2007-01-22 15:58:50 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE |
| FBC2004 |
| |
| 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO |
| PERMIT PICKUP, FS713.13. |
| |
| 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY |
| PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.THE PLANS |
| MUST BE STAMPED AND THE RECEIPT ATTACHED TO THE |
| APPLICATION.PLEASE CALL 561-233-5025 FOR MORE |
| INFORMATION. |
| |
| 3.)RADON FEES HAVE BEEN ADDED FS553.721.THIS MAY BE |
| ADJUSTED AFTER EXACT BUILDING SIZE IS DETERMINED. |
| |
| 4.) FBC* 109.3.7RESIDENT INSPECTOR. SUBMIT INSPECTOR |
| RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA, |
| DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT |
| INSPECTOR PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO |
| ONE OR MORE OF THE FOLLOWING: |
| - BUILDINGS/ADDITIONS OF TYPE I OR II |
| CONSTRUCTION |
| - ANY MAJOR STRUCTURAL ALTERATIONS |
| - STRUCTURES IN WHICH THE CONCRETE |
| DESIGN IS BASED ON COMPRESSIVE |
| STRENGTH (F'C) IN EXCESS OF 3000 PSI |
| - PILE DRIVING |
| - BUILDINGS OVER 20,000 SQFT IN AREA |
| - BUILDINGS OVER 2 STORIES IN HEIGHT |
| - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS |
| OF CONSTRUCTION |
| |
| ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION |
| SERVICES MANAGER - TEL: |
| 561 805 6711), A MEETING INVOLVING THE OWNER, RESIDENT |
| INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER. THIS |
| MUST BE DONE PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL |
| SETS OF ALL DOCUMENTS ARE REQUIRED FOR PERMITTING. |
| |
| 5.)AS DISCUSSED, ARCHITECT IS TO APPLY FOR |
| CERTIFICATE OF AUTHORIZATION FOR DAVID LAWRENCE |
| ARCHITECTURE INC., FS481.219(2).THE CORPORATION NAME |
| IS NOT TO APPEAR ON DRAWINGS UNTIL APPROVED BY THE |
| FLORIDA BOARD OF ARCHITECTS AND AN ARCHITECT BUSINESS |
| NUMBER ASSIGNED.IF ARCHITECT BUSINESS NAME IS USED, |
| THE COFA NUMBER IS TO APPEAR ON EACH SHEET |
| FAC61G1-16.002,003. |
| |
| 6.)ALL INFORMATION REQUIRED BY FAC61G16-23.002 IS |
| REQUIRED TO BE ON EACH SHEET SEALED BY THE ENGINEER |
| (CERTIFICATE OF AUTHORIZATION). |
| |
| 7.)HYDRAULIC CALCS ARE REQUIRED TO HAVE ALL |
| INFORMATION REQUIRED BY FAC61G16-23.002 (TITLE BLOCK |
| INFORMATION FOR THE ENGINEER). |
| |
| 8.)SHEET A1.0, PLANS STATE THAT THE BUILDINGS MUST |
| COMPLY WITH FBC1606; THIS IS THE SECTION FOR DEAD |
| LOADS, NOT WIND LOADS.PLEASE REVISE. |
