Plan Review Notes
Plan Review Notes For Permit 06120129
Permit Number 06120129
Review Stop E
Sequence Number 1
Notes
Date Text
2007-01-07 17:52:04** UNSAT **
  
 ** PLEASE SEE THESE ARE COMMENTS BASED ON THE PLANS
 SUBMITTED. PLEASE SEE THAT THERE MAY BE COMMENTS ON THE
 NEXT REVIEW WHICH MAY BE NEW AS SOME INFORMATION AS
 SHOWN ON THESE PLANS WILL BE CHANGING SYSTEMS.
  
 ** PLEASE SEE ANY REFERENCES IN PLAN REVIEW NOTES TO
 CHAPTER 1 OF THE FBC ARE THAT WHICH IS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE SEE PLANS ARE BEING SUBMITTED AND
 LABELED AS TOWNHOUSE UNITS, HOWEVER PLEASE SEE IF THESE
 ARE INDEED FEE SIMPLE "TOWNHOUSES" AS PER FBC
 DEFINITIONS, PLEASE SEE REQUIREMENTS OF THE FBC AND
 ELECTRICAL CODE WHICH WOULD CHANGE MANY ITEMS IN THE
 DESIGN AND PLEASE KNOW SEPARATE PERMIT APPLICATIONS,
 PLANS AND FEES WOULD BE REQUIRED ON EACH FEE SIMPLE
 TOWNHOUSE. PLEASE SEE AS ALL UNITS ARE CONNECTED BY A
 COMMON AREA AND ONE BUILDING THIS DOES NOT SEEM
 POSSIBLE.
 PLEASE KNOW THE PLANS AS SUBMITTED IS FOR ONE BUILDING
 AND PLEASE SEE COMMENTS FOR ELECTRICAL SERVICE(S) AS
 SUBMITTED.
 PLEASE CORRELATE SITE SURVEY PLANS WITH THAT OF THE
 SITE CIVIL PLANS. PLEASE SEE THERE ARE TWO COMPLETELY
 DIFFERENT LAYOUTS FOR THE PROPOSED BUILDING AND SITE.
 TH SITE SURVEY DIFFER FROM THE "A" SHEETS AND OTHER
 PLANS.
 PLEASE SEE COMMENTS FROM OTHER TRADES
 FBC ADMIN SECTION 106.1.2 FOR ADDITIONAL INFORMATION.
  
 2) NOTE: PLEASE SEE MISSING INFORMATION ON THE TITLE
 BLOCKS FOR THE LANDSCAPE SHEETS AS REQUIRED PER FLORIDA
 ADMINISTRATIVE CODE 61G1-16.004, AND FLORIDA STATUTES
 481.219.
 PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION NUMBER,
 PRINTED NAME, PRINTED LICENSE NUMBER ETC.
 PLEASE SEE 481.221 AS PLANS ARE REQUIRED TO BE SIGNED
 WITH LEGAL SIGNATURE AND DATED.
 THIS COMMENT IS REQUIRED WHETHER OR NOT COMMENT IS MADE
 BY ANY OTHER TRADE.
  
 3) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1AB.1 FOR
 MISSING ENERGY CALCULATIONS FOR "HOUSE" CONNECTED
 POWER.
 PLEASE ALSO SEE 13-415.2 FOR PERFORMANCE CALCULATIONS
 FOR "HOUSE".
 PLEASE SEE ANY "HOUSE" ROOMS WITH LIGHTING WILL REQUIRE
 AUTOMATIC SHUT OFF OF LIGHTING PER 13-415.1.ABC.1.1,
 .1.2, AND .1.3.
  
 4) NOTE: PLEASE SE POSSIBLE BUILDING REVIEW COMMENTS IF
 THIS BUILDING IS CONSIDERED A THRESHOLD BUILDING OR
 THAT WHICH WILL REQUIRE A SPECIAL INSPECTOR. PLEASE SEE
 FS 553.71(7), FBC ADMIN SECTION 109.3.6 PLEASE KNOW IF
 THIS BUILDING IS EITHER ONE, THREE SETS OF PLANS WILL
 BE REQUIRED FOR PROJECT.
  
