Text |
2007-01-07 17:52:04 | ** UNSAT ** |
| |
| ** PLEASE SEE THESE ARE COMMENTS BASED ON THE PLANS |
| SUBMITTED. PLEASE SEE THAT THERE MAY BE COMMENTS ON THE |
| NEXT REVIEW WHICH MAY BE NEW AS SOME INFORMATION AS |
| SHOWN ON THESE PLANS WILL BE CHANGING SYSTEMS. |
| |
| ** PLEASE SEE ANY REFERENCES IN PLAN REVIEW NOTES TO |
| CHAPTER 1 OF THE FBC ARE THAT WHICH IS ADOPTED BY THE |
| CITY OF WEST PALM BEACH. |
| |
| 1) NOTE: PLEASE SEE PLANS ARE BEING SUBMITTED AND |
| LABELED AS TOWNHOUSE UNITS, HOWEVER PLEASE SEE IF THESE |
| ARE INDEED FEE SIMPLE "TOWNHOUSES" AS PER FBC |
| DEFINITIONS, PLEASE SEE REQUIREMENTS OF THE FBC AND |
| ELECTRICAL CODE WHICH WOULD CHANGE MANY ITEMS IN THE |
| DESIGN AND PLEASE KNOW SEPARATE PERMIT APPLICATIONS, |
| PLANS AND FEES WOULD BE REQUIRED ON EACH FEE SIMPLE |
| TOWNHOUSE. PLEASE SEE AS ALL UNITS ARE CONNECTED BY A |
| COMMON AREA AND ONE BUILDING THIS DOES NOT SEEM |
| POSSIBLE. |
| PLEASE KNOW THE PLANS AS SUBMITTED IS FOR ONE BUILDING |
| AND PLEASE SEE COMMENTS FOR ELECTRICAL SERVICE(S) AS |
| SUBMITTED. |
| PLEASE CORRELATE SITE SURVEY PLANS WITH THAT OF THE |
| SITE CIVIL PLANS. PLEASE SEE THERE ARE TWO COMPLETELY |
| DIFFERENT LAYOUTS FOR THE PROPOSED BUILDING AND SITE. |
| TH SITE SURVEY DIFFER FROM THE "A" SHEETS AND OTHER |
| PLANS. |
| PLEASE SEE COMMENTS FROM OTHER TRADES |
| FBC ADMIN SECTION 106.1.2 FOR ADDITIONAL INFORMATION. |
| |
| 2) NOTE: PLEASE SEE MISSING INFORMATION ON THE TITLE |
| BLOCKS FOR THE LANDSCAPE SHEETS AS REQUIRED PER FLORIDA |
| ADMINISTRATIVE CODE 61G1-16.004, AND FLORIDA STATUTES |
| 481.219. |
| PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION NUMBER, |
| PRINTED NAME, PRINTED LICENSE NUMBER ETC. |
| PLEASE SEE 481.221 AS PLANS ARE REQUIRED TO BE SIGNED |
| WITH LEGAL SIGNATURE AND DATED. |
| THIS COMMENT IS REQUIRED WHETHER OR NOT COMMENT IS MADE |
| BY ANY OTHER TRADE. |
| |
| 3) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1AB.1 FOR |
| MISSING ENERGY CALCULATIONS FOR "HOUSE" CONNECTED |
| POWER. |
| PLEASE ALSO SEE 13-415.2 FOR PERFORMANCE CALCULATIONS |
| FOR "HOUSE". |
| PLEASE SEE ANY "HOUSE" ROOMS WITH LIGHTING WILL REQUIRE |
| AUTOMATIC SHUT OFF OF LIGHTING PER 13-415.1.ABC.1.1, |
| .1.2, AND .1.3. |
| |
| 4) NOTE: PLEASE SE POSSIBLE BUILDING REVIEW COMMENTS IF |
| THIS BUILDING IS CONSIDERED A THRESHOLD BUILDING OR |
| THAT WHICH WILL REQUIRE A SPECIAL INSPECTOR. PLEASE SEE |
| FS 553.71(7), FBC ADMIN SECTION 109.3.6 PLEASE KNOW IF |
| THIS BUILDING IS EITHER ONE, THREE SETS OF PLANS WILL |
| BE REQUIRED FOR PROJECT. |
| |
| 5) NOTE: PLEASE SEE FBC ADMIN SECTION 109.3.6, |
| 109.3.6.4.4 WHICH REQUIRES THE STATEMENT FOR THRESHOLD |
| PROJECTS ON ALL ARCH AND ENG SHEETS. |
| " TO THE BEST OF THE ARCHITECT'S /OR ENGINEER'S |
| KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE |
| FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER |
| 633 OF THE FLORIDA STATUTES". |
| THIS IS REQUIRED FOR EACH DESIGN PROFESSIONAL ON |
| PLANS. |
| |
| 6) NOTE: PLEASE CLARIFY THE TYPE FIRE PROTECTION BEING |
| INSTALLED FOR BUILDING. PLEASE SEE ARCHITECTURAL SHEETS |
| REFERENCE A 13R , HOWEVER PLEASE SEE NFPA-72 11-5.1.1, |
| 11.8.3. PLEASE SEE NFPA-72 DEFINITIONS AS PLANS CALL |
| FOR SD FOR SMOKE DETECTORS THIS IS OK, HOWEVER PLEASE |
| KNOW IF THESE ARE INDEED SMOKE DETECTORS AS DEFINED IN |
| NFPA72, THESE WOULD BE DEVICES WHICH ONLY DETECT AND |
| WOULD SIGNAL TO OTHER ALARM/HORN DEVICES. NO ALARM HORN |
| DEVICES ARE SHOWN. PLEASE INDICATE IF PART OF A FUTURE |
| LV FA SYSTEM. |
| PLEASE KNOW AS PER SECTIONS GIVEN IF THESE ARE INDEED |
| DEVICES WHICH DETECT AND ALSO SOUND AN ALARM, THEN THEY |
| WOULD BE LABELED AS SA FOR SMOKE ALARMS. |
| PLEASE KNOW AS OF OCT 06 IT CAME TO OUR ATTENTION AT |
| THE SOUTHERN SECTION MEETING FROM NFPA THAT IF UNITS |
| ARE INDEED DEVICES WHICH DETECT AND SOUND AN ALARM, |
| PLANS SHOULD SHOW THEM AS SA'S AND THIS IS NOT NEW |
| CODE. THIS HAS BEEN AN ACCEPTED METHOD IN THE PAST TO |
| SHOW SD FOR BOTH HOWEVER ALL PLANS SINCE OCT 06 SHOULD |
| BE CHANGING IF AND WHERE APPLICABLE. |
| IF PART OF A LV FIRE/SECURITY SYSTEM PLEASE INDICATE AS |
| SUCH. PLEASE SHOW DEVICES THEN FOR SOUNDING. PLEASE |
| ALSO SEE MISSING SMOKE DETECTION/ SMOKE ALARM DEVICE IN |
| UNIT "C" FIRST FLOOR. |
| |
| 7) NOTE: PLEASE SEE FBC 2004 13-103.1.1.1 WHICH |
| REQUIRES THE TYPE OF RECESSED LIGHTS TO BE INSTALLED. |
| PLEASE NOTE ON PLANS ACCORDINGLY AND INDICATE |
| FIXTURES. |
| |
| 13) NOTE: PLEASE SEE FBC 2004 11-4.28.2, .3(4). PLEASE |
| STATE ALL MINIMUM LEVELS AS REQUIRED FOR ALL AREAS |
| WHICH MAY CONTAIN ANY FIRE HORN/STROBE DEVICES. AS IT |
| IS NOT KNOWN AT THIS TIME OF ANY FIRE ALARM PANEL WILL |
| BE REQUIRED FOR THE GARAGE OR BUILDING, PLEASE BE AWARE |
| OF THE SECTIONS GIVEN IN ORDER TO INDICATE THE LEVELS |
| AS REQUIRED IF A FA SYSTEM IS INSTALLED. 11-4.28.1 |
| PLEASE BE SURE TO SEE SECTIONS GIVEN FOR STROBE AND |
| HORN DEVICES FROM THE FBC AND PLEASE ALSO SEE NFPA-72. |
| PLEASE KNOW THAT THE FBC CHAPTER 11 REQUIREMENTS ARE |
| MORE STRINGENT AND THE MORE STRINGENT SHALL APPLY. |
| |
