Plan Review Notes
Plan Review Notes For Permit 06120074
Permit Number 06120074
Review Stop B
Sequence Number 4
Notes
Date Text
2007-08-15 11:30:282004 FBC W/ 2005 SUPPLEMENT
 ADD WINDOWS AND INSTALL FACADE
  
 DENIED BY BUILDING
  
 1) SUBMIT NOTICE OF COMMENCEMENT.
  
 2) THE PRODUCT APPROVALS SUBMITTED ARE NOT ACCEPTABLE.
 IN ADDITION TO THE FLORIDA COVERSHEETS, THE STATE
 APPROVED EVALUATION REPORT OR MIAMI-DADE NOA SPECIFYING
 THE DESIGN PRESSURES FOR THE PRODUCT AND THE
 INSTALLATION DRAWINGS ARE REQUIRED TO BE SUBMITTED FOR
 REVIEW. SEE FAC RULE 9B-72. IF MULTIPLE PRODUCTS ARE
 LISTED, SPECIFY THE ONES THAT WILL BE USED.
  
 3)THE STATE PRODUCT APPROVAL COVERSHEETS THAT WERE
 SUBMITTED FOR THE JELD-WEN-POZZI CASEMENT WINDOWS AND
 FIXED WINDOWS ARE FOR THE 2001 CODE VERSION. SUBMIT THE
 ONES FOR THE 2004 CODE ALONG WITH THE NOA OR OTHER
 EVALUATION REPORT AS REQUESTED IN COMMENT #2.
  
 4) PLEASE REVIEW PRODUCT APPROVALS FOR ADEQUATE DESIGN
 PRESSURES AND IMPACT PROTECTION. CHECK FOR CORRECT CODE
 ADDITION AND CURRENT REVISIONS OF PRODUCT APPROVALS.
 CHECK THAT THE MULLIONS SPECIFIED ARE COMPATIBLE WITH
 THE WINDOW MODELS THAT ARE SPECIFIED.
  
 5) THE BEAM ANALYSIS THAT WAS SUBMITTED IS FOR A W12 X
 65STEEL I-BEAM, WHICH HAS BEEN CHANGED ON THE
 ARCHITECTURAL DRAWINGS TO A HSS 8 X 8 X 1/2" TUBE STEEL
 BEAM. SUBMIT ANENGINEERED ANALYSIS OF THE TUBE STEEL
 BEAM FOR BENDING AND TORSION. 2004 FBC* 106.1.2
 (AMENDED)
  
 6) PROVIDE THE COLUMN SPACING DIMENSIONS ON THE PLANS
 FOR THE COLUMNS THAT WILL BE SUPPORTING THE BEAM. 2004
 FBC* 106.1.2 (AMENDED)
  