Date |
Text |
2007-01-07 19:44:05 | ** UNSAT ** |
| |
| |
| 222 LAKEVIEW |
| 4THFLOOR BUILD-OUT/REMODEL |
| |
| |
| 1) NOTE: PLEASE SEE MISSING ADDRESS INFORMATION FROM |
| TITLE BLOCKS. PLEASE SEE THE SUITE/UNIT NUMBER IS BEING |
| SHOWN, HOWEVER NOT THE ADDRESS/ LOCATION. |
| FAC 61G1-16.004, FAC61G15-23.002 |
| |
| 2) NOTE: PLEASE SEE MISSING COMPLETE INFORMATION FOR A |
| TITLE BLOCK FOR THE ARCHITECT OF RECORD AND FIRM. |
| PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION NUMBER |
| ALSO KNOW AS FIRM LICENSE NUMBER. |
| PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER |
| FOR ARCHITECT. |
| FLORIDA ADMINISTRATIVE CODE 61G1-16.004, FLORIDA |
| STATUTES 481.219 |
| **THIS IS NOT A COMMENT RELATED TO KAMM CONSULTING, |
| HOWEVER TITLE BLOCKS ARE REQUIRED FOR ALL SHEETS PER |
| ABOVE AND WHETHER OR NOT COMMENT IS MADE BY ANY OTHER |
| TRADE. |
| |
| 3) NOTE: PLEASE LIST THE FOLLOWING MINIMUM CODES |
| RELEVANT TO THIS PROJECT AND DESIGN. |
| 2005 NFPA-72, 2005 NFPA-70, 2003 NFPA-101 |
| PLEASE ADJUST THE ARCHITECTURAL SHEETS AS WELL AS THE |
| ELECTRICAL SHEETS. |
| PLEASE SEE AS THE PERMIT WAS APPLIED FOR AFTER DECEMBER |
| 8TH, 2006 THE 2006 REVISIONS TO THE 2004 FBC AND THE |
| 2005 NATIONAL ELECTRICAL CODE WAS ADOPTED BY THE STATE |
| OF FLORIDA. |
| PLEASE ADJUST CODES ON PLANS. |
| |
| 4) NOTE: PLEASE CLARIFY PERMIT APPLICATION HAS APPLIED |
| FOR NEW TENANT BUILD OUT, HOWEVER PLANS DO NOT |
| CORRELATE WITH THIS. PLEASE CLARIFY AS THE NEXTTWO |
| COMMENTS MAY APPLY FOR FLOOR OR FOR NEW ROOMS AS |
| SHOWN. |
| |
| 5) NOTE: PLEASE SEE MISSING LIGHTING CONTROL FOR ALL |
| PER 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE |
| MISSING CONTROLS FOR COMMON AREAS. PLEASE SEE OVER |
| RIDES DEVICES FOR THESE AREAS ALSO DEPENDING ON |
| "SYSTEM" OR DEVICES CHOSEN. PLEASE SEE THE SYMBOL |
| LEGEND FOR ALL DEVICES SHALL INDICATE ALL MAXIMUM TIMES |
| FOR DEVICES. (30MINS FOR OCCUPANCY SENSOR TYPE AND 4HRS |
| MAX FOR TIMER TYPE) |
| PLEASE SEE ROOMS AND AREAS WHICH DO NOT INDICATE ANY OF |
| THE DEVICES FOR AUTOMATED CONTROL. |
| PLEASE PROVIDE SCHEDULING FOR ANY PROPOSED SYSTEM. |
| PLEASE SEE ALL AREAS CONTAIN FLOOR TO CEILING HEIGHT |
| PARTITIONS SHALL CONTAIN DEVICE(S) FOR CONTROL. (PLEASE |
| SEE STORAGE) |
| PLEASE SEE 13-415.2, 13-415.2.ABC.1 FOR MISSING MAXIMUM |
| PERMITTED LIGHTING POWER DENSITIES. |
| PLEASE ALSO SEE 13-415.AB.1 FOR MISSING ENERGY |
| CALCULATIONS REQUIRED FOR NEW TENANT BUILD-OUT. |
| ** PLEASE SUBMIT THE ABOVE. AS THERE ARE ITEMS NOT YET |
| SUBMITTED, A REVIEW OF SAID SYSTEM/DEVICES ETC CAN NOT |
| BE FULLY ACCOMPLISHED AT THIS TIME. |
| |
| 6) NOTE: PLEASE PROVIDE A DETAIL ON ALL EMERGENCY |
| AND/OR EXIT LIGHTING WIRED AHEAD OF ANY OVER RIDE |
| CONTROL DEVICES PER 700.12E. PLEASE SEE A |
| CLOUDED/HIGHLIGHTED NOTE MAY ALSO BE DONE. THIS AHJ HAS |
| BEEN HAVING MANY INSTANCES WHERE EMERGENCY AND EXIT |
| LIGHTS ARE BEING WIRED ON THE LOAD SIDE OF OC/ TIMER |
| DEVICES. |
| |
| 6) NOTE: PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%. |
| 215.3, 230.42 ETC. |
| FBC 106.1.2 ADMIN SECTION. |
| |
| 7) NOTE: PLEASE KNOW EITHER AT THIS POINT OR BEFORE |
| FINAL, A REVISION FOR ALL CIRCUITS TO SPECIFIC ROOMS |
| AND AREAS WILL BE REQUIRED. (LIGHTING CIRCUITS ETC.) |
| 408.4. |
| |
| |
| 8) NOTE: PLEASE SEE THE PANELSHV, LV1 AND LV2 WHICH |
| DO NOT SEEM TO MEET 110.26 FOR PANEL HV AND |
| TRANSFORMER. PLEASE VERIFY THIS AND KNOW THAT IF THIS |
| WALL IS ACTUALLY INSTALLED IN FRONT OF THE |
| PANEL/EQUIPMENT AS SHOWN, THIS WILL BE REQUIRED TO MEET |
| 110.26/450.9, 450.13 ETC |
| |
| 9) NOTE: PLEASE SEE THE RISER SHEET CONTAINS A BOX WITH |
| NOTES FROM 9/25/01? PLEASE UPDATE NOTE. |
| PLEASE SEE THIS NOTE #3 IN THIS BOX SHOW A NOTATION FOR |
| A NEW BREAKER TO COME FROM THE EXISTING "H" PANEL TO |
| FEED PANEL "H1" WHICH ON RISER IS SHOWN AS NEW, YET |
| THIS PANEL SCHEDULE FOR "H1" INDICATES THIS PANEL AS |
| A120/208V PANEL AND IS BEING FED FROM H WHICH IS |
| 277/480V. |
| PLEASE SEE RISER AND PLANS DO NOT SHOW ANY |
| TRANSFORMER. |
| PLEASE SEE 450.3, 450.9, 450.13B, 240.21C ETC PLEASE |
| CORRELATE PLANS AND ADJUST. |
| |
| 10) NOTE: PLEASE SEE PLANS APPEAR TO SHOW TRANSFORMER |
| "T1A" DIRECTLY IN THE MIDDLE OF THE CONFERENCE ROOM. |
| PLEASE SEE 450.13B AS THIS UNIT IS A 75 KVA TRANSFORMER |
| AND IF ABOVE CEILING IT WILL BE REQUIRED TO BE |
| RELOCATED BELOW CEILING. THIS IS A FIRE/LIFE SAFETY |
| HAZARD AND THE CODE EVEN WHEN THE BUILDING WAS BUILT |
| DID NOT ALLOW THIS INSTALLATION AS SHOWN. PLEASE ALSO |
| VERIFY LOCATION FOR TAPS ON A TRANSFORMER PER 240.21C. |
| PLEASE ADJUST PLANS AND VERIFY THE ACTUAL |
| INSTALLATION. |
| |
| |
| 11) NOTE: PLEASE SEE THE LOW VOLTAGE AUDIO/VISUAL PLANS |
| SUBMITTED MAY ONLY BE PART OF THE PERMITTED RECORD SET |
| OF PLANS IF BEING DONE BY THE ELECTRICAL SUB |
| CONTRACTOR. AS THESE SHEETS SEEM TO INDICATE A SEPARATE |
| LV SOUND/AUDIO VISUAL CONTRACTOR, THESE SHALL BE |
| SUBMITTED UNDER A SEPARATE PERMIT APPLICATION. PLEASE |
| KNOW IN EITHER CASE ALL PLANS ARE REQUIRED TO BE |
| SIGNED, DATED PRINTED NAME ETC FOR THE PERSON TAKING |
| RESPONSIBILITY OF SUCH PLANS. |
| FBC 106.1.2, FS 481/471, FAC 61G15-23.002, FAC |
| 61G1-16.004 ETC |
| |
| 12) NOTE: PLEASE SEE "S" SHEET IN BOTH SETS ARE NOT |
| SIGNED AND DATED BY THE ENGINEER OF RECORD. SHEETS DO |
| CONTAIN THE RAISED SEAL. |
| PLEASE SEE FS 471.025, FAC 61G15-23.002 |
| THIS IS ONLY NOTED AND SHOULD ALSO BE IN NOTES FROM THE |
| BUILDING REVIEWER. |
| |
| 13) NOTE:** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDEDSHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS.PLEASE KNOW ONLY |
| ONE SET OF THE OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |