2007-07-03 14:39:04 | DENIED BY BUILDING |
| |
| 1)A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) THE PLANS SPECIFY THIS STRUCTURE AS A TYPE III- B. |
| THIS IS INCORRECT. IN ORDER TO BE TYPE III- B, THE |
| EXTERIOR WALLS ARE REQUIRED TO BE OF NONCOMBUSTABLE |
| MATERIALS. BECAUSE OF THE WOOD FRAME EXTERIOR WALL, |
| THIS BUILDING IS TYPE V- B. |
| |
| 3)WPB ADMIN CODE 106.3* PRODUCT |
| APPROVALS. THOSE PRODUCT WHICH ARE |
| REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| 4)PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCTS HAVE A STATE PRODUCT APPROVAL |
| SUBMIT A COVERSHEET WITH THE STATE APPROVAL NUMBER. |
| |
| 5) THE PLANS SPECIFY 3' X 6'CASEMENT WINDOWS. THE |
| PRODUCT APPROVAL SUBMITTED FOR THE JELD-WEN CASEMENT |
| WINDOWS, NOA 03-1204.02 HAS A MAXIMUM WINDOW SIZE OF |
| 30" X 72". |
| |
| 6) THE PRODUCT APPROVAL NOA 04-1122.04 FOR THE MULLIONS |
| HAS BEEN REVISED BY NOA 05-0223.01. SUBMIT THE NEW |
| NOA. |
| |
| 7) IN REGUARD TO THE STRUCTURAL ANALYSIS OF THE SOUTH |
| WALL OF THE BUILDING: |
| - SUBMIT LOAD CALCULATIONS FOR THE 8" X 8" TUBE STEEL |
| BEAM WHICH INDICATE THAT IT IS CAPABLE OF SUPPORTING |
| THE NEW BRICK AND MORTAR VENEER AND THE EXISTING STUCCO |
| AND WOOD FRAME WALL. |
| - SHOW HOW THE EXISTING WOOD FRAME AND STUCCO WALL WILL |
| SUPPORT THE ECCENTRIC LOADS. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |