Plan Review Notes For Permit 06120143 |
Permit Number |
06120143 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-01-19 16:40:32 | BUILDING REVIEW CHECKLIST: | | 1- PROVIDE APPROVED PRODUCT APPROVAL AS REQUIRED BY DCA | | RULE 9B-72 FOR STORM SHUTTERS.DRAWINGS SUBMITTED ARE | | NOT AN APPROVED PRODUCT APPROVAL. | | | | 2- SOME STORM PANELS EXCEED THE MAXIMUM PANEL SPAN AS | | ALLOWED BY TABLE 1 ON SHEET 3 OF 4 OF DRAWING NO | | 05-421. REVISE AS REQUIRED FOR OPENINGS 18, 22 AND 23. | | | | 3- SOME STORM PANELS EXCEED THE MINIMUM PANEL SPAN AS | | ALLOWED BY TABLE 2ON SHEET 3 OF 4 OF DRAWING NO | | 05-421. REVISE AS REQUIRED FOR OPENINGS 3, 25, 26, 27 | | AND 28. | | | | 4- PERMIT VALUATION WAS UPDATEDAS REQUIRED BY SEC. | | 108.3 CITY AMENDMENTS TO FBC 2004.OWES $29.42FOR | | ADDITIONAL PERMIT FEES. | | | | 5- INSTALLATION SCHEDULE USED IS TOO OLD. PLEASE USE | | ATTACHED SAMPLE OF REVISED INSTALLATION SCHEDULE WHICH | | PROVIDES ALL REQUIRED INFORMATION FOR PLAN REVIEW. FILL | | IN ALL INFORMATION TO AVOID DELAYS. SEC. 106.1.2 CITY | | AMENDMENTS TO FBC 2004. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|