 5) NOTE: PLEASE SEE FBC ADMIN SECTION 109.3.6,
 109.3.6.4.4 WHICH REQUIRES THE STATEMENT FOR THRESHOLD
 PROJECTS ON ALL ARCH AND ENG SHEETS.
 " TO THE BEST OF THE ARCHITECT'S /OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER
 633 OF THE FLORIDA STATUTES".
 THIS IS REQUIRED FOR EACH DESIGN PROFESSIONAL ON
 PLANS.
  
 6) NOTE: PLEASE CLARIFY THE TYPE FIRE PROTECTION BEING
 INSTALLED FOR BUILDING. PLEASE SEE ARCHITECTURAL SHEETS
 REFERENCE A 13R , HOWEVER PLEASE SEE NFPA-72 11-5.1.1,
 11.8.3. PLEASE SEE NFPA-72 DEFINITIONS AS PLANS CALL
 FOR SD FOR SMOKE DETECTORS THIS IS OK, HOWEVER PLEASE
 KNOW IF THESE ARE INDEED SMOKE DETECTORS AS DEFINED IN
 NFPA72, THESE WOULD BE DEVICES WHICH ONLY DETECT AND
 WOULD SIGNAL TO OTHER ALARM/HORN DEVICES. NO ALARM HORN
 DEVICES ARE SHOWN. PLEASE INDICATE IF PART OF A FUTURE
 LV FA SYSTEM.
 PLEASE KNOW AS PER SECTIONS GIVEN IF THESE ARE INDEED
 DEVICES WHICH DETECT AND ALSO SOUND AN ALARM, THEN THEY
 WOULD BE LABELED AS SA FOR SMOKE ALARMS.
 PLEASE KNOW AS OF OCT 06 IT CAME TO OUR ATTENTION AT
 THE SOUTHERN SECTION MEETING FROM NFPA THAT IF UNITS
 ARE INDEED DEVICES WHICH DETECT AND SOUND AN ALARM,
 PLANS SHOULD SHOW THEM AS SA'S AND THIS IS NOT NEW
 CODE. THIS HAS BEEN AN ACCEPTED METHOD IN THE PAST TO
 SHOW SD FOR BOTH HOWEVER ALL PLANS SINCE OCT 06 SHOULD
 BE CHANGING IF AND WHERE APPLICABLE.
 IF PART OF A LV FIRE/SECURITY SYSTEM PLEASE INDICATE AS
 SUCH. PLEASE SHOW DEVICES THEN FOR SOUNDING. PLEASE
 ALSO SEE MISSING SMOKE DETECTION/ SMOKE ALARM DEVICE IN
 UNIT "C" FIRST FLOOR.
  
 7) NOTE: PLEASE SEE FBC 2004 13-103.1.1.1 WHICH
 REQUIRES THE TYPE OF RECESSED LIGHTS TO BE INSTALLED.
 PLEASE NOTE ON PLANS ACCORDINGLY AND INDICATE
 FIXTURES.
  
 13) NOTE: PLEASE SEE FBC 2004 11-4.28.2, .3(4). PLEASE
 STATE ALL MINIMUM LEVELS AS REQUIRED FOR ALL AREAS
 WHICH MAY CONTAIN ANY FIRE HORN/STROBE DEVICES. AS IT
 IS NOT KNOWN AT THIS TIME OF ANY FIRE ALARM PANEL WILL
 BE REQUIRED FOR THE GARAGE OR BUILDING, PLEASE BE AWARE
 OF THE SECTIONS GIVEN IN ORDER TO INDICATE THE LEVELS
 AS REQUIRED IF A FA SYSTEM IS INSTALLED. 11-4.28.1
 PLEASE BE SURE TO SEE SECTIONS GIVEN FOR STROBE AND
 HORN DEVICES FROM THE FBC AND PLEASE ALSO SEE NFPA-72.
 PLEASE KNOW THAT THE FBC CHAPTER 11 REQUIREMENTS ARE
 MORE STRINGENT AND THE MORE STRINGENT SHALL APPLY.
  
