2007-05-02 17:57:03 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| ****FROM PREVIOUS REVIEW: |
| |
| 1. ALL ARCHITECTURAL SHEETS. THE FIRM LICENSE NUMBER, |
| (CERTIFICATE OF AUTHORIZATION), IS REQUIRED IN THE |
| TITLE BLOCK OF EACH SHEET. FAC 61G1-16.004(2) & FS |
| 481.219, 481.2055. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 2. SHT A3.4 SUBMIT CALCULATIONS FOR PRIMARY AND |
| SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOTAGE OF EACH |
| AREA AS WELL AS 1/2 AREA OF ALL VERTICAL WALLS |
| INCLUDING PARAPETS. ALSO INDICATE ANY AREA OF A ROOF |
| THAT DRAINS FROM ABOVE IF APPLICABLE. SECTIONS 1106 & |
| 1107 WITH ALL SUBSECTIONS. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 3. SHT A3.4 DETAIL 4, SECONDARY DRAINS SHALL BE A |
| MINIMUM 2" HIGHER THAN THE MAIN DRAIN. AS SHOWN THEY |
| ARE ONLY ABOUT 3/4" ABOVE THE MAIN DRAINS. THIS IS |
| REQUIRED SO THAT THE SECONDARY DRAINS WILL NOT DRAIN |
| STORM WATER UNLESS THERE IS A BLOCKAGE IN THE PRIMARY |
| DRAINS.--SUBMIT A DETAIL SHOWING THE ELEVATION AT |
| THE FLOOR AT THE PATIO DOOR, AND INDICATE THE ELEVATION |
| OF THE PRIMARY DRAIN AND THE SECONDARY DRAIN. SECTION |
| 106.1.1. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 4. SHT A3.5 SHOWS 6" OVERFLOW DRAINS CONNECTING TO |
| MANHOLES. SECTION 1107.2 REQUIRES THE DISCHARGE TO BE |
| ABOVE GRADE IN AN OBSERVABLE LOCATION. PLEASE CHANGE |
| TERMINATION POINT FOR THE OVERFLOW DRAINS.--ONE 7" |
| DOWNSPOUT DOES NOT SHOW THE PIPING TO THE MANHOLE. |
| PLEASE SHOW ALL PIPING. SECTION 106.1.1. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 5. SHTS A4.1 & A5.1. SHT A4.1 SHOWS THE GUTTER TO BE |
| CONTINUOUS AROUND THE INSIDE OF THE BLDG ROOF EXCEPT AT |
| THE CHIMNEYS. SHT A5.1 ONLY SHOWS THE GUTTER AT THE |
| MAIN ROOF SECTIONS, AND NO GUTTER AT THE HIP ROOF |
| SECTIONS. ALSO NO DOWNSPOUTS ARE INDICATED AT THE HIP |
| ROOF SECTIONS. PLEASE CLARIFY. SECTION 106.1.1. ****NO |
| RESPONSE, NOT ADDRESSED. |
| |
| 6. OK |
| |
| 7. SHT P-1 THE SANITARY PARTIAL RISER DIAGRAMS DO NOT |
| REFLECT THE FLOOR PLAN IN MANY INSTANCES. ALL OFFSETS |
| SHALL BE SHOWN ON THE RISER DIAGRAM, SOME EXTRA PIPING |
| IS SHOWN, SOME FIXTURE BRANCH LINES ARE NOT SHOWN.-- |
| THE AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL |
| CONNECT TO A BRANCH DRAIN OR A DRAINAGE STACK A MINIMUM |
| OF 3" IN DIAMETER. SECTION 406.3.-- SEE RED LINE |
| NOTES ON ONE SET OF PLUMBING PLANS. SECTION 106.1.1. |
| ****NO RESPONSE. PARTAL RISER 2ND FLOOR DOES NOT |
| REFLECT THE NEW FLOOR PLAN, NOR DOES THE 3RD FLOORM/B |
| TUB. SEE RED LINE CORRECTIONS.--SHOW ALL VENT |
| PIPING AND WATER PIPING ON THE FLOOR PLAN TO REFLECT |
| THE RISER DIAGRAMS. VENT OFFSETS ARE NOT SHOWN ON THE |
| FLOOR PLAN.--THE WATER RISER DIAGRAM DOES NOT SHOW |
| THE WATER PIPING & WATER HAMMER ARRESTOR FOR THE REF. |
| WITH ICE MAKER NOR IS IT SHOWN ON THE FLOOR PLAN. |
| |
| 8. SHT P-2 THE SANITARY PARTIAL RISER DIAGRAMS DO NOT |
| REFLECT THE FLOOR PLAN IN MANY INSTANCES. ALL OFFSETS |
| SHALL BE SHOWN ON THE RISER DIAGRAM, SOME EXTRA PIPING |
| IS SHOWN, SOME FIXTURE BRANCH LINES ARE NOT SHOWN, THE |
| VENT & SANT LINES ARE CROSSED FROM FLOOR TO FLOOR.-- |
| THE AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL |
| CONNECT TO A BRANCH DRAIN OR A DRAINAGE STACK A MINIMUM |
| OF 3" IN DIAMETER. SECTION 406.3.-- SEE RED LINE |
| NOTES ON ONE SET OF PLUMBING PLANS. SECTION 106.1.1. |
| ****NO RESPONSE. OFFSET FROM THE POWDER ROOM TO BATH #2 |
| IS NOT SHOWN ON THE FLOOR PLAN, AND THE RISER INDICATES |
| THE RISER GOING IN THE WRONG DIRECTION.--RISERS |
| FROM THE 1ST FLOOR BY BATH#3 TO THE 2ND FLOOR BY THE |
| POWDER ROOM ARE CROSSED.--PARTIAL RISER TO BATH #2 |
| DOES NOT REFLECT THE FLOOR PLAN.--THE WATER LINE & |
| WATER HAMMER ARRESTOR TO THE ICE MAKER IN THE REF IS |
| NOT SHOWN ON THE WATER RISER NOR ON THE FLOOR PLAN.-- |
| SHOW ALL VENT OFFSETS AND WATER PIPING ON THE FLOOR |
| PLAN. |
| |
| 9. SHT P-3 THE SANITARY PARTIAL RISER DIAGRAMS DO NOT |
| REFLECT THE FLOOR PLAN IN MANY INSTANCES. ALL OFFSETS |
| SHALL BE SHOWN ON THE RISER DIAGRAM, SOME EXTRA PIPING |
| IS SHOWN, SOME FIXTURE BRANCH LINES ARE NOT SHOWN, BATH |
| 2 INDICATES A TUB ON THE RISER, BUT SHOWS A SHOWER ON |
| THE FLOOR PLAN. THE KITCHEN SHOWS A 3" TO THE 3RD |
| FLOOR. PLEASE INDICATE WHERE THIS LINE IS TERMINATING. |
| --THE AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL |
| CONNECT TO A BRANCH DRAIN OR A DRAINAGE STACK A MINIMUM |
| OF 3" IN DIAMETER. SECTION 406.3.-- SEE RED LINE |
| NOTES ON ONE SET OF PLUMBING PLANS. SECTION 106.1.1. |
| ****NO RESPONSE. PARTIAL RISERS FOR THE 3RD FLOOR NEED |
| TO IDENTIFY VENTS WHEN REVENTING FROM ONE RISER TO |
| ANOTHER.--NO WATER LINE OR WATER HAMMER ARRESTOR |
| FOR THE ICE MAKER IN THE REF SHOWN ON THE RISER NOR ON |
| THE FLOOR PLAN.--PARTIAL WATER TO THE DISH WASHER |
| SHOW COLD WATER SUPPLY. HOT WATER REQUIRED.--SHOW |
| VENTS AND WATER SUPPLY PIPING ON THE FLOOR PLAN. |
| |
| 10. SHT P-4 THE SANITARY PARTIAL RISER DIAGRAMS DO NOT |
| REFLECT THE FLOOR PLAN IN MANY INSTANCES. ALL OFFSETS |
| SHALL BE SHOWN ON THE RISER DIAGRAM, SOME EXTRA PIPING |
| IS SHOWN, SOME FIXTURE BRANCH LINES ARE NOT SHOWN. THE |
| VENT FROM THE FIRST FLOOR, BATHROOM 3 IS NOT SHOWN ON |
| THE FLOOR PLAN OF THE SECOND FLOOR. --THE |
| AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL CONNECT TO |
| A BRANCH DRAIN OR A DRAINAGE STACK A MINIMUM OF 3" IN |
| DIAMETER. SECTION 406.3.-- SEE RED LINE NOTES ON ONE |
| SET OF PLUMBING PLANS. SECTION 106.1.1. |
| ****NO RESPONSE. OFFSETS OF THE VENTS ARE NOT SHOWN ON |
| THE FLOOR PLAN.--IDENTIFY WHERE ALL REVENT PIPING |
| IS CONNECTING TO.--MASTER BATH RISER DOES NOT |
| REFLECT THE FLOOR PLAN.--PARTIAL WATER RISER 2ND |
| FLOOR DOES NOT REFLECT THE FLOOR PLAN.--1ST FLOOR |
| PIPING SHOWS EXTRA UNDERGROUND PIPING. PLEASE CLARIFY. |
| --SHOW ALL VENT PIPING & WATER PIPING ON THE FLOOR |
| PLAN.--IDENTIFY THE RISER THAT THE W/M AND M/BATH |
| CONNECT TO ON THE FLOOR PLAN 2ND FLOOR. |
| |
| 11. SUBMIT A WATER RISER DIAGRAM FOR EACH TYPE OF UNIT. |
| SHOW ALL PIPE SIZES, VALVES AND WATER HAMMER ARRESTORS |
| REQUIRED BY SECTION 604.9. (ICE MAKERS, DISHWASHERS, & |
| WASH MACHINES). SECTION 106.3.5.1.3(3)(13). |
