Plan Review Notes For Permit 06120143 |
Permit Number |
06120143 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-01-31 11:04:40 | BUILDING REVIEW SECOND CHECKLIST: | | | | 1- INSTALLATION SCHEDULE SUBMITTED SHOWS ANCHOR SPACING | | TO BE 13" O.C. FOR ALL PANELS.ACCORDING TO ANCHOR | | SCHEDULE ON SHEET 7 OF 7 OF DRAWING 05-420 THE ANCHOR | | SPACING FOR ANCHORS IN CONCRETE BLOCK SHALL BE LESS | | THAN 13' O.C. FOR PANELS SPANS GREATER THAN 72". | | REVISE INSTALLATION SCHEDULED AS REQUIRED. | | | | 2- INSTALLATION SCHEDULE SUBMITTED SHOWS THAT SHUTTER | | GLASS SEPARATION IS NOT REQUIRED.ACCORDING TO TABLE 2 | | ON SHEET 6 OF 7 OF DRAWING 05-420 THERE ISA MINIMUM | | GLASS SEPARATION THAT NEED TO BE MET. REVISE | | INSTALLATION SCHEDULE AS REQUIRED. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|