2007-04-14 15:57:58 | |
| ** UNSAT2ND REVIEW** |
| |
| ** PLEASE SEE THAT ITEMS ARE FROM PREVIOUS REVIEW; |
| HOWEVER MOST ARE NEW DUE TO CHANGES IN PLANS AND ITEMS |
| WHICH ARE NEW TO PLANS SUBMITTED. |
| NOW THAT THE CIRCUITING HAS FOR THE MOST PART BEEN |
| COMPLETED ON PLANS, THERE ARE SOME NEW COMMENTS BASED |
| ON CIRCUITS AS SHOWN. |
| |
| ** PLEASE KNOW THAT IT IS MOST HELPFUL WHEN A RESPONSE |
| LETTER OR COMMENTARY IS SUBMITTED FOR RESPONSE TO THE |
| REVIEW COMMENTS AS PREVIOUSLY NOTED. THIS WILL HELP IN |
| THE REVIEW PROCESS, HOWEVER NOT REQUIRED. |
| |
| ** PLEASE SEE ANY REFERENCES IN PLAN REVIEW NOTES TO |
| CHAPTER 1 OF THE FBC ARE THAT WHICH IS ADOPTED BY THE |
| CITY OF WEST PALM BEACH. |
| |
| 1) NOTE: PLEASE SEE PLANS ARE STILL INDICATING |
| TOWNHOUSE UNITS? PLEASE SEE BUILDING REVIEW COMMENTS AS |
| THESE ARE NOT TRUE TOWNHOUSES BY DEFINITIONS. |
| PLEASE SEE THAT IF THESE ARE INDEED FEE SIMPLE |
| "TOWNHOUSES" AS PER FBC DEFINITIONS, PLEASE SEE |
| REQUIREMENTS OF THE FBC AND ELECTRICAL CODE WHICH WOULD |
| CHANGE MANY ITEMS IN THE DESIGN AND PLEASE KNOW |
| SEPARATE PERMIT APPLICATIONS, PLANS AND FEES WOULD BE |
| REQUIRED ON EACH FEE SIMPLE TOWNHOUSE. PLEASE SEE AS |
| ALL UNITS ARE CONNECTED BY A COMMON AREA AND ONE |
| BUILDING THIS DOES NOT SEEM POSSIBLE. |
| PLEASE SEE COMMENTS FROM OTHER TRADES |
| FBC ADMIN SECTION 106.1.2 FOR ADDITIONAL INFORMATION. |
| |
| 2) NOTE:PLEASE SEE THAT THIS IS THE SAME COMMENT FROM |
| PREVIOUS REVIEW AND NO CHANGES HAVE BEEN MADE. PLEASE |
| KNOW THAT THIS WAS STATED AS BEING REQUIRED WHETHER OR |
| NOT COMMENT IS MADE BY ANY OTHER TRADE. |
| PLEASE SEE MISSING INFORMATION ON THE TITLE BLOCKS FOR |
| THE LANDSCAPE SHEETS AS REQUIRED PER FLORIDA |
| ADMINISTRATIVE CODE 61G1-16.004, AND FLORIDA STATUTES |
| 481.319. |
| PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION NUMBER, |
| PRINTED NAME, PRINTED LICENSE NUMBER ETC. |
| PLEASE SEE 481.221 AS PLANS ARE REQUIRED TO BE SIGNED |
| WITH LEGAL SIGNATURE AND DATED. |
| THIS COMMENT IS REQUIRED WHETHER OR NOT COMMENT IS MADE |
| BY ANY OTHER TRADE. |
| |
| 3) NOTE: PLEASE SEE FBC CHAPTER 13. |
| PLEASE SEE ANY "HOUSE" ROOMS WITH LIGHTING WILL REQUIRE |
| AUTOMATIC SHUT OFF OF LIGHTING PER 13-415.1.ABC.1.1, |
| .1.2, AND .1.3. THESE ROOMS ON PLANS DO NOT INDICATE |
| ANY LIGHTING? PLEASE CLARIFY. |
| |
| 4) NOTE: PLEASE SEE THAT AS FAR AS THIS REVIEW HAS |
| TAKEN PLACE, THIS PREVIOUS NOTE IS STILL APPLICABLE. |
| PLEASE SEE FBC ADMIN SECTION 109.3.6, 109.3.6.4.4 |
| WHICH REQUIRES THE STATEMENT FOR THRESHOLD PROJECTS ON |
| ALL ARCH AND ENG SHEETS. |
| " TO THE BEST OF THE ARCHITECT'S /OR ENGINEER'S |
| KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE |
| FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER |
| 633 OF THE FLORIDA STATUTES". |
| THIS IS REQUIRED FOR EACH DESIGN PROFESSIONAL ON |
| PLANS. |
| |
| 5) NOTE:PLEASE SEE THE NOTES ALSO STATED BY THE |
| BUILDING REVIEWER AS PREVIOUSLY NOTED AS IT SEEMS A FA |
| SYSTEM OF SOME TYPE IS REQUIRED FOR THE PARKING GARAGE |
| AREA. PLEASE KNOW THAT EVEN IF A SYSTEM IS GOING TO BE |
| UNDER A SEPARATE PERMIT, THE BASE BUILDING PLANS SHALL |
| INDICATE THE BASE INTENT IN DESIGN FOR LIFE SAFETY. FBC |
| 106.3.5.1.2. PLEASE SEE COMMENTS WITH RESPECT TO SMOKE |
| ALARM DEVICES IN UNITS. |
| |
| PLEASE CLARIFY THE TYPE FIRE PROTECTION BEING INSTALLED |
| FOR BUILDING. PLEASE SEE ARCHITECTURAL SHEETS REFERENCE |
| A 13R , HOWEVER PLEASE SEE NFPA-72 11-5.1.1, 11.8.3. |
| PLEASE SEE NFPA-72 DEFINITIONS AS PLANS CALL FOR SD FOR |
| SMOKE DETECTORS THIS IS OK, HOWEVER PLEASE KNOW IF |
| THESE ARE INDEED SMOKE DETECTORS AS DEFINED IN NFPA72, |
| THESE WOULD BE DEVICES WHICH ONLY DETECT AND WOULD |
| SIGNAL TO OTHER ALARM/HORN DEVICES. NO ALARM HORN |
| DEVICES ARE SHOWN. PLEASE INDICATE IF PART OF A FUTURE |
| LV FA SYSTEM. |
| |
| 6) NOTE: PLEASE SEE THAT THE CIRCUITING IS MISSING FROM |
| SEVERAL OF THE SMOKE ALARM DEVICES ON PLANS. PLEASE SEE |
| THAT ON THE UNITS WHICH DO INDICATE CIRCUITS, THE PLANS |
| INDICATE AS MANY AS 3,4 OR MORE CIRCUITS FOR THE SAME |
| SMOKE ALARMS WHICH ARE REQUIRED TO BE WIRED *IN-LINE* |
| PER NFPA-72 11.5.1.1.1. PLEASE KNOW AS THESE DEVICES |
| ARE WIRED INLINE AND IF ON MORE THAN ONE CIRCUIT AND/OR |
| PHASE THIS WOULD SEND 240V TO UNITS AS THEY ARE ALL |
| INTERCONNECTED. PLEASE COMPLETE CIRCUITING FOR THE |
| DEVICES WHICH ARE MISSING CIRCUITING AND PLEASE ADJUST |
| CIRCUITING SO THAT ALL *S* DEVICES ARE WIRED TO THE |
| SAME CIRCUIT. |
| |
| 7) NOTE: PLEASE BE SURE THE *S*/SMOKE ALARM DEVICES |
| ARE WIRED TO ONE OF THE EXISTING ARC FAULT CIRCUITS AS |
| REQUIRED PER 210.12 OF THE NEC. (SOME OF THE CIRCUITS |
| AS SHOWN ON SOME OF THE DEVICES AT THIS TIME ARE NOT |
| ARC FAULT CIRCUITS AS NOTED ON PANEL SCHEDULE) |
| PLEASE INDICATE THE CIRCUITS ON PANEL SCHEDULE WHICH |
| WILL CONTAIN THE AFCI BREAKERS. THIS MAY BE DONE WITH |
| AN ASTERISK WHICH CORRELATES TO NOTE BELOW PANEL |
| SCHEDULE OR BY SOME OTHER MEANS. |
| PLEASE SEE NOTE # 17 BELOW AS THIS WAS NOTED ON |
| PREVIOUS REVIEW. |
| |
| 8) NOTE:PLEASE SEE THIS NOTE REMAINS AS NO NOTES, OR |
| DETAIL WAS PROVIDED TO MEET THIS PREVIOUS NOTE. THE |
| SECTION OF CODE GIVEN WAS INCORRECT HOWEVER THE CORRECT |
| SECTION WAS GIVEN TO THE ENGINEER OVER A PHONE MEETING |
| AFTER THE INITIAL REVIEW. |
| PLEASE SEE THE CORRECTED SECTION HAS BEEN INSERTED. |
| THE SECTION GIVEN WAS FOR THE DESIGNER TO CERIFY THE |