| 8) NOTE: PLEASE BE SURE PLANS REFLECT THE CODES IN |
| WHICH THE DESIGN IS UNDER AND PERMITTED UNDER. PLEASE |
| LIST THE FOLLOWING AT A MINIMUM FOR ELECTRICAL SHEETS |
| AND ARCHITECTURAL SHEETS. |
| 2002 NFPA-70 (NEC), 2002-NFPA-72 NATIONAL FIRE ALARM |
| CODE AND 2003 NFPA-101 LIFE SAFETY CODE. |
| ** PLEASE KNOW FOR INFORMATIONAL PURPOSE, AS OF |
| DECEMBER 8TH, 2006 THE STATE OF FLORIDA ADOPTED THE |
| 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70( |
| NEC). AS THIS PROJECT WAS SUBMITTED FOR PERMIT BEFORE |
| THIS DATE, THIS PROJECT IS UNDER THE PREVIOUS CODES AS |
| STATED ABOVE. (NOTED FOR INFORMATION ONLY) |
| |
| 9) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL |
| EGRESS PATHS UNDER NORMAL LIGHTING LEVELS AND UNDER |
| EMERGENCY LIGHTING LEVELS TO THE PUBLIC RIGHT OF WAY |
| OUT AND AWAY FROM BUILDING. |
| PLEASE SEE NFPA-101 7.8 AND 7.9 AS BATTERY BACK UP |
| LIGHTS OF SOME KIND WILL BE REQUIRED FOR EGRESS OUT OF |
| THE GARAGE AREA. |
| PLEASE SEE 700.12E FOR CIRCUITING . |
| FBC 106.1.2 ADMIN SECTION. |
| REVIEW FOR COMPLIANCE OF THIS CAN NOT BE DONE AT THIS |
| TIME. |
| |
| 10) NOTE: PLEASE PROVIDE MORE INFORMATION FOR FAIL SAFE |
| OPERATION OF THE ELECTRICAL GATES AS SHOWN ON PLANS. |
| PLANS NOTE IN MANY LOCATIONS THAT THE GATES SHALL |
| AUTOMATICALLY OPEN IN THE EVENT OF POWER FAILURE; |
| HOWEVER THERE ARE TWO SCENARIOS WHICH NEED TO BE |
| ADDRESSED. |
| A) PLEASE INDICATE HOW GATES WILL OPEN UNDER POWER |
| FAILURE. (BATTERY BACK UP? ETC) |
| B) PLEASE KNOW THAT IN AN EMERGENCY AND POWER IS STILL |
| ON, THE OCCUPANTS SHALL BE ABLE TO EGRESS FROM THIS |
| AREA OF THE STRUCTURE WITHOUT ANY IMPEDANCE FROM |
| DEVICES WHICH MAY FAIL OR DELAY EGRESS IN ANY FASHION. |
| PLEASE SEE NFPA-101 7.2, MORE SPECIFICALLY: 7.2.1.5.1 |
| DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE |
| EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| |
| 7.2.1.5.2 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR |
| OPERATION FROM THE EGRESS SIDE. |
| THERE ARE NUMEROUS OTHER CODE SECTIONS, HOWEVER ONLY |
| NOTED A COUPLE. |
| PLEASE SEE REVIEW NOTES FROM THE FIRE MARSHAL AND |
| BUILDING REVIEWER WHICH MAY ALSO ADDRESS THIS COMMENT. |
| PLEASE KNOW THAT MORE INFORMATION IS REQUIRED FOR THIS |
| WHETHER OR NOT COMMENT IS MADE SPECIFICALLY BY OTHER |
| TRADES. |
| THIS WILL AFFECT THE ELECTRICAL PLANS AND ALONG WITH |
| NOTES ON POSSIBLE "A" SHEETS. |
| |
| 11) NOTE: PLEASE SEE THAT SENSE THIS GARAGE SEEMS TO BE |
| CONSIDERED AN ENCLOSED GARAGE PLEASE SEE THAT THERE MAY |
| BE OTHER ELECTRICAL DEVICES WHICH MAY BE REQUIRED FOR |
