Plan Review Notes
Plan Review Notes For Permit 06120129
Permit Number 06120129
Review Stop E
Sequence Number 2
Notes
Date Text
2007-04-14 15:57:58 
 ** UNSAT2ND REVIEW**
  
 ** PLEASE SEE THAT ITEMS ARE FROM PREVIOUS REVIEW;
 HOWEVER MOST ARE NEW DUE TO CHANGES IN PLANS AND ITEMS
 WHICH ARE NEW TO PLANS SUBMITTED.
 NOW THAT THE CIRCUITING HAS FOR THE MOST PART BEEN
 COMPLETED ON PLANS, THERE ARE SOME NEW COMMENTS BASED
 ON CIRCUITS AS SHOWN.
  
 ** PLEASE KNOW THAT IT IS MOST HELPFUL WHEN A RESPONSE
 LETTER OR COMMENTARY IS SUBMITTED FOR RESPONSE TO THE
 REVIEW COMMENTS AS PREVIOUSLY NOTED. THIS WILL HELP IN
 THE REVIEW PROCESS, HOWEVER NOT REQUIRED.
  
 ** PLEASE SEE ANY REFERENCES IN PLAN REVIEW NOTES TO
 CHAPTER 1 OF THE FBC ARE THAT WHICH IS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE SEE PLANS ARE STILL INDICATING
 TOWNHOUSE UNITS? PLEASE SEE BUILDING REVIEW COMMENTS AS
 THESE ARE NOT TRUE TOWNHOUSES BY DEFINITIONS.
 PLEASE SEE THAT IF THESE ARE INDEED FEE SIMPLE
 "TOWNHOUSES" AS PER FBC DEFINITIONS, PLEASE SEE
 REQUIREMENTS OF THE FBC AND ELECTRICAL CODE WHICH WOULD
 CHANGE MANY ITEMS IN THE DESIGN AND PLEASE KNOW
 SEPARATE PERMIT APPLICATIONS, PLANS AND FEES WOULD BE
 REQUIRED ON EACH FEE SIMPLE TOWNHOUSE. PLEASE SEE AS
 ALL UNITS ARE CONNECTED BY A COMMON AREA AND ONE
 BUILDING THIS DOES NOT SEEM POSSIBLE.
 PLEASE SEE COMMENTS FROM OTHER TRADES
 FBC ADMIN SECTION 106.1.2 FOR ADDITIONAL INFORMATION.
  
 2) NOTE:PLEASE SEE THAT THIS IS THE SAME COMMENT FROM
 PREVIOUS REVIEW AND NO CHANGES HAVE BEEN MADE. PLEASE
 KNOW THAT THIS WAS STATED AS BEING REQUIRED WHETHER OR
 NOT COMMENT IS MADE BY ANY OTHER TRADE.
 PLEASE SEE MISSING INFORMATION ON THE TITLE BLOCKS FOR
 THE LANDSCAPE SHEETS AS REQUIRED PER FLORIDA
 ADMINISTRATIVE CODE 61G1-16.004, AND FLORIDA STATUTES
 481.319.
 PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION NUMBER,
 PRINTED NAME, PRINTED LICENSE NUMBER ETC.
 PLEASE SEE 481.221 AS PLANS ARE REQUIRED TO BE SIGNED
 WITH LEGAL SIGNATURE AND DATED.
 THIS COMMENT IS REQUIRED WHETHER OR NOT COMMENT IS MADE
 BY ANY OTHER TRADE.
  
 3) NOTE: PLEASE SEE FBC CHAPTER 13.
 PLEASE SEE ANY "HOUSE" ROOMS WITH LIGHTING WILL REQUIRE
 AUTOMATIC SHUT OFF OF LIGHTING PER 13-415.1.ABC.1.1,
 .1.2, AND .1.3. THESE ROOMS ON PLANS DO NOT INDICATE
 ANY LIGHTING? PLEASE CLARIFY.
  
 4) NOTE: PLEASE SEE THAT AS FAR AS THIS REVIEW HAS
 TAKEN PLACE, THIS PREVIOUS NOTE IS STILL APPLICABLE.
 PLEASE SEE FBC ADMIN SECTION 109.3.6, 109.3.6.4.4
 WHICH REQUIRES THE STATEMENT FOR THRESHOLD PROJECTS ON
 ALL ARCH AND ENG SHEETS.
 " TO THE BEST OF THE ARCHITECT'S /OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER
 633 OF THE FLORIDA STATUTES".
 THIS IS REQUIRED FOR EACH DESIGN PROFESSIONAL ON
 PLANS.
  
 5) NOTE:PLEASE SEE THE NOTES ALSO STATED BY THE
 BUILDING REVIEWER AS PREVIOUSLY NOTED AS IT SEEMS A FA
 SYSTEM OF SOME TYPE IS REQUIRED FOR THE PARKING GARAGE
 AREA. PLEASE KNOW THAT EVEN IF A SYSTEM IS GOING TO BE
 UNDER A SEPARATE PERMIT, THE BASE BUILDING PLANS SHALL
 INDICATE THE BASE INTENT IN DESIGN FOR LIFE SAFETY. FBC
 106.3.5.1.2. PLEASE SEE COMMENTS WITH RESPECT TO SMOKE
 ALARM DEVICES IN UNITS.
  
 PLEASE CLARIFY THE TYPE FIRE PROTECTION BEING INSTALLED
 FOR BUILDING. PLEASE SEE ARCHITECTURAL SHEETS REFERENCE
 A 13R , HOWEVER PLEASE SEE NFPA-72 11-5.1.1, 11.8.3.
 PLEASE SEE NFPA-72 DEFINITIONS AS PLANS CALL FOR SD FOR
 SMOKE DETECTORS THIS IS OK, HOWEVER PLEASE KNOW IF
 THESE ARE INDEED SMOKE DETECTORS AS DEFINED IN NFPA72,
 THESE WOULD BE DEVICES WHICH ONLY DETECT AND WOULD
 SIGNAL TO OTHER ALARM/HORN DEVICES. NO ALARM HORN
 DEVICES ARE SHOWN. PLEASE INDICATE IF PART OF A FUTURE
 LV FA SYSTEM.
  
 6) NOTE: PLEASE SEE THAT THE CIRCUITING IS MISSING FROM
 SEVERAL OF THE SMOKE ALARM DEVICES ON PLANS. PLEASE SEE
 THAT ON THE UNITS WHICH DO INDICATE CIRCUITS, THE PLANS
 INDICATE AS MANY AS 3,4 OR MORE CIRCUITS FOR THE SAME
 SMOKE ALARMS WHICH ARE REQUIRED TO BE WIRED *IN-LINE*
 PER NFPA-72 11.5.1.1.1. PLEASE KNOW AS THESE DEVICES
 ARE WIRED INLINE AND IF ON MORE THAN ONE CIRCUIT AND/OR
 PHASE THIS WOULD SEND 240V TO UNITS AS THEY ARE ALL
 INTERCONNECTED. PLEASE COMPLETE CIRCUITING FOR THE
 DEVICES WHICH ARE MISSING CIRCUITING AND PLEASE ADJUST
 CIRCUITING SO THAT ALL *S* DEVICES ARE WIRED TO THE
 SAME CIRCUIT.
  
 7) NOTE: PLEASE BE SURE THE *S*/SMOKE ALARM DEVICES
 ARE WIRED TO ONE OF THE EXISTING ARC FAULT CIRCUITS AS
 REQUIRED PER 210.12 OF THE NEC. (SOME OF THE CIRCUITS
 AS SHOWN ON SOME OF THE DEVICES AT THIS TIME ARE NOT
 ARC FAULT CIRCUITS AS NOTED ON PANEL SCHEDULE)
 PLEASE INDICATE THE CIRCUITS ON PANEL SCHEDULE WHICH
 WILL CONTAIN THE AFCI BREAKERS. THIS MAY BE DONE WITH
 AN ASTERISK WHICH CORRELATES TO NOTE BELOW PANEL
 SCHEDULE OR BY SOME OTHER MEANS.
 PLEASE SEE NOTE # 17 BELOW AS THIS WAS NOTED ON
 PREVIOUS REVIEW.
  
 8) NOTE:PLEASE SEE THIS NOTE REMAINS AS NO NOTES, OR
 DETAIL WAS PROVIDED TO MEET THIS PREVIOUS NOTE. THE
 SECTION OF CODE GIVEN WAS INCORRECT HOWEVER THE CORRECT
 SECTION WAS GIVEN TO THE ENGINEER OVER A PHONE MEETING
 AFTER THE INITIAL REVIEW.
 PLEASE SEE THE CORRECTED SECTION HAS BEEN INSERTED.
 THE SECTION GIVEN WAS FOR THE DESIGNER TO CERIFY THE
 ENERGY CALCULATIONS WHICH WAS CORRECT ALSO.
 PLEASE SEE FBC 2004 13-606.1.ABC.1.2.4 WHICH REQUIRES
 THE TYPE OF RECESSED LIGHTS TO BE INSTALLED. PLEASE
 NOTE ON PLANS ACCORDINGLY AND INDICATE FIXTURES.
  
 9) NOTE:THIS NOTE WILL REMAIN AS THE NOTE #5 ABOVE IS
 NOT CLEAR AT THIS TIME. THE MINIMUM LEVELS FOR DEVICE
 IN GARAGE AREA WILL BE REQUIRED TO BE INDICATED.
 PLEASE SEE FBC 2004 11-4.28.2, .3(4). PLEASE STATE ALL
 MINIMUM LEVELS AS REQUIRED FOR ALL AREAS WHICH MAY
 CONTAIN ANY FIRE HORN/STROBE DEVICES. AS IT IS NOT
 KNOWN AT THIS TIME OF ANY FIRE ALARM PANEL WILL BE
 REQUIRED FOR THE GARAGE OR BUILDING, PLEASE BE AWARE OF
 THE SECTIONS GIVEN IN ORDER TO INDICATE THE LEVELS AS
 REQUIRED IF A FA SYSTEM IS INSTALLED. 11-4.28.1. PLEASE
 BE SURE TO SEE SECTIONS GIVEN FOR STROBE AND HORN
 DEVICES FROM THE FBC AND PLEASE ALSO SEE NFPA-72.
 PLEASE KNOW THAT THE FBC CHAPTER 11 REQUIREMENTS ARE
 MORE STRINGENT AND THE MORE STRINGENT SHALL APPLY.
  
 10) NOTE: THIS NOTE WILL REMAIN FROM PREVIOUS REVIEW AS
 CONTROLS ETC ARE NOT CLEAR AT THIS TIME OR SHOWN ON
 ELECTRICAL PLANS.
 PLEASE SEE THAT SENSE THIS GARAGE SEEMS TO BE
 CONSIDERED AN ENCLOSED GARAGE PLEASE SEE THAT THERE MAY
 BE OTHER ELECTRICAL DEVICES WHICH MAY BE REQUIRED FOR
 CO SENSORS ETC. TO BE SHOWN AS PART OF ANY LV
 SYSTEMS/DEVICES ETC.
 THIS IS ONLY NOTED.
  
 11) NOTE: PLEASE SEE AS THIS IS ONE BUILDING; PLEASE
 SEE 230.2 AS THE PROPOSED SERVICES ARE NOT GRANTED AS
 SHOWN ON PLANS. PLEASE SEE THE SIZE OF THE SERVICES DO
 NOT EXCEED THE RATINGS FOR 2K AMPS FOR THE ADDITIONAL
 SERVICE.
 PLANS AT THIS TIME ARE SHOWING AS MANY AS FOUR
 SERVICES. PLEASE SEE AT THIS TIME ONLY TWO SERVICES
 WILL BE GRANTED BY SPECIAL PERMISSION. THIS MAY BE DONE
 BY ONE MAIN FOR EACH AND FEEDING A MLO METER*-CENTER OR
 SERVICE WHICH WOULD CONTAIN THE MAIN AS PART OF THE
 METER-CENTER. ONE WILL BE PERMITTED AT EACH SIDE OF THE
 BUILDING AS SHOWN.
 PLEASE SEE THAT SIGNAGE NOTES WILL BE REQUIRED ON PLANS
 FOR CORRECT SIGNS TO BE INSTALLED PER 230.2E. PLEASE
 KNOW THAT ALL SIGNS SHALL HAVE LETTERING A MINIMUM OF
 1INCH WITH A CONTRASTING BACKGROUND.
 PLEASE REVISE SERVICE RISER DIAGRAM FOR GROUPING OF
 MAINS AND SERVICES.
 PLEASE SEE OTHER COMMENTS WITH RESPECT TO LOAD
 CALCULATIONS.
 PLEASE REVISE RISER DIAGRAM.
  
 12) NOTE: PLEASE SEE 250.50, 250.104 ETC FOR MISSING
 ATTACHMENTS FOR THE FIRE SPRINKLER LINE.
  
 13) NOTE:PLEASE SEE AS NEW CIRCUITS ARE NOW SHOWN ON
 PLANS, PLEASE SEE 210.52B1, 210.11C1, AND 220.16 AS THE
 DINING ROOM RECEPTACLES ARE TO BE ON ONE OR MORE OF THE
 SMALL APPLIANCE CIRCUITS. THESE CIRCUITS MUST BE
 FIGURED AT 1500VA MINIMUM (1000VA SHOWN), MAY NOT FEED
 ANY OTHER DEVICES WHICH ARE OUTSIDE THE DINING
 DESIGNATED AREAS.
 PLEASE ALSO SEE SOME PLANS WHICH INDICATE THE DINING
 CIRCUIT AS CIRCUIT #25 DOES NOT SHOW ON PANEL SCHEDULE
 AS THE PANEL SCHEDULE IS SHOWN INDICATING A *SPARE*
 WITH A 1000VALOAD DESIGNATED.
 PLEASE SEE UNIT B, C AND D AS THIS SCENARIO EXIST.
 PLEASE SEE THIS WAS NOTED ON NOTE #25 ON PREVIOUS
 REVIEW.
  
 14) NOTE:PLEASE SEE SOME AREAS OF ROOMS DO NOT SEEM
 TO MEET 210.52 FOR RECEPTACLE SPACING. PLEASE SEE SOME
 UNITS WHICH RAIL AREAS ARE ACTUALLY PART OF THE ROOMS.
 PLEASE ALSO SEE DINING ROOM WALLS WHICH ARE MISSING
 DEVICES. PLEASE SEE UNITS A, B, C AND D.
 NOTE #27 PREVIOUS REVIEW
  
 15) NOTE: PLEASE SEE SOME AREAS WHICH A RECEPTACLE
 DEVICE SEEMS TO BE SHOWN TO MEET 210.52H FOR HALLWAYS,
 YET THIS DEVICE IS ACTUALLY LOCATED IN WHAT WOULD BE AN
 EGRESS PATH AND WOULD CREATE A TRIPPING HAZARD. PLEASE
 SEE PLANS FOR ALTERNATE LOCATIONS WHICH ARE PERHAPS ON
 OPPOSITE WALLS; SOME ARE THE POWDER ROOM WALLS ETC
 WHICH WOULD BE PERMITTED.
 PLEASE SEE SOME REDLINED AREAS ON PLANS. PLEASE KNOW
 THIS CAN BE GONE OVER ON THE PHONE AS LONG AS A SET OF
 PLANS ARE STILL LOCATED IN THIS OFFICE.
 NOTE #27 PREVIOUS REVIEW.
  
 16) NOTE: PLEASE SEE PANELS SCHEDULE FOR ALL UNITS
 WHICH CONTAIN A WHIRLPOOL TUB, HOWEVER THE LOAD
 CALCULATIONS DO NOT INDICATE THIS LOAD OF THIS JACUZZI
 TUB. PLEASE COORDINATE UNIT PANEL SCHEDULE AND REVISED
 LOAD CALCULATIONS.
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION.
 NEC 680.71, 408.4.
  
 17) NOTE: PLEASE LIST THE REQUIRED ARC FAULT PROTECTED
 CIRCUITS ON THE PANEL SCHEDULE. PLEASE KNOW THE NOTE ON
 PLANS IS NOT ENOUGH AT THIS TIME. PLEASE SEE THIS CAN
 BE DONE WITH AN * AT EACH CIRCUIT TO THIS NOTE ONCE ALL
 CIRCUITING IS PLACED ON PLANS. PLEASE BE SURE TO SEE
 NOTE PERTAINING TO SMOKE ALARM/DETECTORS DEVICES AND
 WHICH TYPE WILL BE INSTALLED. THIS WILL AFFECT THE
 CIRCUITING AND INDICATION OF THE REQUIRED AFCI
 PROTECTION.
 2002 NEC 210.12
  
 18) NOTE: PLEASE SEE THAT NOW LOAD CALCULATIONS HAVE
 BEEN SUBMITTED, PLEASE SEE NOTES PERTAINING TO
 ADDITIONAL SERVICES. PLEASE SEE THE LOAD SHOWN FOR
 PANEL HP IS SHOWN AS ONE LOAD ON LOAD CALCULATIONS AND
 A DIFFERENT LOAD ON PANEL SCHEDULE.
 PLEASE ALSO SEE THIS PANEL IS BEING SHOWN WITH 42POLES,
 YET THE PANEL SCHEDULE INFORMATION INDICATES ONLY
 30POLES.
 PLEASE CORRELATE THE ABOVE.
 FBC 106.1.2, 106.3.5.1.2
  
 19) NOTE: PLEASE SEE THERE ARE SEVERAL ELECTRICAL
 DEVICES ON PLANS WHICH DO NOT INDICATE ANY CIRCUITING.
 PLEASE SEE MASTER BATH GFI'S UNIT A, COMMON HALLS,
 BEDROOMS ETC FOR UNIT C, AND SOME OTHERS IN OTHER
 UNITS.
 PLEASE SEE NOTE PERTAINING TO CIRCUITING OF SMOKE
 ALARMS, DINING AND OTHER DEVICES.
 408.4, 310.16, 240.4.
 FBC 106.3.1.2, 106.1.2
  
 20) NOTE: PLEASE SEE THIS NOTE FROM PREVIOUS REVIEW.
 PLEASE SEE THE DEVICE HEIGHTS ARE SHOWN , HOWEVER
 INSTALLATION AND NOTES AS THIS IS REQUIRED PER FHAR
 24CFR 100.205 SHOULD BE INDICATE ON PLANS AS THE
 INSTALLATION OF DEVICES FOR OTHER CLEARANCES ETC ARE
 REQUIRED.
 AS NOTED ON PREVIOUS REVIEW*
 PLEASE INDICATE ALL DEVICE HEIGHTS. PLEASE SEE IF THIS
 IS GOING TO BE A MULTI-FAMILY BUILDING AS SHOWN, PLEASE
 SEE FHAR 24CFR100.205 FOR FIRST FLOOR AT A MINIMUM.
 PLEASE KNOW IF ANY VERTICAL ACCESSIBILITY IS INSTALLED,
 THEN THESE DEVICE HEIGHTS AND LOCATIONS SHALL BE FOR
 ALL FLOORS OR FLOORS THAT THE VERTICAL ACCESS IS
 PROVIDED.
 (15INCHES MIN FOR RECEPTS, 48INCHES MAX FOR SWITCHES,
 ETC).
  
 21) NOTE:PLEASE SEE 13-413.1ABC.1 OF THE 2004 FBC.
 PLEASE INDICATE THE VOLTAGE DROP FOR FEEDERS/BRANCH
 CIRCUITS. THIS CAN BE DONE IN A WORST CASE SCENARIO.
 THIS WAS NOT NOTED IN PREVIOUS REVIEW AND IS A NEW
 COMMENT.
  
 22) NOTE: PLEASE SEE SOME SHEETS ARE NOW SHOWING AN
 ADDRESS OF 2918 AND MANY SHEETS IN THE SET DO NOT
 INDICATE ANY ADDRESS OF PROJECT AT ALL.
 PLEASE SEE THE ADDRESSING REVIEWER'S COMMENTS AND
 PLEASE SEE OUR COMPUTER SYSTEM FOR THIS PCN IS STILL
 INDICATING 2900. PLEASE BE SURE NOT TO MAKE ANY CHANGES
 UNTIL THE FINAL ADDRESS HAS BEEN ISSUED BY THE
 ADDRESSING REVIEWER.
 PLEASE SEE THAT THE ADDRESS FOR THIS PROJECT SHALL BE
 PLACED ON THE TITLE BLOCKS. PLEASE KNOW AT THIS TIME,
 THIS IS A MULTI-FAMILY SINGLE BUILDING WITH THE ADDRESS
 OF 2900 BROADWAY.
 THIS IS NOT AND HAS NOT BEEN SUBMITTED AS TOWNHOUSES,
 OR CONDO'S.
 FAC 61G15-23.002, FAC 61G1-16.004
  
 23) NOTE: PLEASE SEE THE HOUSE PANEL INDICATES *ALLEY
 LIGHTS*, YET THESE CIRCUITS AND LIGHTING COULD NOT BE
 LOCATED ON PLANS.
 IF THESE ARE SITE LIGHTING POLES, PLEASE BE SURE TO
 SUBMIT THE REQUIRED WIND LOAD CALCULATIONS AND
 INFORMATION FOR BUILDING REVIEW.
 IF THESE ARE NOT POLES PLEASE INDICATE ON PLANS. ARE
 THE LIGHTS ON BACK OF BUILDING ACTUALLY THES LIGHTS,
 ONLY THE CIRCUITING IS NOT SHOWN??
 PLEASE CLARIFY.
 FBC 106.1.2
  
 24) NOTE: PLEASE SEE THE ATTACHED COPY OF FS
 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS. THIS IS
 ONLY GIVEN AS A NOTICE AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717