| ENERGY CALCULATIONS WHICH WAS CORRECT ALSO. |
| PLEASE SEE FBC 2004 13-606.1.ABC.1.2.4 WHICH REQUIRES |
| THE TYPE OF RECESSED LIGHTS TO BE INSTALLED. PLEASE |
| NOTE ON PLANS ACCORDINGLY AND INDICATE FIXTURES. |
| |
| 9) NOTE:THIS NOTE WILL REMAIN AS THE NOTE #5 ABOVE IS |
| NOT CLEAR AT THIS TIME. THE MINIMUM LEVELS FOR DEVICE |
| IN GARAGE AREA WILL BE REQUIRED TO BE INDICATED. |
| PLEASE SEE FBC 2004 11-4.28.2, .3(4). PLEASE STATE ALL |
| MINIMUM LEVELS AS REQUIRED FOR ALL AREAS WHICH MAY |
| CONTAIN ANY FIRE HORN/STROBE DEVICES. AS IT IS NOT |
| KNOWN AT THIS TIME OF ANY FIRE ALARM PANEL WILL BE |
| REQUIRED FOR THE GARAGE OR BUILDING, PLEASE BE AWARE OF |
| THE SECTIONS GIVEN IN ORDER TO INDICATE THE LEVELS AS |
| REQUIRED IF A FA SYSTEM IS INSTALLED. 11-4.28.1. PLEASE |
| BE SURE TO SEE SECTIONS GIVEN FOR STROBE AND HORN |
| DEVICES FROM THE FBC AND PLEASE ALSO SEE NFPA-72. |
| PLEASE KNOW THAT THE FBC CHAPTER 11 REQUIREMENTS ARE |
| MORE STRINGENT AND THE MORE STRINGENT SHALL APPLY. |
| |
| 10) NOTE: THIS NOTE WILL REMAIN FROM PREVIOUS REVIEW AS |
| CONTROLS ETC ARE NOT CLEAR AT THIS TIME OR SHOWN ON |
| ELECTRICAL PLANS. |
| PLEASE SEE THAT SENSE THIS GARAGE SEEMS TO BE |
| CONSIDERED AN ENCLOSED GARAGE PLEASE SEE THAT THERE MAY |
| BE OTHER ELECTRICAL DEVICES WHICH MAY BE REQUIRED FOR |
| CO SENSORS ETC. TO BE SHOWN AS PART OF ANY LV |
| SYSTEMS/DEVICES ETC. |
| THIS IS ONLY NOTED. |
| |
| 11) NOTE: PLEASE SEE AS THIS IS ONE BUILDING; PLEASE |
| SEE 230.2 AS THE PROPOSED SERVICES ARE NOT GRANTED AS |
| SHOWN ON PLANS. PLEASE SEE THE SIZE OF THE SERVICES DO |
| NOT EXCEED THE RATINGS FOR 2K AMPS FOR THE ADDITIONAL |
| SERVICE. |
| PLANS AT THIS TIME ARE SHOWING AS MANY AS FOUR |
| SERVICES. PLEASE SEE AT THIS TIME ONLY TWO SERVICES |
| WILL BE GRANTED BY SPECIAL PERMISSION. THIS MAY BE DONE |
| BY ONE MAIN FOR EACH AND FEEDING A MLO METER*-CENTER OR |
| SERVICE WHICH WOULD CONTAIN THE MAIN AS PART OF THE |
| METER-CENTER. ONE WILL BE PERMITTED AT EACH SIDE OF THE |
| BUILDING AS SHOWN. |
| PLEASE SEE THAT SIGNAGE NOTES WILL BE REQUIRED ON PLANS |
| FOR CORRECT SIGNS TO BE INSTALLED PER 230.2E. PLEASE |
| KNOW THAT ALL SIGNS SHALL HAVE LETTERING A MINIMUM OF |
| 1INCH WITH A CONTRASTING BACKGROUND. |
| PLEASE REVISE SERVICE RISER DIAGRAM FOR GROUPING OF |
| MAINS AND SERVICES. |
| PLEASE SEE OTHER COMMENTS WITH RESPECT TO LOAD |
| CALCULATIONS. |
| PLEASE REVISE RISER DIAGRAM. |
| |
| 12) NOTE: PLEASE SEE 250.50, 250.104 ETC FOR MISSING |
| ATTACHMENTS FOR THE FIRE SPRINKLER LINE. |
| |
| 13) NOTE:PLEASE SEE AS NEW CIRCUITS ARE NOW SHOWN ON |
| PLANS, PLEASE SEE 210.52B1, 210.11C1, AND 220.16 AS THE |
| DINING ROOM RECEPTACLES ARE TO BE ON ONE OR MORE OF THE |