| CO SENSORS ETC. TO BE SHOWN AS PART OF ANY LV |
| SYSTEMS/DEVICES ETC. |
| THIS IS ONLY NOTED. |
| |
| 12) NOTE: PLEASE SEE AS THIS IS ONE BUILDING; PLEASE |
| SEE 230.2 AS THE PROPOSED SERVICES ARE NOT GRANTED AS |
| SHOWN ON PLANS. PLEASE REVISE SERVICE RISER DIAGRAM FOR |
| GROUPING OF MAINS AND SERVICES. |
| PLEASE SEE PLANS DO NOT CORRELATE WITH RISER AT THIS |
| TIME; PLEASE SEE EACH UNIT SHOWS AN ELECTRICAL METER AT |
| EACH UNIT WHICH IS NOT PERMITTED. |
| PLEASE SEE OTHER COMMENTS WITH RESPECT TO LOAD |
| CALCULATIONS. |
| PLEASE REVISE RISER DIAGRAM. |
| |
| 13) NOTE: PLEASE SEE 250.50, 250.104 ETC FOR MISSING |
| ATTACHMENTS FOR THE FOOTER STEEL AND FIRE SPRINKLER |
| LINES. |
| |
| 14) NOTE: PLEASE SHOW ALL ROOMS AND AREA DESIGNATIONS |
| ON PLANS. PLEASE COMPLETE ALL CIRCUITING ON PLANS AND |
| CORRELATE WITH THE PANEL SCHEDULES SUBMITTED. PLEASE |
| SEE THERE ARE SOME ITEMS WHICH CAN NOT BE REVIEWED FOR |
| CODE COMPLIANCE AT THIS TIME DUE TO THIS INFORMATION |
| NOT SHOWN. |
| NEC 408.4, 310.16, 240.4 ETC. |
| FBC 106.1.2, 106.3.5.1.2 ADMIN SECTIONS. |
| |
| 15) NOTE: PLEASE SUBMIT PANEL SCHEDULES SPECIFIC TO |
| EACH UNIT. THESE CAN NOT BE TYPICAL FOR A, B AND D AS |
| SUBMITTED AS SOME OF THESE UNITS DO NOT CONTAIN |
| ELECTRICAL APPLIANCES AS NOTED ON PANEL SCHEDULE(S) AND |
| SOME UNITS DO NOT CONTAIN THE SAME ELECTRICAL POWER |
| REQUIREMENTS FOR THE FOLLOWING LISTED IN NOTES TO COME. |
| PLEASE KNOW ALL CIRCUITING AND IDENTIFICATION ON PANELS |
| NEEDS TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH THEY |
| FEED. |
| IE: LIVING RM LTS,BEDRM RECEPTS , DINING RM, ETC. |
| 408.4, 310.16, |
| FBC 106.1.2, 106.3.5.1.2 |
| |
| 16) NOTE: PLEASE SEE MECHANICAL PLANS WHICH INDICATE |
| LOADS FOR THE AHU WITH LESS OF A LOAD THAN THAT SHOWN |
| ON THE PANEL SCHEDULES AND LOAD CALCULATIONS |
| SUBMITTED. |
| PLEASE CORRELATE ALL OVER CURRENT PROTECTION DEVICES |
| WITH EACH. AS NOTED ABOVE IN NOTE #15, EACH PANEL SHALL |
| BE SPECIFIC AS THE CU'S CONTAIN DIFFERENT OVER CURRENT |
| PROTECTION FOR EACH UNIT. PLEASE ALSO SEE THE OVER |
| PROTECTION FOR BOTH THE AHU'S AND THE CU'S SHALL |
| CORRELATE WITH THE PANEL SCHEDULES. |
| 424.3B, 240.4, 310.16 ETC. |
| |
| 17) NOTE: PLEASE SEE PANELS SCHEDULE FOR ALL UNITS |
| INDICATE A WHIRLPOOL TUB, HOWEVER THE PLANS DO NOT SHOW |
| THE SAME OR CONTAIN ELECTRICAL GFI'S AT THE TUB |
| LOCATIONS? |
| PLEASE CORRELATE EACH UNIT WITH PANEL SCHEDULE TO BE |
| SUBMITTED FOR EACH UNIT. |
| FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION. |
