Plan Review Notes
Plan Review Notes For Permit 06120319
Permit Number 06120319
Review Stop P
Sequence Number 2
Notes
Date Text
2007-03-19 08:07:29DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 (COMMENT NUMBERS TO REMAIN THE SAME)
  
 1. OK
 2. OK
  
 3. ALL ARCHITECTURAL SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING:THE FIRM LICENSE
 NUMBER & THE PRINTED NAME OF THE PERSON SEALING THE
 DOCUMENT. FAC 61G1-16.004(2)(6) & FS 481.219,
 481.2055.
 ****NO RESPONSE, THE PRINTED NAME HAS BEEN INDICATED,
 BUT THE CA# AS INDICATED ON THE PLANS IS SHOWN AS
 ANOTHER BUSINESS NAME IN THE STATE DBPR WEBSITE. SEE
 ATTACHED SHEET.
  
 4. OK
 5. OK
  
 6. SHTS A1.04 & A7.041 DETAIL 1. THE BREAK ROOMSINK
 SHALL COMPLY WITH SECTION 11-4.24 AND ALL SUBSECTIONS.
 SHOW THE FOLLOWING:
 A. OK
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD APPROACH
 EXTENDING A MAXIMUM 19" UNDERNEATH THE SINK IS
 REQUIRED. CABINET DOORS ARE NOT APPROVED.
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 E. 11-4.24.7 FAUCETS
 ****NO RESPONSE, THE SINK DEPTH IS NOT SHOWN. THE
 CABINET DOORS ARE STILL SHOWN ON ELEVATION 1 SHT
 A-7.041. EXPOSED PIPES & SURFACES NOT ADDRESSED.
 INDICATE FAUCET TYPE. (INDICATING ADA COMPLIANT FAUCET
 IS NOT ENOUTH INFORMATION).
  
 7. SHOW THE FIXTURES REQUIRED BY SECTION 1004.1.3
 (BLDG) & 403.1 MINIMUM FACILITIES. INDICATE ON THE
 FLOOR PLAN THE DRINKING FOUNTAINS. SECTION 106.1.1.
 ****NO RESPONSE. NOT ADDRESSED.
  
 8. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]