2007-05-01 19:09:07*****UNSAT*****
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
  
  
 08.INDICATE THE LOCATION OF THE FIRE HYDRANT(S) IN
 THE VICINITY OF THE SITE.BE ADVISED THAT IF THE
 HYDRANT(S) IS GREATER THAN 500 FEET, AN ADDITIONAL
 HYDRANT SHALL BE REQUIRED.UNABLE TO VERIFY HYRANTS,
 DUE TO THE SMALLNESS OF THE FIRE HYDRANT VICINITY MAP.
 PLEASE SHOW NEAREST HYDRANTS ON PLAN SHEET WITH THE
 DISTANCE TO THE PROPERTY
  
 10.IN ADDITION TO THE EXTERIOR ELEVATION DETAILS ON
 SHEET A5.1 AND A5.2, SPECIFY ELEVATIONS AS NORTH, EAST,
 WEST, AND SOUTH.ON SHEET STILL UNCLEAR AS TO REAR,
 LEFT, AND RIGHT ELEVATION
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  