 8) NOTE: PLEASE BE SURE PLANS REFLECT THE CODES IN
 WHICH THE DESIGN IS UNDER AND PERMITTED UNDER. PLEASE
 LIST THE FOLLOWING AT A MINIMUM FOR ELECTRICAL SHEETS
 AND ARCHITECTURAL SHEETS.
 2002 NFPA-70 (NEC), 2002-NFPA-72 NATIONAL FIRE ALARM
 CODE AND 2003 NFPA-101 LIFE SAFETY CODE.
 ** PLEASE KNOW FOR INFORMATIONAL PURPOSE, AS OF
 DECEMBER 8TH, 2006 THE STATE OF FLORIDA ADOPTED THE
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70(
 NEC). AS THIS PROJECT WAS SUBMITTED FOR PERMIT BEFORE
 THIS DATE, THIS PROJECT IS UNDER THE PREVIOUS CODES AS
 STATED ABOVE. (NOTED FOR INFORMATION ONLY)
  
 9) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL
 EGRESS PATHS UNDER NORMAL LIGHTING LEVELS AND UNDER
 EMERGENCY LIGHTING LEVELS TO THE PUBLIC RIGHT OF WAY
 OUT AND AWAY FROM BUILDING.
 PLEASE SEE NFPA-101 7.8 AND 7.9 AS BATTERY BACK UP
 LIGHTS OF SOME KIND WILL BE REQUIRED FOR EGRESS OUT OF
 THE GARAGE AREA.
 PLEASE SEE 700.12E FOR CIRCUITING .
 FBC 106.1.2 ADMIN SECTION.
 REVIEW FOR COMPLIANCE OF THIS CAN NOT BE DONE AT THIS
 TIME.
  
 10) NOTE: PLEASE PROVIDE MORE INFORMATION FOR FAIL SAFE
 OPERATION OF THE ELECTRICAL GATES AS SHOWN ON PLANS.
 PLANS NOTE IN MANY LOCATIONS THAT THE GATES SHALL
 AUTOMATICALLY OPEN IN THE EVENT OF POWER FAILURE;
 HOWEVER THERE ARE TWO SCENARIOS WHICH NEED TO BE
 ADDRESSED.
 A) PLEASE INDICATE HOW GATES WILL OPEN UNDER POWER
 FAILURE. (BATTERY BACK UP? ETC)
 B) PLEASE KNOW THAT IN AN EMERGENCY AND POWER IS STILL
 ON, THE OCCUPANTS SHALL BE ABLE TO EGRESS FROM THIS
 AREA OF THE STRUCTURE WITHOUT ANY IMPEDANCE FROM
 DEVICES WHICH MAY FAIL OR DELAY EGRESS IN ANY FASHION.
 PLEASE SEE NFPA-101 7.2, MORE SPECIFICALLY: 7.2.1.5.1
 DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE
 EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
  
 7.2.1.5.2 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
 THERE ARE NUMEROUS OTHER CODE SECTIONS, HOWEVER ONLY
 NOTED A COUPLE.
 PLEASE SEE REVIEW NOTES FROM THE FIRE MARSHAL AND
 BUILDING REVIEWER WHICH MAY ALSO ADDRESS THIS COMMENT.
 PLEASE KNOW THAT MORE INFORMATION IS REQUIRED FOR THIS
 WHETHER OR NOT COMMENT IS MADE SPECIFICALLY BY OTHER
 TRADES.
 THIS WILL AFFECT THE ELECTRICAL PLANS AND ALONG WITH
 NOTES ON POSSIBLE "A" SHEETS.
  
 11) NOTE: PLEASE SEE THAT SENSE THIS GARAGE SEEMS TO BE
 CONSIDERED AN ENCLOSED GARAGE PLEASE SEE THAT THERE MAY
 BE OTHER ELECTRICAL DEVICES WHICH MAY BE REQUIRED FOR
 CO SENSORS ETC. TO BE SHOWN AS PART OF ANY LV
 SYSTEMS/DEVICES ETC.
 THIS IS ONLY NOTED.
  
