2007-01-29 14:27:34 | ----------------DENIED----------------- |
| |
| 1.PAGE M1, UNIT A 3RD FLOOR: PLAN SHOWS WASHER/DRYER IN |
| CLOSET WITH AIR HANDLER. CLOTHES WASHERS, CLOTHES |
| DRYERS SHALL NOT BE LOCATED IN MECHANICAL CLOSETS USED |
| AS RETURN AIR PLENUMS PER FBC SEC. 13-610.1.ABC.3.7 |
| |
| 2.PAGE M1, UNIT A 3RD FLOOR: PLAN SHOWS 10X3 EXHAUST |
| DUCT IN A/C CLOSET. FOR PURPOSES OF CONTAMINATION |
| PREVENTION, EXHAUST DUCTS UNDER POSITIVE PRESSURE SHALL |
| NOT EXTEND INTO OR PASS THROUGH DUCTS OR PLENUMS PER |
| FBC,M 601.3 |
| |
| 3.GARAGE EXHAUST FANS ARE CALLED FOR ON EF SCHEDULE. |
| FANS ALONG WITH DUCTS AND DISCHARGE LOCATIONS ARE NOT |
| SHOWN ON MECHANICAL PLAN. |
| |
| 4.FAN SCHEDULE SHOWS EF 3 (GARAGE) TO BE CONTROLLED BY |
| A TIME CLOCK. THIS FAN SHOULD RUN CONTINUOUS PER FBC,M |
| T403.3 |
| |
| 5.FAN SCHEDULE: NOTES 1,2 DO NOT USUALLY APPLY TO |
| 'RESIDENTIAL' TYPE CEILING MOUNTED EXHAUST FANS. IS THE |
| INTENT TO HAVE THESE ITEMS INSTALLED ON BATHROOM |
| EXHAUST FANS? |
| |
| 6.FAN SCHEDULE SHOWS THREE DIFFERENT FAN TYPES. FANS |
| ARE NOT IDENTIFIED BY TYPE ON MECHANICAL PLANS. PLEASE |
| INDICATE ON PLAN WHICH TYPE OF FAN GOES IN EACH |
| LOCATION. |
| |
| 7.FBC,M 601.4 REQUIRES BALANCED RETURN IN ALL HABITABLE |
| ROOMS. A PRESSURE DIFFERENTIAL OF .01" WC OR LESS IS |
| REQUIRED UNLESS RETURNS ARE DESIGNED TO MEET THE |
| EXCEPTIONS AS STATED IN THIS SECTION. IF RETURNS ARE |
| NOT DESIGNED TO THESE EXCEPTIONS, A FIELD TEST WILL BE |
| REQUIRED AT FINAL INSPECTION TO DETERMINE IF PRESSURE |
| DIFFERENTIAL IS CODE COMPLIANT. |
| |
| 8.HVAC SPECIFICATIONS NOTE # 19 CITES 2001 FBC(M) TABLE |
| 403.3. PLEASE REFERENCE 2004 FBC(M). ALSO TABLE 403.3 |
| DOES NOT RELATE TO CONDENSATE OVERFLOW PROTECTION. |
| PLEASE CLARIFY (307.2.3 RELATES TO CONDENSATE |
| DISPOSAL/OVERFLOW PROTECTION) |
| |
| 9.HVAC SPECIFICATIONS NOTE #24 INDICATES FRESH AIR |
| DAMPERS TO BE CONTROLLED BY T-STAT. AHU SCHEDULE STATES |
| MECHANICAL FRESH AIR IS NOT REQUIRED. PLEASE CLARIFY. |
| |
| 10. PLEASE PROVIDE DETAIL SHOWING BATH AND DRYER |
| EXHAUST TERMINATIONS AT ROOF. |
| |