Plan Review Notes For Permit 06120084 |
Permit Number |
06120084 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-12-11 16:15:15 | BUILDING REVIEW 2ND CHECKLIST: | | 1- PROVIDE RAS 117 CALCULATIONS FOR ENHANCED FASTENING | | AT PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | LIMITATION #7 ON LAST PAGE OF DADE COUNTY NOA | | 02-1219.01.FASTENER SPACING TABLE SUBMITTED CAN'T BE | | USED IN THIS AREA. TABLE IS ONLY GOOD FOR120MPH WIND | | ZONE. THE CITY IS IN 140MPH WIND ZONE. ON THE OTHER | | HAND TABLE APPLIES TO NAIL ENHANCEMENT IN THE FIELD | | AREA ONLY. | | | | 2- A)SUBMITTED WIND UPLIFT PRESSURE CALCULATIONS FOR | | ROOF NEED TO BE SIGNED AND SEALED BY THE ENGINEER WHO | | MADE THE CALCULATIONS AS REQUIRED BY CHAPTER 471 | | FLORIDA STATUTES. ENGINEER TO PROVIDE ALL HIS | | INFORMATION AS REQUIRED BY FLORIDA ADMINISTRATIVE CODE | | SEC. 61G15-23.002. | | | | B) ENGINEER TO IDENTIFY SPECIFIC APPROVEDASSEMBLY | | FROM THE NOA SUBMITTED. | | | | C) CALCULATIONS ARE DONE FOR NOA 02.0710.01. NOA | | SUBMITTED IS 02-1219.01. INFORMATION NEED TO MATCH. | | | | D) ENGINEER TO PROVIDE ALL THE INFORMATION ON TOP OF | | FORM. INFORMATION WAS ERASED WITH WHITE OUT. | | | | 3- OWES $128.27. | | | | | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|