 12) NOTE: PLEASE SEE AS THIS IS ONE BUILDING; PLEASE
 SEE 230.2 AS THE PROPOSED SERVICES ARE NOT GRANTED AS
 SHOWN ON PLANS. PLEASE REVISE SERVICE RISER DIAGRAM FOR
 GROUPING OF MAINS AND SERVICES.
 PLEASE SEE PLANS DO NOT CORRELATE WITH RISER AT THIS
 TIME; PLEASE SEE EACH UNIT SHOWS AN ELECTRICAL METER AT
 EACH UNIT WHICH IS NOT PERMITTED.
 PLEASE SEE OTHER COMMENTS WITH RESPECT TO LOAD
 CALCULATIONS.
 PLEASE REVISE RISER DIAGRAM.
  
 13) NOTE: PLEASE SEE 250.50, 250.104 ETC FOR MISSING
 ATTACHMENTS FOR THE FOOTER STEEL AND FIRE SPRINKLER
 LINES.
  
 14) NOTE: PLEASE SHOW ALL ROOMS AND AREA DESIGNATIONS
 ON PLANS. PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULES SUBMITTED. PLEASE
 SEE THERE ARE SOME ITEMS WHICH CAN NOT BE REVIEWED FOR
 CODE COMPLIANCE AT THIS TIME DUE TO THIS INFORMATION
 NOT SHOWN.
 NEC 408.4, 310.16, 240.4 ETC.
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTIONS.
  
 15) NOTE: PLEASE SUBMIT PANEL SCHEDULES SPECIFIC TO
 EACH UNIT. THESE CAN NOT BE TYPICAL FOR A, B AND D AS
 SUBMITTED AS SOME OF THESE UNITS DO NOT CONTAIN
 ELECTRICAL APPLIANCES AS NOTED ON PANEL SCHEDULE(S) AND
 SOME UNITS DO NOT CONTAIN THE SAME ELECTRICAL POWER
 REQUIREMENTS FOR THE FOLLOWING LISTED IN NOTES TO COME.
 PLEASE KNOW ALL CIRCUITING AND IDENTIFICATION ON PANELS
 NEEDS TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH THEY
 FEED.
 IE: LIVING RM LTS,BEDRM RECEPTS , DINING RM, ETC.
 408.4, 310.16,
 FBC 106.1.2, 106.3.5.1.2
  
 16) NOTE: PLEASE SEE MECHANICAL PLANS WHICH INDICATE
 LOADS FOR THE AHU WITH LESS OF A LOAD THAN THAT SHOWN
 ON THE PANEL SCHEDULES AND LOAD CALCULATIONS
 SUBMITTED.
 PLEASE CORRELATE ALL OVER CURRENT PROTECTION DEVICES
 WITH EACH. AS NOTED ABOVE IN NOTE #15, EACH PANEL SHALL
 BE SPECIFIC AS THE CU'S CONTAIN DIFFERENT OVER CURRENT
 PROTECTION FOR EACH UNIT. PLEASE ALSO SEE THE OVER
 PROTECTION FOR BOTH THE AHU'S AND THE CU'S SHALL
 CORRELATE WITH THE PANEL SCHEDULES.
 424.3B, 240.4, 310.16 ETC.
  
 17) NOTE: PLEASE SEE PANELS SCHEDULE FOR ALL UNITS
 INDICATE A WHIRLPOOL TUB, HOWEVER THE PLANS DO NOT SHOW
 THE SAME OR CONTAIN ELECTRICAL GFI'S AT THE TUB
 LOCATIONS?
 PLEASE CORRELATE EACH UNIT WITH PANEL SCHEDULE TO BE
 SUBMITTED FOR EACH UNIT.
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION.
 NEC 680.71
  
 18) NOTE: PLEASE SEE THE LOAD SHOWN ON THE PANEL
 SCHEDULE FOR THE GARAGE DOOR OPENER DOES NOT CORRELATE
 WITH THE LOAD CALCULATIONS. PLEASE CORRELATE. 408.4,
 220.31
  
