Plan Review Notes
Plan Review Notes For Permit 06120129
Permit Number 06120129
Review Stop B
Sequence Number 1
Notes
Date Text
2007-01-22 15:58:50****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.THE PLANS
 MUST BE STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.PLEASE CALL 561-233-5025 FOR MORE
 INFORMATION.
  
 3.)RADON FEES HAVE BEEN ADDED FS553.721.THIS MAY BE
 ADJUSTED AFTER EXACT BUILDING SIZE IS DETERMINED.
  
 4.) FBC* 109.3.7RESIDENT INSPECTOR. SUBMIT INSPECTOR
 RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA,
 DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT
 INSPECTOR PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO
 ONE OR MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS
 OF CONSTRUCTION
  
 ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION
 SERVICES MANAGER - TEL:
 561 805 6711), A MEETING INVOLVING THE OWNER, RESIDENT
 INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER. THIS
 MUST BE DONE PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL
 SETS OF ALL DOCUMENTS ARE REQUIRED FOR PERMITTING.
  
 5.)AS DISCUSSED, ARCHITECT IS TO APPLY FOR
 CERTIFICATE OF AUTHORIZATION FOR DAVID LAWRENCE
 ARCHITECTURE INC., FS481.219(2).THE CORPORATION NAME
 IS NOT TO APPEAR ON DRAWINGS UNTIL APPROVED BY THE
 FLORIDA BOARD OF ARCHITECTS AND AN ARCHITECT BUSINESS
 NUMBER ASSIGNED.IF ARCHITECT BUSINESS NAME IS USED,
 THE COFA NUMBER IS TO APPEAR ON EACH SHEET
 FAC61G1-16.002,003.
  
 6.)ALL INFORMATION REQUIRED BY FAC61G16-23.002 IS
 REQUIRED TO BE ON EACH SHEET SEALED BY THE ENGINEER
 (CERTIFICATE OF AUTHORIZATION).
  
 7.)HYDRAULIC CALCS ARE REQUIRED TO HAVE ALL
 INFORMATION REQUIRED BY FAC61G16-23.002 (TITLE BLOCK
 INFORMATION FOR THE ENGINEER).
  
 8.)SHEET A1.0, PLANS STATE THAT THE BUILDINGS MUST
 COMPLY WITH FBC1606; THIS IS THE SECTION FOR DEAD
 LOADS, NOT WIND LOADS.PLEASE REVISE.
  
 9.)DECLARE MEAN ROOF HEIGHT, FBC CHAPTER 5..NOTE
 THAT THE SHINGLE PRODUCT APPROVAL IS LIMITED TO A MRH
 OF LESS THAN 33 FEET.PLEASE CONTACT ME TO DISCUSS IF
 THIS IS AN ISSUE.
  
 10.)INCLUDE 2005 AMENDMENTS IN GOVERNING CODE.THERE
 WAS A CODE AMENDMENT EFFECTIVE DECEMBER 8, 2006 (PERMIT
 APPLICATION DATE IS PRIOR TO THIS DATE).
  
 11.)SHEET A1.0 REFERS TO OCCUPANCY SEPARATION; IS
 THIS REFERRING TO TENANT SEPARATION?
  
 12.)A2.1 FLOOR PLAN NOTES STATES THAT HURRICANE
 SHUTTERS ARE TO BE INSTALLED.SEE ATTACHED POLICY IN
 REGARDS TO IMPACT PROTECTION ON COMMERCIAL BUILDINGS.
 PRODUCT APPROVALS SUBMITTED ARE FOR LARGE MISSILE
 IMPACT RATED PRODUCTS.PLEASE ADDRESS CONFLICT.IF
 YOUR INTENT IS TO USE SHUTTERS, NOTE THAT REMOVABLE
 SHUTTERS ARE PERMITTED ON THE FIRST FLOOR ONLY AND MUST
 BE APPROVED BY THE BUILDING OFFICIAL.PLEASE CONTACT
 ME IF THIS IS YOUR INTENT.
  
 13.)NOTE THAT THE UNITS ARE CALLED TOWNHOMES.THEY
 DO NOT MEET THE FLORIDA STATUTE DEFINITION OF A
 TOWNHOUSE.THIS COMMENT DOES NOT NEED TO BE
 ADDRESSED; INFORMATIONAL ONLY.OCCUPANCY
 CLASSIFICATION FOR THE RESIDENTIAL AREA IS NOTED AS
 DECLARED, R2.
  
 14.)SEE FBC406, FBC311.3.THE GARAGES AND ACCESS TO
 THE INDIVIDUAL GARAGE SPACES ACT AS A PARKING GARAGE.
 OCCUPANCY SEPARATION REQUIRED FBC302.3.2, BOTH
 HORIZONTAL AND VERTICAL.PENETRATIONS AND DUCTS TO BE
 PROTECTED, FBC716, FBC712.
  
