2007-02-03 12:58:40 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. ALL ARCHITECTURAL SHEETS. THE FIRM LICENSE NUMBER, |
| (CERTIFICATE OF AUTHORIZATION), IS REQUIRED IN THE |
| TITLE BLOCK OF EACH SHEET. FAC 61G1-16.004(2) & FS |
| 481.219, 481.2055. |
| |
| 2. SHT A3.4 SUBMIT CALCULATIONS FOR PRIMARY AND |
| SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOTAGE OF EACH |
| AREA AS WELL AS 1/2 AREA OF ALL VERTICAL WALLS |
| INCLUDING PARAPETS. ALSO INDICATE ANY AREA OF A ROOF |
| THAT DRAINS FROM ABOVE IF APPLICABLE. SECTIONS 1106 & |
| 1107 WITH ALL SUBSECTIONS. |
| |
| 3. SHT A3.4 DETAIL 4, SECONDARY DRAINS SHALL BE A |
| MINIMUM 2" HIGHER THAN THE MAIN DRAIN. AS SHOWN THEY |
| ARE ONLY ABOUT 3/4" ABOVE THE MAIN DRAINS. THIS IS |
| REQUIRED SO THAT THE SECONDARY DRAINS WILL NOT DRAIN |
| STORM WATER UNLESS THERE IS A BLOCKAGE IN THE PRIMARY |
| DRAINS.--SUBMIT A DETAIL SHOWING THE ELEVATION AT |
| THE FLOOR AT THE PATIO DOOR, AND INDICATE THE ELEVATION |
| OF THE PRIMARY DRAIN AND THE SECONDARY DRAIN. SECTION |
| 106.1.1. |
| |
| 4. SHT A3.5 SHOWS 6" OVERFLOW DRAINS CONNECTING TO |
| MANHOLES. SECTION 1107.2 REQUIRES THE DISCHARGE TO BE |
| ABOVE GRADE IN AN OBSERVABLE LOCATION. PLEASE CHANGE |
| TERMINATION POINT FOR THE OVERFLOW DRAINS.--ONE 7" |
| DOWNSPOUT DOES NOT SHOW THE PIPING TO THE MANHOLE. |
| PLEASE SHOW ALL PIPING. SECTION 106.1.1. |
| |
| 5. SHTS A4.1 & A5.1. SHT A4.1 SHOWS THE GUTTER TO BE |
| CONTINUOUS AROUND THE INSIDE OF THE BLDG ROOF EXCEPT AT |
| THE CHIMNEYS. SHT A5.1 ONLY SHOWS THE GUTTER AT THE |
| MAIN ROOF SECTIONS, AND NO GUTTER AT THE HIP ROOF |
| SECTIONS. ALSO NO DOWNSPOUTS ARE INDICATED AT THE HIP |
| ROOF SECTIONS. PLEASE CLARIFY. SECTION 106.1.1. |
| |
| 6. ALL PLUMBING, MECHANICAL, ELECTRICAL & SL SHEETS. |
| THE ENGINEERS SEAL SHALL IMPRESS THE REQUIRED |
| INFORMATION ON EACH SHEET. MANY SHEETS ONLY SHOW A |
| PORTION OF REQUIRED INFORMATION. PLEASE MAKE SURE ALL |
| INFORMATION REQUIRED BY FAC 61G15-23.001(1)(2), |
| 61G15-23.002(1)(2) AND FS 471.025 IS IMPRESSED ON EACH |
| SHEET WHEN SEALING THE PLANS. |
| |
| 7. SHT P-1 THE SANITARY PARTIAL RISER DIAGRAMS DO NOT |
| REFLECT THE FLOOR PLAN IN MANY INSTANCES. ALL OFFSETS |
| SHALL BE SHOWN ON THE RISER DIAGRAM, SOME EXTRA PIPING |
| IS SHOWN, SOME FIXTURE BRANCH LINES ARE NOT SHOWN.-- |
| THE AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL |
| CONNECT TO A BRANCH DRAIN OR A DRAINAGE STACK A MINIMUM |
| OF 3" IN DIAMETER. SECTION 406.3.-- SEE RED LINE |
| NOTES ON ONE SET OF PLUMBING PLANS. SECTION 106.1.1. |
| |
| 8. SHT P-2 THE SANITARY PARTIAL RISER DIAGRAMS DO NOT |
| REFLECT THE FLOOR PLAN IN MANY INSTANCES. ALL OFFSETS |
| SHALL BE SHOWN ON THE RISER DIAGRAM, SOME EXTRA PIPING |
| IS SHOWN, SOME FIXTURE BRANCH LINES ARE NOT SHOWN, THE |
| VENT & SANT LINES ARE CROSSED FROM FLOOR TO FLOOR.-- |
| THE AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL |
| CONNECT TO A BRANCH DRAIN OR A DRAINAGE STACK A MINIMUM |
| OF 3" IN DIAMETER. SECTION 406.3.-- SEE RED LINE |
| NOTES ON ONE SET OF PLUMBING PLANS. SECTION 106.1.1. |
| |