| NEC 680.71 |
| |
| 18) NOTE: PLEASE SEE THE LOAD SHOWN ON THE PANEL |
| SCHEDULE FOR THE GARAGE DOOR OPENER DOES NOT CORRELATE |
| WITH THE LOAD CALCULATIONS. PLEASE CORRELATE. 408.4, |
| 220.31 |
| |
| 19) NOTE: PLEASE SEE BOTH THE DISHWASHER AND DISPOSAL |
| ARE BEING FED TO THE SAME RECEPTACLE DEVICE/YOKE WHICH |
| IS OK AND A TYPICAL INSTALLATION; HOWEVER PLEASE SEE |
| 210.4(A)&(B) AS THESE SHALL BE FED FROM THE SAME |
| BREAKER WHICH WOULD BE A 2-POLE BREAKER. NO HANDLE TIES |
| ARE PERMITTED. THE OTHER SCENARIO WOULD BE TO INSTALL |
| TWO INDIVIDUAL SINGLE RECEPTACLES. |
| PLEASE VERIFY THIS AS THE LOADS SHOWN FOR EACH UNIT |
| SEEM TO EXCEED THAT OF A STANDARD 15A RATED DEVICE. |
| MUST BE 20A RATED. PLEASE VERIFY 210.21(B)(2) AND |
| (B)(3). |
| |
| 20) NOTE: PLEASE LIST THE REQUIRED ARC FAULT PROTECTED |
| CIRCUITS ON THE PANEL SCHEDULE. PLEASE KNOW THE NOTE ON |
| PLANS IS NOT ENOUGH AT THIS TIME. PLEASE SEE THIS CAN |
| BE DONE WITH AN * AT EACH CIRCUIT TO THIS NOTE ONCE ALL |
| CIRCUITING IS PLACED ON PLANS. PLEASE BE SURE TO SEE |
| NOTE PERTAINING TO SMOKE ALARM/DETECTORS DEVICES AND |
| WHICH TYPE WILL BE INSTALLED. THIS WILL AFFECT THE |
| CIRCUITING AND INDICATION OF THE REQUIRED AFCI |
| PROTECTION. |
| 2002 NEC 210.12 |
| |
| 21) NOTE: PLEASE SEE PLANS CONTAIN A NOTE THAT STATE |
| ALL EXTERIOR LIGHT FIXTURES SHALL BE RATED FOR "DAMP |
| LOCATION"?? PLEASE KNOW THAT ANY FIXTURES OUTSIDE SHALL |
| BE LISTED FOR "WET LOCATIONS". |
| 110.3, 90.4 |
| |
| 22) NOTE: PLEASE SEE MISSING THE REQUIRED GFI FOR SOME |
| CONDENSING UNITS PER 210.63, 210.8A3 (UNIT "C"). |
| |
| 23) NOTE: PLEASE SEE SUBMIT COMPLETE LOAD CALCULATIONS |
| FOR SERVICE. 220..3, 220.10, 220.11, 220.13 AND 220.32 |
| ETC |
| PLEASE KNOW DEPENDING ON THE NEW SERVICE AND LOAD, |
| CONSIDERATION OF 230.2 WILL BE REVIEWED, HOWEVER PLEASE |
| KNOW AT THIS TIME THE FOUR SERVICES AS SHOWN WILL NOT |
| BE GRANTED IN EITHER CASE AND ANY SERVICES GRANTED FOR |
| THIS SINGLE BUILDING WILL STILL REQUIRE MAINS TO BE |
| GROUPED AS PREVIOUSLY NOTED ABOVE. |
| |
| 24) NOTE: PLEASE SEE 210.52D FOR UNIT "A" MASTER BATH |
| WHICH WILL REQUIRE THE ADDITION OF ONE ADDITIONAL GFI |
| RECEPT OR MOVE THE ONE SHOWN BETWEEN THE TWO LAVATORIES |
| AS SHOWN. PLEASE KNOW THE CROSSING OVER A SINK/LAVATORY |
| IS NOT PERMITTED IN ORDER TO PLUG IN ANY APPLIANCE FOR |
| USE. |
| |
| 25) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.16 OR |
| DINING ROOMS AND AREAS OF THE LIKE. AS NOTED ABOVE, |
| REVIEW FOR CIRCUITING OF THIS AREA CAN NOT BE DONE AT |
| THIS TIME. |
