2006-12-12 16:00:30 | BUILDING REVIEW CHECKLIST: | | 1-COPY OF CONTRACTOR'S PROPOSAL TO THE OWNERINCLUDES | | 1/4" INSULATION. SELECTED APPROVED ASSEMBLYON NOA | | #03-0501.02 IS FOR A NON-INSULATED ASSEMBLY. CLARIFY IF | | INSTALLING INSULATEDOR NON-INSULATED SYSTEM AND | | PROVIDE CORRESPONDING INFORMATION. | | | | 2- FROM SELECTED ASSEMBLY SPECIFY FASTENING OPTION AS | | REQUIRED BY CITY POLICY FOR RE-ROOFING PERMITS TO | | VERIFY MAXIMUM DESIGN PRESSURES. SEE ATTACHED COPY OF | | CITY POLICY. | | | | 3- PROVIDE RAS 117 CALCULATIONSAS REQUIRED BY GENERAL | | LIMITATION #7 FOR ENHANCED FASTENING AT PERIMETER AND | | CORNER AREAS. SEE TABLE 1609.6B FOR REQUIRED DESIGN | | PRESSURES. SEE GENERAL LIMITATION #7 ON LAST PAGE OF | | NOA TO SEE REQUIRED INFORMATION TO BE SUBMITTED. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|