2007-02-09 16:29:33 | *****DENIED***** |
| |
| |
| 01.THE COMPLETE AND/OR ACTUAL ADDRESS OF THE PROJECT |
| SITE SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN |
| SHEET. |
| |
| 02.NFPA 101-2003 EDITION AND THE FLORIDA FIRE |
| PREVENTION CODE SHALL BE REFERENCED. |
| |
| 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| |
| 04.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL |
| NOT HINDER OR INTERFERE WITH EMERGENCY ACCESS RESPONSE |
| TO THE SAID PROPERTY OR VICINITY THEREOF (INCLUDING |
| FIRE HYDRANTS AND FIRE LANES). |
| |
| 05.ALL PAVEMENT ROAD SYSTEMS SHALL BE CAPABLE OF |
| SUPPORTING 32 TONS FOR FIRE APPARATUS/EQUIPMENT. |
| |
| 06. FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN |
| UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND AN |
| UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13 |
| FEET 6 INCHES. |
| |
| 07.LANDSCAPING SHALL NOT OBSTRUCT OR INTERFERE WITH |
| FIRE PROTECTION EQUIPMENT.PROPER CLEARANCES SHALL BE |
| MAINTAINED AT ALL TIMES. |
| |
| 08.INDICATE THE LOCATION OF THE FIRE HYDRANT(S) IN |
| THE VICINITY OF THE SITE.BE ADVISED THAT IF THE |
| HYDRANT(S) IS GREATER THAN 500 FEET, AN ADDITIONAL |
| HYDRANT SHALL BE REQUIRED. |
| |
| 09.ON THE APPROPIATE EXTERIOR ELEVATION, SHOW/DISPLAY |
| THE NUMERICAL ADDRESS FOR THE BUILDINGS TO BE VISIBLE |
| FROM BROADWAY AVENUE.ONCE EMERGENCY RESPONDERS ARE |
| INSIDE OF THE COMPLEX, HOW ARE BUILDINGS DISTINGUISHED |
| FROM EACH OTHER. |
| |
| 10.IN ADDITION TO THE EXTERIOR ELEVATION DETAILS ON |
| SHEET A5.2 AND A5.2, SPECIFY ELEVATIONS AS NORTH, EAST, |
| WEST, AND SOUTH. |
| |
| 11.PLEASE INDICATE IF THIS BUILDING WILL BE EQUIPPED |
| WITH A FIRE ALARM SYSTEM.BE ADVISED THAT SMOKE |
| DETECTORS, AS LEGENDED ON SHEET E-1, ARE TIED INTO A |
| FIRE ALARM SYSTEM.SMOKE ALARMS ON THE OTHER HAND ARE |
| NOT TIED INTO A FIRE ALARM SYSTEM. |
| |
| 12.ON SHEET FS-6, PLEASE BE ADVISED THAT A 2 1/2" |
| SINGLE INLET FIRE DEPARTMENT CONNECTION W/CHECK VALVE |
| WILL BE REQUIRED. |
| |
| 13.ON SHEET FS-6, THE FIRE SPRINKLER SYSTEM IS TO BE |
| MONITORED.IT SHALL BE PROVIDED WITH AN APPROVED ALARM |
| INITIATION DEVICE THAT OPERATES WHEN THE FLOW OF WATER |
| IS EQUAL OR GREATER THAN THAT FROM A SINGLE AUTOMATIC |
| SPRINKLER. |
| |
| 14.IN REFERENCE TO THE HYDRAULIC CALCULATIONS THAT |
| WERE SUBMITTED:3RD FLOOR UNIT-A SYSTEM 4, 3RD FLOOR |
| UNIT-B SYSTEM 1, 3RD FLOOR UNIT-C SYSTEM 2, ALL SHOW AN |
| UNACCEPTABLE SAFETY MARGIN.AS PER WPBFR, A SAFETY |
| MARGIN OF AT LEAST 5.0 PSI IS REQUIRED. |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED |
| |
| |
| CAPT. MICHAEL A. WILLIAMS |
| FIRE PLAN REVIEW |