2007-02-09 16:29:33*****DENIED*****
  
  
 01.THE COMPLETE AND/OR ACTUAL ADDRESS OF THE PROJECT
 SITE SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN
 SHEET.
  
 02.NFPA 101-2003 EDITION AND THE FLORIDA FIRE
 PREVENTION CODE SHALL BE REFERENCED.
  
 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 04.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT HINDER OR INTERFERE WITH EMERGENCY ACCESS RESPONSE
 TO THE SAID PROPERTY OR VICINITY THEREOF (INCLUDING
 FIRE HYDRANTS AND FIRE LANES).
  
 05.ALL PAVEMENT ROAD SYSTEMS SHALL BE CAPABLE OF
 SUPPORTING 32 TONS FOR FIRE APPARATUS/EQUIPMENT.
  
 06. FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND AN
 UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13
 FEET 6 INCHES.
  
 07.LANDSCAPING SHALL NOT OBSTRUCT OR INTERFERE WITH
 FIRE PROTECTION EQUIPMENT.PROPER CLEARANCES SHALL BE
 MAINTAINED AT ALL TIMES.
  
 08.INDICATE THE LOCATION OF THE FIRE HYDRANT(S) IN
 THE VICINITY OF THE SITE.BE ADVISED THAT IF THE
 HYDRANT(S) IS GREATER THAN 500 FEET, AN ADDITIONAL
 HYDRANT SHALL BE REQUIRED.
  
 09.ON THE APPROPIATE EXTERIOR ELEVATION, SHOW/DISPLAY
 THE NUMERICAL ADDRESS FOR THE BUILDINGS TO BE VISIBLE
 FROM BROADWAY AVENUE.ONCE EMERGENCY RESPONDERS ARE
 INSIDE OF THE COMPLEX, HOW ARE BUILDINGS DISTINGUISHED
 FROM EACH OTHER.
  
 10.IN ADDITION TO THE EXTERIOR ELEVATION DETAILS ON
 SHEET A5.2 AND A5.2, SPECIFY ELEVATIONS AS NORTH, EAST,
 WEST, AND SOUTH.
  
 11.PLEASE INDICATE IF THIS BUILDING WILL BE EQUIPPED
 WITH A FIRE ALARM SYSTEM.BE ADVISED THAT SMOKE
 DETECTORS, AS LEGENDED ON SHEET E-1, ARE TIED INTO A
 FIRE ALARM SYSTEM.SMOKE ALARMS ON THE OTHER HAND ARE
 NOT TIED INTO A FIRE ALARM SYSTEM.
  
 12.ON SHEET FS-6, PLEASE BE ADVISED THAT A 2 1/2"
 SINGLE INLET FIRE DEPARTMENT CONNECTION W/CHECK VALVE
 WILL BE REQUIRED.
  
 13.ON SHEET FS-6, THE FIRE SPRINKLER SYSTEM IS TO BE
 MONITORED.IT SHALL BE PROVIDED WITH AN APPROVED ALARM
 INITIATION DEVICE THAT OPERATES WHEN THE FLOW OF WATER
 IS EQUAL OR GREATER THAN THAT FROM A SINGLE AUTOMATIC
 SPRINKLER.
  
 14.IN REFERENCE TO THE HYDRAULIC CALCULATIONS THAT
 WERE SUBMITTED:3RD FLOOR UNIT-A SYSTEM 4, 3RD FLOOR
 UNIT-B SYSTEM 1, 3RD FLOOR UNIT-C SYSTEM 2, ALL SHOW AN
 UNACCEPTABLE SAFETY MARGIN.AS PER WPBFR, A SAFETY
 MARGIN OF AT LEAST 5.0 PSI IS REQUIRED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  