIT WHETHER OR NOT BUILD OUT IS DONE TO |
| ALLEVIATE ANY FURTHER ACTION FOR DISCONNECT OF SERVICE |
| UTILITIES. |
| ** AN ELECTRICAL CONTRACTOR MAY APPLY FOR THIS WORK |
| SEPARATELY TO BEGIN. PLEASE CONTACT THIS OFFICE IF THIS |
| OPTION IS TAKEN. |
| AS THIS IS NOT ONLY A LIFE SAFETY HAZARD BUT AS WELL AS |
| A FIRE HAZARD FOR LIFE AND PROPERTY, NO EXCEPTIONS TO |
| ANY EXISTING NON-CODE COMPLIANCE WILL BE GRANTED. |
| THIS IS FOR ANY OF THE TRANSFORMER(S), PANEL(S), AND |
| DISCONNECT(S) LOCATIONS. |
| |
| ** PLEASE KNOW AT THIS TIME AS SOME OF THE INSTALLATION |
| IS NOT CLEAR, THERE MAY BE COMMENTS IF THE INSTALLATION |
| CHANGES AND/OR PERMIT APPLICATION CHANGES. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |