2007-01-25 08:32:06 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. SHT A.000 CODE ANALYSIS #1 INDICATES THE AUTHORITY |
| AS PALM BEACH COUNTY. THE AUTHORITY FOR THIS ADDRESS IS |
| THE CITY OF WEST PALM BEACH. #2 INDICATES THE FIRE |
| MARSHALL AS ROBERT PRUSIECKI. HE HAS RETIRED AND THE |
| NEW FIRE MARSHALL IS MIKE CARCILLO.PLEASE UPDATE THE |
| INFORMATION ON THE PLANS. SECTION 106.1.1. |
| |
| 2. SHT A.000 APPLICABLE BUILDING CODES INDICATES PBC |
| AMENDMENTS. THIS SHALL BE CHANGED TO WPB AMENDMENTS. |
| SECTION 106.1.1. |
| |
| 3. ALL ARCHITECTURAL SHEETS. THE TITLE BLOCK MUST, AT A |
| MINIMUM, CONTAIN THE FOLLOWING:THE FIRM LICENSE |
| NUMBER & THE PRINTED NAME OF THE PERSON SEALING THE |
| DOCUMENT. FAC 61G1-16.004(2)(6) & FS 481.219, |
| 481.2055. |
| |
| 4. SHT S-2 THE ENGINEER SHALL SIGN/DATE SEALED PLANS. |
| FAC 61G15-23.002(2) & FS 471.025. |
| |
| 5. SHT AD1.04 GENERAL DEMOLITION NOTES 0.1.4 INDICATES |
| PLUMBING TO BE REMOVED 1/2" BEHIND THE FINISH FACE OF |
| THE SURFACE. IN THE REMOVAL OF ANY PART OF THE DRAINAGE |
| SYSTEM, DEAD ENDS ARE PROHIBITED. ALL DEMO'D PIPING |
| SHALL BE CAPPED AND INSPECTED PRIOR TO COVERING PER |
| SECTION 704.5. PLEASE INDICATE ON THE DEMO PLANS. |
| |
| 6. SHTS A1.04 & A7.041 DETAIL 1. THE BREAK ROOMSINK |
| SHALL COMPLY WITH SECTION 11-4.24 AND ALL SUBSECTIONS. |
| SHOW THE FOLLOWING: |
| A. 11-4.24.3 KNEE CLEARANCE |
| B. 11-4.24.4 SINK DEPTH |
| C. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD APPROACH |
| EXTENDING A MAXIMUM 19" UNDERNEATH THE SINK IS |
| REQUIRED. CABINET DOORS ARE NOT APPROVED. |
| D. 11-4.24.6 EXPOSED PIPES & SURFACES |
| E. 11-4.24.7 FAUCETS |
| |
| 7. SHOW THE FIXTURES REQUIRED BY SECTION 1004.1.3 |
| (BLDG) & 403.1 MINIMUM FACILITIES. INDICATE ON THE |
| FLOOR PLAN THE DRINKING FOUNTAINS. SECTION 106.1.1. |
| |
| 8. SHT P2.1 DOMESTIC WATER ISOMETRIC. THE WATER HAMMER |
| ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES, IN AN |
| "EFFECTIVE RANGE", NOT IN THE CEILING AS SHOWN. PDI-WH |
| 201 AND MANUF. INSTALLATION INSTRUCTIONS. |
| |
| REVIEW BY KEN STEVENS |