| |
| 9.)DECLARE MEAN ROOF HEIGHT, FBC CHAPTER 5..NOTE |
| THAT THE SHINGLE PRODUCT APPROVAL IS LIMITED TO A MRH |
| OF LESS THAN 33 FEET.PLEASE CONTACT ME TO DISCUSS IF |
| THIS IS AN ISSUE. |
| |
| 10.)INCLUDE 2005 AMENDMENTS IN GOVERNING CODE.THERE |
| WAS A CODE AMENDMENT EFFECTIVE DECEMBER 8, 2006 (PERMIT |
| APPLICATION DATE IS PRIOR TO THIS DATE). |
| |
| 11.)SHEET A1.0 REFERS TO OCCUPANCY SEPARATION; IS |
| THIS REFERRING TO TENANT SEPARATION? |
| |
| 12.)A2.1 FLOOR PLAN NOTES STATES THAT HURRICANE |
| SHUTTERS ARE TO BE INSTALLED.SEE ATTACHED POLICY IN |
| REGARDS TO IMPACT PROTECTION ON COMMERCIAL BUILDINGS. |
| PRODUCT APPROVALS SUBMITTED ARE FOR LARGE MISSILE |
| IMPACT RATED PRODUCTS.PLEASE ADDRESS CONFLICT.IF |
| YOUR INTENT IS TO USE SHUTTERS, NOTE THAT REMOVABLE |
| SHUTTERS ARE PERMITTED ON THE FIRST FLOOR ONLY AND MUST |
| BE APPROVED BY THE BUILDING OFFICIAL.PLEASE CONTACT |
| ME IF THIS IS YOUR INTENT. |
| |
| 13.)NOTE THAT THE UNITS ARE CALLED TOWNHOMES.THEY |
| DO NOT MEET THE FLORIDA STATUTE DEFINITION OF A |
| TOWNHOUSE.THIS COMMENT DOES NOT NEED TO BE |
| ADDRESSED; INFORMATIONAL ONLY.OCCUPANCY |
| CLASSIFICATION FOR THE RESIDENTIAL AREA IS NOTED AS |
| DECLARED, R2. |
| |
| 14.)SEE FBC406, FBC311.3.THE GARAGES AND ACCESS TO |
| THE INDIVIDUAL GARAGE SPACES ACT AS A PARKING GARAGE. |
| OCCUPANCY SEPARATION REQUIRED FBC302.3.2, BOTH |
| HORIZONTAL AND VERTICAL.PENETRATIONS AND DUCTS TO BE |
| PROTECTED, FBC716, FBC712. |
| |
| 15.)PROVIDE EGRESS FROM THE PARKING GARAGE AREA ON |
| THE FIRST FLOOR. |
| |
| 16.)THE PARKING GARAGE VENTILATION TO BE IN |
| COMPLIANCE WITH FLORIDA BUILDING CODE, MECHANICAL. |
| |
| 16.)NFPA 13 SYSTEM REQUIRED AS PARKING GARAGE IS NOT |
| A RESIDENTIAL OCCUPANCY, SEE NFPA 13R 1.1, NFPA 101. |
| ALSO SEE FBC504.2, NFPA 13 SYSTEM REQUIRED IF YOU ARE |
| USING AREA MODIFICATIONS FOR SPRINKLED BUILDINGS. |
| |
| 17.)A5.2, DESIGNER HAS NOT PROVIDED CALCULATIONS IN |
| REGARDS TO OPENINGS FOR THE REAR ELEVATION FBC704.8. |
| NOTE THAT DISTANCE IS TO BE MEASURED TO THE CENTER OF |
| THE ALLEY FOR DISTANCE TO ASSUMED PROPERTY LINE. |
| |
| 18.)A2.1, STAIRS SHOWS "VARIES" FOR TREADS.STAIRS |
| ARE TO COMPLY WITH FBC1009.3.1, DIMENSIONAL UNIFORMITY. |
| NOTE DESIGN CRITERIA FOR THE STAIRS (RANGE FOR RISER |
| HEIGHT) ON THE PLAN. |
| |
| 19.)A2.1, BATHROOM DOOR IS TO HAVE A 29INCH CLEAR |
| OPENING, FBC11-11.1(1). |