| ****NO PIPING SHOWN ON THE FLOOR PLAN OR RISER DIAGRAMS |
| FOR THE ICE MAKERS IN THE REF'S. |
| |
| 12. SUBMIT A STORM RISER DIAGRAM FOR THE PRIMARY |
| DRAINAGE AND SECONDARY DRAINAGE SYSTEMS. SHOW ALL PIPE |
| SIZES, OFFSETS, AND INDICATE SQUARE FOOTAGE BEING |
| DRAINED.SECTION 106.3.5.1.3(7)(13). |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 13. OK. |
| |
| 14. SHT P-5 WATER HEATER DETAIL. PLEASE INDICATE THE |
| TERMINATION POINT FOR THE EMERGNECY PAN DRAIN AND THE |
| T/P RELIEF DISCHARGE LINE. SECTIONS 504.6.1 & 504.7.2. |
| ****MORE INFORMATION IS REQUIRED ON THE DETAIL. IT |
| SHOWS A 4" HOUSE KEEPING PAD, THE THE DRAIN LINES |
| APPEAR TO DROP DOWN TO THE GARAGE FLOOR. PLEASE |
| INDICATE HOW THIS WILL COMPLY WITH THE CODE SECTIONS |
| FOR THESE LINES TO BE 6" ABOVE GRADE AND NOT HAVE ANY |
| TRAPPED SECTIONS PER SECTIONS 504.6.1 & 504.7.2. SUBMIT |
| AN ISOMETRIC FOR EACH TYPICAL P/T & PAN DRAIN LINE. |
| |
| 15. SHT IR-1 THE CONTROLLER AND THE RAIN SENSOR LOCTION |
| ARE REQUIRED ON THE PLAN. SECTION 106.1.1.--THE |
| BACKFLOW PREVENTOR SHALL BE INSTALLED BYA LICENCED |
| PLUMBING CONTRACTOR.--A SEPARATE IRRIGATION PERMIT |
| IS REQUIRED. SECTION 105.1. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 16. SHTS IR-1, LP-1 & LP-2 LANDSCAPE ARCHITECT LICENSE |
| IS NULL & VOID PER DBPR WESITE. (SEE ATTACHED SHEET). |
| ONE SET OF SHEETS SHALL BE RETAINED FOR POSSIBLE REVIEW |
| BY THE STATE LANDSCAPE ARCHITECTURAL BOARD AS THIS SEAL |
| HAS BEEN NULL & VOID SINCE 11/30/95. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 17. SHTS IR-1, LP-1 & LP-2THE LANDSCAPE FIRM LICENSE |
| NUMBER AS WELL AS THE PRINTED NAME OF THE PERSON |
| SEALING THE DOCUMENT SHALL BE IN THE TITLE BLOCK OF |
| EACH SHEET. FAC 61G1-16.004(2)(6) & FS 481.2055. ****NO |
| RESPONSE, NOT ADDRESSED. |
| |
| |
| 18. THE MANHOLES, TRENCH DRAINS, STORM DRAINS AND |
| RELATED PIPING SHALL BE DESIGNED BY THE BUILDING |
| ENGINEER, AND INSTALLED BY THE PLUMBING CONTRACTOR AS |
| THIS IS WITHIN THE FOOTPRINT OF THE BUILDING. THE CIVIL |
| ENGINEER, AND THE SITE CONTRACTOR CAN ONLY DESIGN AND |
| INSTALL UP TO FIVE FEET OF THE BUILDING STRUCTURE. FS |
| 489. |
| (INFORMATIONAL) |
| |
| ***********NEW COMMENTS*********** |
| |
| 1B. SHTS LP-1, LP-2 & IR-1 THE LANDSCAPE FIRM LICENSE |
| NUMBER PER FLA STATE DBPR WEBSITE IN IN APPLICANT |
| STATUS. (SEE ATTACHED SHEET). AS SUCH THESE PLANS CAN |
| NOT BE APPROVED.--WHEN APPROVED SHEETS ARE |
| SUBMITTED, THE DATE THE SEAL AND SIGNATURE OF THE |
| LANDSCAPE ARCHITECT ARE AFFIXED TO THE PLANS, THE DATE |
| SHALL BE ALSO AFFIXED BELOW THE SIGNATURE. FAC |
| 61G1-16.004(5) & FS 481.2055. |
| |
| 2B. COMPLETE RISERS FROM THE HORIZONTAL BUILDING |
| ISOMETRIC DIAGRAM TO THE VTRSHALL BE SUBMITTED AS |
| PARTIAL RISER DIAGRAMS ARE HARD TO FOLLOW AND NOT ALL |
| INFORMATION REQUIRED ON THE PARTIAL RISERS IS BEING |
| SUBMITTED SUCH AS OFFSETS, VENTING, REVENTING ETC. |
| SECTION 106.3.5.1.3. THE RISER DIAGRAMS SHALL REFLECT |
| THE PIPING ON THE FLOOR PLAN. SECTION 106.1.1. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |