Date |
Text |
2007-04-21 13:39:27 | -------2ND REVIEW: DENIED-------- |
| |
| THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| PERVIOUS COMMENTS FOR THE PURPOSE OF CONTINUITY. |
| |
| 1. OK |
| |
| 2. OK |
| |
| 3. PLEASE SHOW MEANS OF MECHANICAL EXHAUST FOR GARAGE |
| ON MECHANICAL PLANS. FBC,M 403.3, FBC 106.1.1 |
| |
| 4. OK PENDING RESPONSE TO COOMENT #3. |
| |
| 5. IF YOU CHOOSE TO LEAVE THESE NOTES ON PLAN, THOSE |
| ELEMENTS WILL BE REQUIRED TO BE INSTALLED AT ROUGH |
| INSPECTION. CONSULT MANUFACTURER'S INSTALLATION |
| ISTRUCTIONS TO SEE IF ANOTHER METHOD OF VIBRATION |
| ISOLATION IS AVAILABLE. |
| |
| 6. OK |
| |
| 7. THIS ISSUE WAS NOT ADDRESSED. IF RETURN TRANSFERS |
| ARE NOT REDESIGNED TO MEET THE EXCEPTIONS UNDER FBC,M |
| 601.4, A FIELD TEST WILL BE REQUIRED AT FINAL |
| INSPECTION TO DETERMINE IF BALANCED RETURN HAS BEEN |
| ACHIEVED WITH A PRESSURE DIFFERENTIAL OF 0.01" WC OR |
| LESS. |
| |
| 8. OK |
| |
| 9. OK |
| |
| 10. (A) PER DETAIL ON M-5, IS IT THE INTENT OF THE |
| DESIGNER TO HAVE A COMBINATION OF 4" ROUND, 10X3 AND |
| 6X3 ROOF JACKS? DETAIL INDICATES SIZE OF ROOF JACK IS |
| TO MATCH SIZE OF EXHAUST DUCT GOING TO ROOF. |
| (B) THIS TYPE OF ROOF JACK WILL NOT WORK FOR DRYER |
| EXHAUST. SCREENS ARE PROHIBITED AND BACKDRAFT DAMPER IS |
| REQUIRED PER FBC,M 504.4. PROVIDE DETAIL FOR DRYER |
| EXHAUST TERMINATION IN ACCORDANCE WITH THIS SECTION. |
| (C) PG M-3: CLOTHES DRYERS ARE TO BE EXHAUSTED IN |
| ACCORDANCE WITH DRYER MANUFACTURER'S INSTALLATION |
| INSTRUCTIONS PER FBC,M 504.1. VERIFY WITH INSTRUCTIONS |
| THAT 6X3 DUCT IS AN ACCEPTABLE ALTERNATIVE TO 4" ROUND |
| DUCT AND THAT SQUARE 90 DEGREE ELBOWS ARE ACCEPTABLE IN |
| LEIU OF 4" ROUND RADIUS 90 DEGREE ELBOWS. PROVIDE |
| MANUFACTURER'S INSTALLATION INSTRUCTIONS TO SHOW |
| COMPLIANCE IF THIS TYPE OF DUCT IS TO BE USED. |
| |
| |
| REVIEWED BY: |
| RONALD J REGUEIRO |
| 561.805.6719 |
| [email protected] |