 19) NOTE: PLEASE SEE BOTH THE DISHWASHER AND DISPOSAL
 ARE BEING FED TO THE SAME RECEPTACLE DEVICE/YOKE WHICH
 IS OK AND A TYPICAL INSTALLATION; HOWEVER PLEASE SEE
 210.4(A)&(B) AS THESE SHALL BE FED FROM THE SAME
 BREAKER WHICH WOULD BE A 2-POLE BREAKER. NO HANDLE TIES
 ARE PERMITTED. THE OTHER SCENARIO WOULD BE TO INSTALL
 TWO INDIVIDUAL SINGLE RECEPTACLES.
 PLEASE VERIFY THIS AS THE LOADS SHOWN FOR EACH UNIT
 SEEM TO EXCEED THAT OF A STANDARD 15A RATED DEVICE.
 MUST BE 20A RATED. PLEASE VERIFY 210.21(B)(2) AND
 (B)(3).
  
 20) NOTE: PLEASE LIST THE REQUIRED ARC FAULT PROTECTED
 CIRCUITS ON THE PANEL SCHEDULE. PLEASE KNOW THE NOTE ON
 PLANS IS NOT ENOUGH AT THIS TIME. PLEASE SEE THIS CAN
 BE DONE WITH AN * AT EACH CIRCUIT TO THIS NOTE ONCE ALL
 CIRCUITING IS PLACED ON PLANS. PLEASE BE SURE TO SEE
 NOTE PERTAINING TO SMOKE ALARM/DETECTORS DEVICES AND
 WHICH TYPE WILL BE INSTALLED. THIS WILL AFFECT THE
 CIRCUITING AND INDICATION OF THE REQUIRED AFCI
 PROTECTION.
 2002 NEC 210.12
  
 21) NOTE: PLEASE SEE PLANS CONTAIN A NOTE THAT STATE
 ALL EXTERIOR LIGHT FIXTURES SHALL BE RATED FOR "DAMP
 LOCATION"?? PLEASE KNOW THAT ANY FIXTURES OUTSIDE SHALL
 BE LISTED FOR "WET LOCATIONS".
 110.3, 90.4
  
 22) NOTE: PLEASE SEE MISSING THE REQUIRED GFI FOR SOME
 CONDENSING UNITS PER 210.63, 210.8A3 (UNIT "C").
  
 23) NOTE: PLEASE SEE SUBMIT COMPLETE LOAD CALCULATIONS
 FOR SERVICE. 220..3, 220.10, 220.11, 220.13 AND 220.32
 ETC
 PLEASE KNOW DEPENDING ON THE NEW SERVICE AND LOAD,
 CONSIDERATION OF 230.2 WILL BE REVIEWED, HOWEVER PLEASE
 KNOW AT THIS TIME THE FOUR SERVICES AS SHOWN WILL NOT
 BE GRANTED IN EITHER CASE AND ANY SERVICES GRANTED FOR
 THIS SINGLE BUILDING WILL STILL REQUIRE MAINS TO BE
 GROUPED AS PREVIOUSLY NOTED ABOVE.
  
 24) NOTE: PLEASE SEE 210.52D FOR UNIT "A" MASTER BATH
 WHICH WILL REQUIRE THE ADDITION OF ONE ADDITIONAL GFI
 RECEPT OR MOVE THE ONE SHOWN BETWEEN THE TWO LAVATORIES
 AS SHOWN. PLEASE KNOW THE CROSSING OVER A SINK/LAVATORY
 IS NOT PERMITTED IN ORDER TO PLUG IN ANY APPLIANCE FOR
 USE.
  
 25) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.16 OR
 DINING ROOMS AND AREAS OF THE LIKE. AS NOTED ABOVE,
 REVIEW FOR CIRCUITING OF THIS AREA CAN NOT BE DONE AT
 THIS TIME.
  