| 9. SHT P-3 THE SANITARY PARTIAL RISER DIAGRAMS DO NOT |
| REFLECT THE FLOOR PLAN IN MANY INSTANCES. ALL OFFSETS |
| SHALL BE SHOWN ON THE RISER DIAGRAM, SOME EXTRA PIPING |
| IS SHOWN, SOME FIXTURE BRANCH LINES ARE NOT SHOWN, BATH |
| 2 INDICATES A TUB ON THE RISER, BUT SHOWS A SHOWER ON |
| THE FLOOR PLAN. THE KITCHEN SHOWS A 3" TO THE 3RD |
| FLOOR. PLEASE INDICATE WHERE THIS LINE IS TERMINATING. |
| --THE AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL |
| CONNECT TO A BRANCH DRAIN OR A DRAINAGE STACK A MINIMUM |
| OF 3" IN DIAMETER. SECTION 406.3.-- SEE RED LINE |
| NOTES ON ONE SET OF PLUMBING PLANS. SECTION 106.1.1. |
| |
| 10. SHT P-4 THE SANITARY PARTIAL RISER DIAGRAMS DO NOT |
| REFLECT THE FLOOR PLAN IN MANY INSTANCES. ALL OFFSETS |
| SHALL BE SHOWN ON THE RISER DIAGRAM, SOME EXTRA PIPING |
| IS SHOWN, SOME FIXTURE BRANCH LINES ARE NOT SHOWN. THE |
| VENT FROM THE FIRST FLOOR, BATHROOM 3 IS NOT SHOWN ON |
| THE FLOOR PLAN OF THE SECOND FLOOR. --THE |
| AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL CONNECT TO |
| A BRANCH DRAIN OR A DRAINAGE STACK A MINIMUM OF 3" IN |
| DIAMETER. SECTION 406.3.-- SEE RED LINE NOTES ON ONE |
| SET OF PLUMBING PLANS. SECTION 106.1.1. |
| |
| 11. SUBMIT A WATER RISER DIAGRAM FOR EACH TYPE OF UNIT. |
| SHOW ALL PIPE SIZES, VALVES AND WATER HAMMER ARRESTORS |
| REQUIRED BY SECTION 604.9. (ICE MAKERS, DISHWASHERS, & |
| WASH MACHINES). SECTION 106.3.5.1.3(3)(13). |
| |
| 12. SUBMIT A STORM RISER DIAGRAM FOR THE PRIMARY |
| DRAINAGE AND SECONDARY DRAINAGE SYSTEMS. SHOW ALL PIPE |
| SIZES, OFFSETS, AND INDICATE SQUARE FOOTAGE BEING |
| DRAINED.SECTION 106.3.5.1.3(7)(13). |
| |
| 13. SHT P-5CONDENSATE RISER DIAGRAM. THE CONDENSATE |
| SHALL HAVE A RELIEF VENT, (RETURN BEND), INSTALLED AS |
| THE CONDENSATE EXITS THE BUILDING. |
| |
| 14. SHT P-5 WATER HEATER DETAIL. PLEASE INDICATE THE |
| TERMINATION POINT FOR THE EMERGNECY PAN DRAIN AND THE |
| T/P RELIEF DISCHARGE LINE. SECTIONS 504.6.1 & 504.7.2. |
| |
| 15. SHT IR-1 THE CONTROLLER AND THE RAIN SENSOR LOCTION |
| ARE REQUIRED ON THE PLAN. SECTION 106.1.1.--THE |
| BACKFLOW PREVENTOR SHALL BE INSTALLED BYA LICENCED |
| PLUMBING CONTRACTOR.--A SEPARATE IRRIGATION PERMIT |
| IS REQUIRED. SECTION 105.1. |
| |
| 16. SHTS IR-1, LP-1 & LP-2 LANDSCAPE ARCHITECT LICENSE |
| IS NULL & VOID PER DBPR WESITE. (SEE ATTACHED SHEET). |
| ONE SET OF SHEETS SHALL BE RETAINED FOR POSSIBLE REVIEW |
| BY THE STATE LANDSCAPE ARCHITECTURAL BOARD AS THIS SEAL |
| HAS BEEN NULL & VOID SINCE 11/30/95. |
| |
| 17. SHTS IR-1, LP-1 & LP-2THE LANDSCAPE FIRM LICENSE |
| NUMBER AS WELL AS THE PRINTED NAME OF THE PERSON |
| SEALING THE DOCUMENT SHALL BE IN THE TITLE BLOCK OF |
| EACH SHEET. FAC 61G1-16.004(2)(6) & FS 481.2055. |
| |
| 18. THE MANHOLES, TRENCH DRAINS, STORM DRAINS AND |
| RELATED PIPING SHALL BE DESIGNED BY THE BUILDING |
| ENGINEER, AND INSTALLED BY THE PLUMBING CONTRACTOR AS |
| THIS IS WITHIN THE FOOTPRINT OF THE BUILDING. THE CIVIL |
| ENGINEER, AND THE SITE CONTRACTOR CAN ONLY DESIGN AND |
| INSTALL UP TO FIVE FEET OF THE BUILDING STRUCTURE. FS |
| 489. |
| |
| REVIEW BY KEN STEVENS |