2007-01-19 16:40:32BUILDING REVIEW CHECKLIST:
 1- PROVIDE APPROVED PRODUCT APPROVAL AS REQUIRED BY DCA
 RULE 9B-72 FOR STORM SHUTTERS.DRAWINGS SUBMITTED ARE
 NOT AN APPROVED PRODUCT APPROVAL.
  
 2- SOME STORM PANELS EXCEED THE MAXIMUM PANEL SPAN AS
 ALLOWED BY TABLE 1 ON SHEET 3 OF 4 OF DRAWING NO
 05-421. REVISE AS REQUIRED FOR OPENINGS 18, 22 AND 23.
  
 3- SOME STORM PANELS EXCEED THE MINIMUM PANEL SPAN AS
 ALLOWED BY TABLE 2ON SHEET 3 OF 4 OF DRAWING NO
 05-421. REVISE AS REQUIRED FOR OPENINGS 3, 25, 26, 27
 AND 28.
  
 4- PERMIT VALUATION WAS UPDATEDAS REQUIRED BY SEC.
 108.3 CITY AMENDMENTS TO FBC 2004.OWES $29.42FOR
 ADDITIONAL PERMIT FEES.
  
 5- INSTALLATION SCHEDULE USED IS TOO OLD. PLEASE USE
 ATTACHED SAMPLE OF REVISED INSTALLATION SCHEDULE WHICH
 PROVIDES ALL REQUIRED INFORMATION FOR PLAN REVIEW. FILL
 IN ALL INFORMATION TO AVOID DELAYS. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712