| |
| 26) NOTE: PLEASE INDICATE ALL DEVICE HEIGHTS. PLEASE |
| SEE IF THIS IS GOING TO BE A MULTI-FAMILY BUILDING AS |
| SHOWN, PLEASE SEE FHAR 24CFR100.205 FOR FIRST FLOOR AT |
| A MINIMUM. PLEASE KNOW IF ANY VERTICAL ACCESSIBILITY IS |
| INSTALLED, THEN THESE DEVICE HEIGHTS AND LOCATIONS |
| SHALL BE FOR ALL FLOORS OR FLOORS THAT THE VERTICAL |
| ACCESS IS PROVIDED. |
| (15INCHES MIN FOR RECEPTS, 48INCHES MAX FOR SWITCHES, |
| ETC). |
| |
| 27) NOTE: PLEASE SEE 210.52 FOR AREAS FOR REQUIRED |
| RECEPTS WHICH ARE MISSING ON PLANS. PLEASE SEE UNIT "C" |
| ETC. |
| PLEASE ALSO SEE OTHER AREAS PER 210.52H FOR HALLWAYS |
| WHICH MAY HAVE A WALL SPACE 10FT OR MORE. |
| ** PLEASE KNOW ANY ROOMS WHICH CONTAIN RAILINGS MAY BE |
| REQUIRED TO CONTAIN RECEPTACLES ALONG THESE RAILINGS AS |
| RAILS ARE CONSIDERED WALL SPACE. |
| PLEASE SEE ONE SET OF PLANS ARE REDLINED FOR LOCATIONS |
| WHICH ARE MISSING DEVICES WITHIN 6FT OF DOOR, 2FT OR |
| MORE OF WALL SPACE AND HALLWAYS AS NOTED. |
| |
| 28) NOTE: PLEASE SEE SOME DEVICES WHICH APPEAR TO BE |
| 3-WAY; DO NOT CONTAIN THE SWITCH WITH THE 3-WAY |
| DESIGNATION. PLEASE VERIFY ALL. (UNIT "C"). |
| |
| 29) NOTE: SEE SOME UNITS SHOW WHAT APPEARS TO BE A |
| STACK WASHER DRYER, HOWEVER NOTATION FOR SUCH ON PLANS |
| AND PANEL SCHEDULES COULD NOT BE FOUND. |
| PLEASE LIST. 408.4. |
| FBC 106.1.2 |
| |
| 30) NOTE: PLEASE CORRELATE THE LOADS FOR THE RANGE. |
| PANEL SCHEDULE SHOWS 10KW AND THE LOAD CALCULATIONS |
| INDICATE 10KW? |
| 310.16, 408.4, 240.4, 220.19 |
| |
| 31) NOTE: PLEASE SEE LIGHT AND RECEPT ON THE "C" UNITS |
| 2ND FLOOR WHICH SEEMS TO BE LOCATED TOO FAR OVER AND |
| PAST THE RAIL AREA OR NEXT BUILDING LOCATION. |
| IF THE GFI IS THAT FOR THE CU AS NOTED IN NOTE #22 |
| ABOVE, DISREGARD NOTE #22 AND RELOCATE. |
| |
| 32) NOTE: PLEASE COMPLETE RISER DIAGRAM WITH ALL |
| FEEDERS TO UNITS AND CORRELATE WITH THE OVER CURRENT |
| PROTECTION DEVICES OF THAT FOR EACH UNIT. |
| 215.5, 310.16, 240.4 ETC. |
| FBC 106.1.2, 106.3.5.1.2 |
| |
| 33) NOTE: PLEASE INDICATE THE EQUIPMENT GROUNDING |
| CONDUCTORS FROM MAINS TO EACH UNIT PER 250.122. |
| 250.24B, 250.110, ETC. |
| |
| 34) NOTE: PLEASE SEE THAT THE ADDRESS FOR THIS PROJECT |
| SHALL BE PLACED ON THE TITLE BLOCKS. PLEASE KNOW AT |
| THIS TIME, THIS IS A MULTI-FAMILY SINGLE BUILDING WITH |
| THE ADDRESS OF 2900 BROADWAY. |
| THIS IS NOT AND HAS NOT BEEN SUBMITTED AS TOWNHOUSES, |
| OR CONDO'S. |
| FAC 61G15-23.002, FAC 61G1-16.004 |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
2007-01-07 14:00:56 | IN ELEC FOR REVIEW. |