Date |
Text |
2007-03-11 10:10:08 | ** UNSAT 2ND REVIEW ** |
| |
| |
| |
| 222 LAKEVIEW |
| 4THFLOOR BUILD-OUT/REMODEL\ |
| |
| ** PLEASE SEE SOME COMMENTS ARE THE SAME AND SOME ARE |
| NEW DUE TO CHANGES IN PLANS. |
| |
| |
| 1) NOTE: PLEASE SEE MISSING COMPLETE INFORMATION FOR A |
| TITLE BLOCK FOR THE ARCHITECT OF RECORD AND FIRM. |
| PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION NUMBER |
| ALSO KNOW AS FIRM LICENSE NUMBER. |
| PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER |
| FOR ARCHITECT. |
| FLORIDA ADMINISTRATIVE CODE 61G1-16.004, FLORIDA |
| STATUTES 481.219 |
| **THIS IS NOT A COMMENT RELATED TO KAMM CONSULTING, |
| HOWEVER TITLE BLOCKS ARE REQUIRED FOR ALL SHEETS PER |
| ABOVE AND WHETHER OR NOT COMMENT IS MADE BY ANY OTHER |
| TRADE. |
| |
| 2) NOTE: PERMIT APPLICATION HAS NOT BEEN ADJUSTED. |
| PLEASE CLARIFY PERMIT APPLICATION HAS APPLIED FOR NEW |
| TENANT BUILD OUT, HOWEVER PLANS DO NOT CORRELATE WITH |
| THIS. |
| |
| 3) NOTE:PLEASE KNOW ANY NEW ROOM LIGHTING AND |
| CONTROLS SHALL COMPLY WITH THIS SECTION. 13-415. |
| PLEASE KNOW THE ENTIRE FLOOR DOES NOT HAVE BE BROUGHT |
| UP TO CURRENT CODES, HOWEVER THE NEW ROOMS/LIGHTS AND |
| CONTROLS WILL BE REQUIRED. THIS CAN BE DONE BY SINGLE |
| DEVICES IN THESE ROOMS/AREAS. |
| PLEASE ALSO KNOW THAT THE LIGHTING POWER DENSITIES FOR |
| EACH OF THE NEW ROOMS SHALL COMPLY WITH THE MAXIMUM |
| LIGHTING AS PERMITTED IN THE TABLES. PLEASE SEE MISSING |
| LIGHTING CONTROL FOR ALL PER 13-415.1.ABC.1.1, .1.2, |
| AND .1.3.NEW AREAS AND ROOMS. PLEASE SEE OVER RIDES |
| DEVICES FOR THESE AREAS ALSO DEPENDING ON IF"SYSTEM" |
| OR "DEVICES" ARECHOSEN. |
| PLEASE SEE THE SYMBOL LEGEND FOR ALL DEVICES SHALL |
| INDICATE ALL MAXIMUM TIMES FOR DEVICES. (30MINS FOR |
| OCCUPANCY SENSOR TYPE AND 4HRS MAX FOR TIMER TYPE) |
| PLEASE SEE ROOMS AND AREAS WHICH DO NOT INDICATE ANY OF |
| THE DEVICES FOR AUTOMATED CONTROL. |
| PLEASE SEE ALL AREAS CONTAIN FLOOR TO CEILING HEIGHT |
| PARTITIONS SHALL CONTAIN DEVICE(S) FOR CONTROL. (PLEASE |
| SEE STORAGE) |
| PLEASE SEE 13-415.2, 13-415.2.ABC.1 FOR MISSING MAXIMUM |
| PERMITTED LIGHTING POWER DENSITIES. |
| |
| 4) NOTE: PLEASE PLACE A NOTE ON PLANS/SHEET E2.1 TO |
| CLOSET AREA TO BE BROUGHT UP TO CODE FOR MINIMUM |
| CLEARANCES AS STATED IN THE SECTIONS OF THE CODE NOTED |
| BELOW. PLEASE KNOW THIS WILL BE A CONDITION OF ISSUANCE |
| AND PLEASE KNOW NO ROUGH ELECTRICAL INSPECTIONS WILL BE |
| DONE UNTIL REVISIONS OR SEPARATE PERMIT IS SUBMITTED |
| FOR CHANGES.ONCE NOTE IS ON PLANS, A HOLD WILL BE |
| PLACED ON INSPECTIONS. |
| PLEASE SEE THE PANELSHV, LV1 AND LV2 WHICH DO NOT |
| SEEM TO MEET 110.26 FOR PANEL HV AND TRANSFORMER. |
| PLEASE VERIFY THIS AND KNOW THAT IF THIS WALL IS |
| ACTUALLY INSTALLED IN FRONT OF THE PANEL/EQUIPMENT AS |
| SHOWN, THIS WILL BE REQUIRED TO MEET 110.26/450.9, |
| 450.13 ETC |
| |
| 5) NOTE: PLEASE SEE PLANS HAVE BEEN REVISED TO SHOW THE |
| TRANSFORMER "T1A" DIRECTLY IN A CLOSET WHEN PREVIOUSLY |
| SHOWN IN THE MIDDLE OF THE CONFERENCE ROOM. PLEASE SEE |
| PANELS *L* AND L1* DO NOT SEEM TO MEET THE TAP |
| CONDUCTOR RULE FOR DISTANCE IN THE LENGTH OF |
| CONDUCTORS. PLEASE SEE 240.21C. |
| PLEASE ALSO SEE MINIMUM CLEARANCES REQUIRED FOR |
| TRANSFORMER. |
| THIS IS A FIRE/LIFE SAFETY HAZARD. |
| PLEASE ALSO VERIFY LOCATION FOR TAPS ON A TRANSFORMER |
| PER 240.21C. PLEASE ADJUST PLANS AND VERIFY THE ACTUAL |
| INSTALLATION. |
| |
| |
| 13) NOTE:** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDEDSHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS.PLEASE KNOW ONLY |
| ONE SET OF THE OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
2007-03-10 18:53:06 | 2007-03-10 18:53:06 |
| IN ELEC FOR REVIEW |