 26) NOTE: PLEASE INDICATE ALL DEVICE HEIGHTS. PLEASE
 SEE IF THIS IS GOING TO BE A MULTI-FAMILY BUILDING AS
 SHOWN, PLEASE SEE FHAR 24CFR100.205 FOR FIRST FLOOR AT
 A MINIMUM. PLEASE KNOW IF ANY VERTICAL ACCESSIBILITY IS
 INSTALLED, THEN THESE DEVICE HEIGHTS AND LOCATIONS
 SHALL BE FOR ALL FLOORS OR FLOORS THAT THE VERTICAL
 ACCESS IS PROVIDED.
 (15INCHES MIN FOR RECEPTS, 48INCHES MAX FOR SWITCHES,
 ETC).
  
 27) NOTE: PLEASE SEE 210.52 FOR AREAS FOR REQUIRED
 RECEPTS WHICH ARE MISSING ON PLANS. PLEASE SEE UNIT "C"
 ETC.
 PLEASE ALSO SEE OTHER AREAS PER 210.52H FOR HALLWAYS
 WHICH MAY HAVE A WALL SPACE 10FT OR MORE.
 ** PLEASE KNOW ANY ROOMS WHICH CONTAIN RAILINGS MAY BE
 REQUIRED TO CONTAIN RECEPTACLES ALONG THESE RAILINGS AS
 RAILS ARE CONSIDERED WALL SPACE.
 PLEASE SEE ONE SET OF PLANS ARE REDLINED FOR LOCATIONS
 WHICH ARE MISSING DEVICES WITHIN 6FT OF DOOR, 2FT OR
 MORE OF WALL SPACE AND HALLWAYS AS NOTED.
  
 28) NOTE: PLEASE SEE SOME DEVICES WHICH APPEAR TO BE
 3-WAY; DO NOT CONTAIN THE SWITCH WITH THE 3-WAY
 DESIGNATION. PLEASE VERIFY ALL. (UNIT "C").
  
 29) NOTE: SEE SOME UNITS SHOW WHAT APPEARS TO BE A
 STACK WASHER DRYER, HOWEVER NOTATION FOR SUCH ON PLANS
 AND PANEL SCHEDULES COULD NOT BE FOUND.
 PLEASE LIST. 408.4.
 FBC 106.1.2
  
 30) NOTE: PLEASE CORRELATE THE LOADS FOR THE RANGE.
 PANEL SCHEDULE SHOWS 10KW AND THE LOAD CALCULATIONS
 INDICATE 10KW?
 310.16, 408.4, 240.4, 220.19
  
 31) NOTE: PLEASE SEE LIGHT AND RECEPT ON THE "C" UNITS
 2ND FLOOR WHICH SEEMS TO BE LOCATED TOO FAR OVER AND
 PAST THE RAIL AREA OR NEXT BUILDING LOCATION.
 IF THE GFI IS THAT FOR THE CU AS NOTED IN NOTE #22
 ABOVE, DISREGARD NOTE #22 AND RELOCATE.
  
 32) NOTE: PLEASE COMPLETE RISER DIAGRAM WITH ALL
 FEEDERS TO UNITS AND CORRELATE WITH THE OVER CURRENT
 PROTECTION DEVICES OF THAT FOR EACH UNIT.
 215.5, 310.16, 240.4 ETC.
 FBC 106.1.2, 106.3.5.1.2
  
 33) NOTE: PLEASE INDICATE THE EQUIPMENT GROUNDING
 CONDUCTORS FROM MAINS TO EACH UNIT PER 250.122.
 250.24B, 250.110, ETC.
  
 34) NOTE: PLEASE SEE THAT THE ADDRESS FOR THIS PROJECT
 SHALL BE PLACED ON THE TITLE BLOCKS. PLEASE KNOW AT
 THIS TIME, THIS IS A MULTI-FAMILY SINGLE BUILDING WITH
 THE ADDRESS OF 2900 BROADWAY.
 THIS IS NOT AND HAS NOT BEEN SUBMITTED AS TOWNHOUSES,
 OR CONDO'S.
 FAC 61G15-23.002, FAC 61G1-16.004
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]