 15.)PROVIDE EGRESS FROM THE PARKING GARAGE AREA ON
 THE FIRST FLOOR.
  
 16.)THE PARKING GARAGE VENTILATION TO BE IN
 COMPLIANCE WITH FLORIDA BUILDING CODE, MECHANICAL.
  
 16.)NFPA 13 SYSTEM REQUIRED AS PARKING GARAGE IS NOT
 A RESIDENTIAL OCCUPANCY, SEE NFPA 13R 1.1, NFPA 101.
 ALSO SEE FBC504.2, NFPA 13 SYSTEM REQUIRED IF YOU ARE
 USING AREA MODIFICATIONS FOR SPRINKLED BUILDINGS.
  
 17.)A5.2, DESIGNER HAS NOT PROVIDED CALCULATIONS IN
 REGARDS TO OPENINGS FOR THE REAR ELEVATION FBC704.8.
 NOTE THAT DISTANCE IS TO BE MEASURED TO THE CENTER OF
 THE ALLEY FOR DISTANCE TO ASSUMED PROPERTY LINE.
  
 18.)A2.1, STAIRS SHOWS "VARIES" FOR TREADS.STAIRS
 ARE TO COMPLY WITH FBC1009.3.1, DIMENSIONAL UNIFORMITY.
 NOTE DESIGN CRITERIA FOR THE STAIRS (RANGE FOR RISER
 HEIGHT) ON THE PLAN.
  
 19.)A2.1, BATHROOM DOOR IS TO HAVE A 29INCH CLEAR
 OPENING, FBC11-11.1(1).
  
 20.)STAIRS ARE TO BE CONSTRUCTED SO THAT WATER WILL
 NOT ACCUMULATE ON THE WALKING SURFACE, FBC1009.5.2
 (ENTRY TO UNITS).
  
 21.)HANDRAIL EXTENSION REQUIRED FOR STAIRS AT UNIT
 ENTRIES, FBC1009.11.5.NOTE THAT THE EXCEPTION STATES
 "WITHIN DWELLING UNITS", THE ENTRY IS OUTSIDE OF THE
 DWELLING UNIT.
  
 22.)FBC13-603.1ABC.1, ADJACENT DOORS SHALL BE SOLID
 CORE, WOOD, OR INSULATED.UNIT C, DOORS 6 AND 9, ARE
 LOCATED IN THE ADJACENT WALL.
  
 23.)DECLARE TOTAL BUILDING SIZE.SHOW COMPLIANCE
 WITH FBC TABLE 503.SHOW AREA INCREASE CALCULATIONS ON
 THE PLAN.PLEASE SEE DEFINITION OF BUILDING AREA, TO
 INCLUDE AREA INCLUDED WITHIN THE HORIZONTAL PROJECTION
 OF THE FLOOR ABOVE (FIRST FLOOR AREA COVERED BY
 BALCONIES ON SECOND FLOOR TO BE INCLUDED).DECLARE
 TOTAL SQUARE FOOT AREA FOR EACH OCCUPANCY
 CLASSIFICATION.
  
  
 24.)ARDAMAN & ASSOCIATESBORING LOCATION PLAN STATES
 THAT THIS IS A TYPE III A FULLY SPRINKLED BUILDING.
 THIS IS IN CONFLICT WITH THE ARCHITECTURAL PLAN.
 BUILDING TYPE IS NOT NECESSARY ON THE SOILS REPORT BUT
 IF PROVIDED MUST BE CONSISTENT WITH THE PLANS.
  
 25.)WIND DESIGN CRITERIA ON CALCULATIONS PREPARED BY
 RICARDO DIAZ, PE STATES EXPOSURE C BUT THE CALCULATIONS
 WERE RUN USING EXPOSURE B.SHEET S1.0 ALSO DECLARES
 EXPOSURE B.
  
 26.)CALCULATIONS WERE DONE USING ASCE7-05.SEE
 FBC35, ASCE7-02 IS THE CORRECT STANDARD.
  
 27.)THE AGREEMENT FOR UNITY OF TITLE IS NOT SIGNED BY
 ALL PARTIES AND OWNER ON THE UNITY OF TITLE IS NOT THE
 OWNER OF RECORD (CLERK?S OFFICE).THIS ISSUE IS
 REQUIRED TO BE RESOLVED PRIOR TO PERMIT ISSUANCE.THE
 PROPOSED IMPROVEMENT CROSSES THE PROPERTY LINE WHICH
 WOULD NOT BE ALLOWED WITHOUT A FIREWALL, FBC CHAPTER
 6.
  
  
 28.)A1.2, THE DISTANCE OF THE BUILDING FROM THE
 PROPERTY LINE IS LESS THAN 30FT (MEASURE TO CENTER LINE
 OF THE ALLEY).ONE HOUR WALL REQUIRED, FBC602. PROVIDE
 A DETAIL.
  
 29.)STRUCTURAL ELEMENTS ARE TO COMPLY WITH FBC TABLE
 601.SHOW CALCULATED FIRE RESISTANCE OR LISTED
 ASSEMBLY.
  
 30.)WINDOW O, HORIZONTAL ROLLER, HAS A DESIGN
 PRESSURE OF -53.72.SEE THE CHART ON SHEET 1 OF 6 OF
 THE PRODUCT APPROVAL, GLASS TYPES A & C ARE NOT
 COMPLIANT FOR THIS SIZE.PLEASE CIRCLE ON THE PRODUCT
 APPROVAL WHICH PRODUCT YOU WILL BE INSTALLING.
  
 31.)SEE SHEET 3 OF 11 OF THE SINGLE HUNG PRODUCT
 APPROVAL.NOT ALL GLASS OPTIONS ARE COMPLIANT FOR
 DESIGN PRESSURES ON A5.3.PLEASE INDICATE WHICH
 PRODUCT YOU WILL INSTALL.
  
 32.)SEE SHEET 5 OF 13 OF THE CASEMENT WINDOW PRODUCT
 APPROVAL.NOT ALL GLASS OPTIONS ARE COMPLIANT FOR
 DESIGN PRESSURES ON A5.3.PLEASE INDICATE WHICH
 PRODUCT YOU WILL INSTALL.
  
 33.)A5.3, ENTRY DOOR 10 IS SHOWN AS 3?0 ON THE DOOR
 SCHEDULE, 2.67 WIDTH ON DOOR PRESSURES.PLEASE
 ADDRESS.
  
 34.)DESIGN PRESSURE REQUIREMENT FOR DOORS 5 AND 6
 EXCEED PRODUCT LIMITATION, SEE THERMATRU PRODUCT
 APPROVAL, SHEET 1.NOTE THAT THE DOOR PRESSURES APPEAR
 TO HAVE BEEN CALCULATED FROM A SINGLE DOOR, BUT CAN BE
 DONE USING THE ENTIRE OPENING (DOUBLE DOOR WITH
 TRANSOM).
  
 35.)THE DOOR PRODUCT APPROVAL SUBMITTED DOES NOT
 INCLUDE THE TRANSOM ABOVE.PLEASE ADDRESS WITH A
 DETAIL AND PRODUCT APPROVALS FOR MULLIONS, FIXED GLASS
 WINDOW OR SUBMIT A PRODUCT APPROVAL WHICH INCLUDES THE
 USE OF A TRANSOM.
  
 36.)A5.3, ENTRY OVERHANG TYPE 1, DOES NOT SHOW THE
 1X2 WHICH IS TYPICALLY INSTALLED UNDER THE DRIP EDGE TO
 PREVENT THE FASCIA BOARD FROM ROTTING.THIS IS SHOWN
 GRAPHICALLY ON ENTRY OVERHANG TYPE 2.YOUR USE OF A PT
 FASCIA IS NOTED; HOWEVER, SINCE A MIAMIDADE NOA WAS
 SUBMITTED FOR THE ROOF SHINGLES, THE SHINGLES ARE TO BE
 INSTALLED IN ACCORDANCE WITH RAS115, RAS111, AND
 FBC1517.6.2.2.PLEASE ADDRESS.
  
 37.)PROVIDE A DETAIL FOR U301, 2 A7.1.
  
 38.)S1.0 REFERS TO DESIGN LOAD REQUIREMENTS FOR ONE
 AND TWO FAMILY DWELLINGS.THIS IS MULTIFAMILY, R2, NOT
 ONE AND TWO FAMILY DWELLINGS, R3.SEE FBC TABLE
 1607.1, 27 RESIDENTIAL AND FBC 310.SEE ALSO
 REQUIREMENTS FOR STAIRS.
  
 39.)S3 SHEATHING NOTES SPECIFIES 4INCH FOR CORNERS ON
 GABLE ENDS.THIS ROOF IS A HIP ROOF, 4 INCH IS
 REQUIRED FOR ZONE 3 REGARDLESS OF ROOF TYPE.
  
 40.)S5 WINDOW NOTES SPECIFICATIONS REFER TO 120 MPH,
 CITY OF WEST PALM BEACH IS IN THE 140MPH WIND ZONE.
  
 41.)FIRE SPRINKLER NOTES REGARDING SPRINKLERS IN
 BATHROOMS IS FOR NFPA13R.THE SYSTEM IS TO COMPLY WITH
 NFPA13.
  
 42.)CIVILS AND ARCHITECTURALS DO NOT MATCH.PLEASE
 ADDRESS.
  
 43.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC,
 FBC13-103.1.
  
 44.)IT APPEARS THAT THE GARAGE DOOR BLOCKS THE FIRE
 SPRINKLER HEAD.PLEASE ADDRESS.