2006-12-27 10:50:33*****DENIED*****
  
  
  
 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE
 PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER ACCESS TO OR EGRESS FROM OTHER
 SUITES ON THE FLOOR OR THE BUILDING.
  
 4.WILL THERE BE ADEQUATE VISIBILITY TOWARDS THE EXIT
 SIGN LIGHT FROM THE FRONT DOOR OF THE #3 OFFICE?IF
 NOT, AN ADDITIONAL EXIT LIGHT WILL BE REQUIRED.
  
 5.IT IS STATED IN THE REFLECTED CEILING /LIGHTING
 NOTE #9 THAT THE ENTIRE SPACE WILL BE FIRE SPRINKLED,
 WHEREAS IN THE POWER PLAN NOTE #8 IT STATES "NO FIRE
 ALARM AT THIS SPACE" ;HOW WILL THE FIRE SPRINKLER
 SYSTEM BE MONITORED?
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  