| |
| 20.)STAIRS ARE TO BE CONSTRUCTED SO THAT WATER WILL |
| NOT ACCUMULATE ON THE WALKING SURFACE, FBC1009.5.2 |
| (ENTRY TO UNITS). |
| |
| 21.)HANDRAIL EXTENSION REQUIRED FOR STAIRS AT UNIT |
| ENTRIES, FBC1009.11.5.NOTE THAT THE EXCEPTION STATES |
| "WITHIN DWELLING UNITS", THE ENTRY IS OUTSIDE OF THE |
| DWELLING UNIT. |
| |
| 22.)FBC13-603.1ABC.1, ADJACENT DOORS SHALL BE SOLID |
| CORE, WOOD, OR INSULATED.UNIT C, DOORS 6 AND 9, ARE |
| LOCATED IN THE ADJACENT WALL. |
| |
| 23.)DECLARE TOTAL BUILDING SIZE.SHOW COMPLIANCE |
| WITH FBC TABLE 503.SHOW AREA INCREASE CALCULATIONS ON |
| THE PLAN.PLEASE SEE DEFINITION OF BUILDING AREA, TO |
| INCLUDE AREA INCLUDED WITHIN THE HORIZONTAL PROJECTION |
| OF THE FLOOR ABOVE (FIRST FLOOR AREA COVERED BY |
| BALCONIES ON SECOND FLOOR TO BE INCLUDED).DECLARE |
| TOTAL SQUARE FOOT AREA FOR EACH OCCUPANCY |
| CLASSIFICATION. |
| |
| |
| 24.)ARDAMAN & ASSOCIATESBORING LOCATION PLAN STATES |
| THAT THIS IS A TYPE III A FULLY SPRINKLED BUILDING. |
| THIS IS IN CONFLICT WITH THE ARCHITECTURAL PLAN. |
| BUILDING TYPE IS NOT NECESSARY ON THE SOILS REPORT BUT |
| IF PROVIDED MUST BE CONSISTENT WITH THE PLANS. |
| |
| 25.)WIND DESIGN CRITERIA ON CALCULATIONS PREPARED BY |
| RICARDO DIAZ, PE STATES EXPOSURE C BUT THE CALCULATIONS |
| WERE RUN USING EXPOSURE B.SHEET S1.0 ALSO DECLARES |
| EXPOSURE B. |
| |
| 26.)CALCULATIONS WERE DONE USING ASCE7-05.SEE |
| FBC35, ASCE7-02 IS THE CORRECT STANDARD. |
| |
| 27.)THE AGREEMENT FOR UNITY OF TITLE IS NOT SIGNED BY |
| ALL PARTIES AND OWNER ON THE UNITY OF TITLE IS NOT THE |
| OWNER OF RECORD (CLERK?S OFFICE).THIS ISSUE IS |
| REQUIRED TO BE RESOLVED PRIOR TO PERMIT ISSUANCE.THE |
| PROPOSED IMPROVEMENT CROSSES THE PROPERTY LINE WHICH |
| WOULD NOT BE ALLOWED WITHOUT A FIREWALL, FBC CHAPTER |
| 6. |
| |
| |
| 28.)A1.2, THE DISTANCE OF THE BUILDING FROM THE |
| PROPERTY LINE IS LESS THAN 30FT (MEASURE TO CENTER LINE |
| OF THE ALLEY).ONE HOUR WALL REQUIRED, FBC602. PROVIDE |
| A DETAIL. |
| |
| 29.)STRUCTURAL ELEMENTS ARE TO COMPLY WITH FBC TABLE |
| 601.SHOW CALCULATED FIRE RESISTANCE OR LISTED |
| ASSEMBLY. |
| |
| 30.)WINDOW O, HORIZONTAL ROLLER, HAS A DESIGN |
| PRESSURE OF -53.72.SEE THE CHART ON SHEET 1 OF 6 OF |
| THE PRODUCT APPROVAL, GLASS TYPES A & C ARE NOT |
| COMPLIANT FOR THIS SIZE.PLEASE CIRCLE ON THE PRODUCT |
| APPROVAL WHICH PRODUCT YOU WILL BE INSTALLING. |
| |
| 31.)SEE SHEET 3 OF 11 OF THE SINGLE HUNG PRODUCT |
| APPROVAL.NOT ALL GLASS OPTIONS ARE COMPLIANT FOR |
| DESIGN PRESSURES ON A5.3.PLEASE INDICATE WHICH |
| PRODUCT YOU WILL INSTALL. |
| |
| 32.)SEE SHEET 5 OF 13 OF THE CASEMENT WINDOW PRODUCT |
| APPROVAL.NOT ALL GLASS OPTIONS ARE COMPLIANT FOR |
| DESIGN PRESSURES ON A5.3.PLEASE INDICATE WHICH |
| PRODUCT YOU WILL INSTALL. |
| |
| 33.)A5.3, ENTRY DOOR 10 IS SHOWN AS 3?0 ON THE DOOR |
| SCHEDULE, 2.67 WIDTH ON DOOR PRESSURES.PLEASE |
| ADDRESS. |
| |
| 34.)DESIGN PRESSURE REQUIREMENT FOR DOORS 5 AND 6 |
| EXCEED PRODUCT LIMITATION, SEE THERMATRU PRODUCT |
| APPROVAL, SHEET 1.NOTE THAT THE DOOR PRESSURES APPEAR |
| TO HAVE BEEN CALCULATED FROM A SINGLE DOOR, BUT CAN BE |
| DONE USING THE ENTIRE OPENING (DOUBLE DOOR WITH |
| TRANSOM). |
| |
| 35.)THE DOOR PRODUCT APPROVAL SUBMITTED DOES NOT |
| INCLUDE THE TRANSOM ABOVE.PLEASE ADDRESS WITH A |
| DETAIL AND PRODUCT APPROVALS FOR MULLIONS, FIXED GLASS |
| WINDOW OR SUBMIT A PRODUCT APPROVAL WHICH INCLUDES THE |
| USE OF A TRANSOM. |
| |
| 36.)A5.3, ENTRY OVERHANG TYPE 1, DOES NOT SHOW THE |
| 1X2 WHICH IS TYPICALLY INSTALLED UNDER THE DRIP EDGE TO |
| PREVENT THE FASCIA BOARD FROM ROTTING.THIS IS SHOWN |
| GRAPHICALLY ON ENTRY OVERHANG TYPE 2.YOUR USE OF A PT |
| FASCIA IS NOTED; HOWEVER, SINCE A MIAMIDADE NOA WAS |
| SUBMITTED FOR THE ROOF SHINGLES, THE SHINGLES ARE TO BE |
| INSTALLED IN ACCORDANCE WITH RAS115, RAS111, AND |
| FBC1517.6.2.2.PLEASE ADDRESS. |
| |
| 37.)PROVIDE A DETAIL FOR U301, 2 A7.1. |
| |
| 38.)S1.0 REFERS TO DESIGN LOAD REQUIREMENTS FOR ONE |
| AND TWO FAMILY DWELLINGS.THIS IS MULTIFAMILY, R2, NOT |
| ONE AND TWO FAMILY DWELLINGS, R3.SEE FBC TABLE |
| 1607.1, 27 RESIDENTIAL AND FBC 310.SEE ALSO |
| REQUIREMENTS FOR STAIRS. |
| |
| 39.)S3 SHEATHING NOTES SPECIFIES 4INCH FOR CORNERS ON |
| GABLE ENDS.THIS ROOF IS A HIP ROOF, 4 INCH IS |
| REQUIRED FOR ZONE 3 REGARDLESS OF ROOF TYPE. |
| |
| 40.)S5 WINDOW NOTES SPECIFICATIONS REFER TO 120 MPH, |
| CITY OF WEST PALM BEACH IS IN THE 140MPH WIND ZONE. |
| |
| 41.)FIRE SPRINKLER NOTES REGARDING SPRINKLERS IN |
| BATHROOMS IS FOR NFPA13R.THE SYSTEM IS TO COMPLY WITH |
| NFPA13. |
| |
| 42.)CIVILS AND ARCHITECTURALS DO NOT MATCH.PLEASE |
| ADDRESS. |
| |
| 43.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC, |
| FBC13-103.1. |
| |
| 44.)IT APPEARS THAT THE GARAGE DOOR BLOCKS THE FIRE |
| SPRINKLER HEAD.PLEASE ADDRESS. |