| SMALL APPLIANCE CIRCUITS. THESE CIRCUITS MUST BE |
| FIGURED AT 1500VA MINIMUM (1000VA SHOWN), MAY NOT FEED |
| ANY OTHER DEVICES WHICH ARE OUTSIDE THE DINING |
| DESIGNATED AREAS. |
| PLEASE ALSO SEE SOME PLANS WHICH INDICATE THE DINING |
| CIRCUIT AS CIRCUIT #25 DOES NOT SHOW ON PANEL SCHEDULE |
| AS THE PANEL SCHEDULE IS SHOWN INDICATING A *SPARE* |
| WITH A 1000VALOAD DESIGNATED. |
| PLEASE SEE UNIT B, C AND D AS THIS SCENARIO EXIST. |
| PLEASE SEE THIS WAS NOTED ON NOTE #25 ON PREVIOUS |
| REVIEW. |
| |
| 14) NOTE:PLEASE SEE SOME AREAS OF ROOMS DO NOT SEEM |
| TO MEET 210.52 FOR RECEPTACLE SPACING. PLEASE SEE SOME |
| UNITS WHICH RAIL AREAS ARE ACTUALLY PART OF THE ROOMS. |
| PLEASE ALSO SEE DINING ROOM WALLS WHICH ARE MISSING |
| DEVICES. PLEASE SEE UNITS A, B, C AND D. |
| NOTE #27 PREVIOUS REVIEW |
| |
| 15) NOTE: PLEASE SEE SOME AREAS WHICH A RECEPTACLE |
| DEVICE SEEMS TO BE SHOWN TO MEET 210.52H FOR HALLWAYS, |
| YET THIS DEVICE IS ACTUALLY LOCATED IN WHAT WOULD BE AN |
| EGRESS PATH AND WOULD CREATE A TRIPPING HAZARD. PLEASE |
| SEE PLANS FOR ALTERNATE LOCATIONS WHICH ARE PERHAPS ON |
| OPPOSITE WALLS; SOME ARE THE POWDER ROOM WALLS ETC |
| WHICH WOULD BE PERMITTED. |
| PLEASE SEE SOME REDLINED AREAS ON PLANS. PLEASE KNOW |
| THIS CAN BE GONE OVER ON THE PHONE AS LONG AS A SET OF |
| PLANS ARE STILL LOCATED IN THIS OFFICE. |
| NOTE #27 PREVIOUS REVIEW. |
| |
| 16) NOTE: PLEASE SEE PANELS SCHEDULE FOR ALL UNITS |
| WHICH CONTAIN A WHIRLPOOL TUB, HOWEVER THE LOAD |
| CALCULATIONS DO NOT INDICATE THIS LOAD OF THIS JACUZZI |
| TUB. PLEASE COORDINATE UNIT PANEL SCHEDULE AND REVISED |
| LOAD CALCULATIONS. |
| FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION. |
| NEC 680.71, 408.4. |
| |
| 17) NOTE: PLEASE LIST THE REQUIRED ARC FAULT PROTECTED |
| CIRCUITS ON THE PANEL SCHEDULE. PLEASE KNOW THE NOTE ON |
| PLANS IS NOT ENOUGH AT THIS TIME. PLEASE SEE THIS CAN |
| BE DONE WITH AN * AT EACH CIRCUIT TO THIS NOTE ONCE ALL |
| CIRCUITING IS PLACED ON PLANS. PLEASE BE SURE TO SEE |
| NOTE PERTAINING TO SMOKE ALARM/DETECTORS DEVICES AND |
| WHICH TYPE WILL BE INSTALLED. THIS WILL AFFECT THE |
| CIRCUITING AND INDICATION OF THE REQUIRED AFCI |
| PROTECTION. |
| 2002 NEC 210.12 |
| |
| 18) NOTE: PLEASE SEE THAT NOW LOAD CALCULATIONS HAVE |
| BEEN SUBMITTED, PLEASE SEE NOTES PERTAINING TO |
| ADDITIONAL SERVICES. PLEASE SEE THE LOAD SHOWN FOR |
| PANEL HP IS SHOWN AS ONE LOAD ON LOAD CALCULATIONS AND |
| A DIFFERENT LOAD ON PANEL SCHEDULE. |
| PLEASE ALSO SEE THIS PANEL IS BEING SHOWN WITH 42POLES, |
| YET THE PANEL SCHEDULE INFORMATION INDICATES ONLY |
| 30POLES. |
| PLEASE CORRELATE THE ABOVE. |
| FBC 106.1.2, 106.3.5.1.2 |
| |
| 19) NOTE: PLEASE SEE THERE ARE SEVERAL ELECTRICAL |
| DEVICES ON PLANS WHICH DO NOT INDICATE ANY CIRCUITING. |
| PLEASE SEE MASTER BATH GFI'S UNIT A, COMMON HALLS, |
| BEDROOMS ETC FOR UNIT C, AND SOME OTHERS IN OTHER |
| UNITS. |
| PLEASE SEE NOTE PERTAINING TO CIRCUITING OF SMOKE |
| ALARMS, DINING AND OTHER DEVICES. |
| 408.4, 310.16, 240.4. |
| FBC 106.3.1.2, 106.1.2 |
| |
| 20) NOTE: PLEASE SEE THIS NOTE FROM PREVIOUS REVIEW. |
| PLEASE SEE THE DEVICE HEIGHTS ARE SHOWN , HOWEVER |
| INSTALLATION AND NOTES AS THIS IS REQUIRED PER FHAR |
| 24CFR 100.205 SHOULD BE INDICATE ON PLANS AS THE |
| INSTALLATION OF DEVICES FOR OTHER CLEARANCES ETC ARE |
| REQUIRED. |
| AS NOTED ON PREVIOUS REVIEW* |
| PLEASE INDICATE ALL DEVICE HEIGHTS. PLEASE SEE IF THIS |
| IS GOING TO BE A MULTI-FAMILY BUILDING AS SHOWN, PLEASE |
| SEE FHAR 24CFR100.205 FOR FIRST FLOOR AT A MINIMUM. |
| PLEASE KNOW IF ANY VERTICAL ACCESSIBILITY IS INSTALLED, |
| THEN THESE DEVICE HEIGHTS AND LOCATIONS SHALL BE FOR |
| ALL FLOORS OR FLOORS THAT THE VERTICAL ACCESS IS |
| PROVIDED. |
| (15INCHES MIN FOR RECEPTS, 48INCHES MAX FOR SWITCHES, |
| ETC). |
| |
| 21) NOTE:PLEASE SEE 13-413.1ABC.1 OF THE 2004 FBC. |
| PLEASE INDICATE THE VOLTAGE DROP FOR FEEDERS/BRANCH |
| CIRCUITS. THIS CAN BE DONE IN A WORST CASE SCENARIO. |
| THIS WAS NOT NOTED IN PREVIOUS REVIEW AND IS A NEW |
| COMMENT. |
| |
| 22) NOTE: PLEASE SEE SOME SHEETS ARE NOW SHOWING AN |
| ADDRESS OF 2918 AND MANY SHEETS IN THE SET DO NOT |
| INDICATE ANY ADDRESS OF PROJECT AT ALL. |
| PLEASE SEE THE ADDRESSING REVIEWER'S COMMENTS AND |
| PLEASE SEE OUR COMPUTER SYSTEM FOR THIS PCN IS STILL |
| INDICATING 2900. PLEASE BE SURE NOT TO MAKE ANY CHANGES |
| UNTIL THE FINAL ADDRESS HAS BEEN ISSUED BY THE |
| ADDRESSING REVIEWER. |
| PLEASE SEE THAT THE ADDRESS FOR THIS PROJECT SHALL BE |
| PLACED ON THE TITLE BLOCKS. PLEASE KNOW AT THIS TIME, |
| THIS IS A MULTI-FAMILY SINGLE BUILDING WITH THE ADDRESS |
| OF 2900 BROADWAY. |
| THIS IS NOT AND HAS NOT BEEN SUBMITTED AS TOWNHOUSES, |
| OR CONDO'S. |
| FAC 61G15-23.002, FAC 61G1-16.004 |
| |
| 23) NOTE: PLEASE SEE THE HOUSE PANEL INDICATES *ALLEY |
| LIGHTS*, YET THESE CIRCUITS AND LIGHTING COULD NOT BE |
| LOCATED ON PLANS. |
| IF THESE ARE SITE LIGHTING POLES, PLEASE BE SURE TO |
| SUBMIT THE REQUIRED WIND LOAD CALCULATIONS AND |
| INFORMATION FOR BUILDING REVIEW. |
| IF THESE ARE NOT POLES PLEASE INDICATE ON PLANS. ARE |
| THE LIGHTS ON BACK OF BUILDING ACTUALLY THES LIGHTS, |
| ONLY THE CIRCUITING IS NOT SHOWN?? |
| PLEASE CLARIFY. |
| FBC 106.1.2 |
| |
| 24) NOTE: PLEASE SEE THE ATTACHED COPY OF FS |
| 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS. THIS IS |
| ONLY GIVEN AS A NOTICE AT THIS TIME. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |