Plan Review Notes
Plan Review Notes For Permit 06120074
Permit Number 06120074
Review Stop B
Sequence Number 2
Notes
Date Text
2007-03-19 11:00:57DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SUBMIT THE INSTALLATION INSTRUCTIONS WITH THE DESIGN
 PRESSURES FOR THE IMPACT WINDOWS. PROVIDE DOCUMENTATION
 THAT THE WINDOWS HAVE BEEN TESTED FOR LARGE MISSLE
 IMPACT. (ITEM #6 FROM FIRST REVIEW.)
  
 3)SUBMIT PRODUCT APPROVALS FOR THE STRUCTURAL
 MULLIONS BETWEEN THE CASEMENT AND FIXED GLASS ARCHED
 WINDOWS. (ITEM #7 FROM FIRST REVIEW.)
  
 4) THE DEMOLITION PLAN ON SHEET D-1.1 IS STILL
 INDICATING SIX WINDOW OPENINGS AND THE NEW ELEVATION ON
 A-1.1 SHOWS FIVE NEW WINDOWS. PLEASE CLARIFY.
  
 5)ON SHEETS A-1.1 AND A-1.2 THE FLORIDA PRODUCT
 APPROVAL NUMBERS FOR THE WINDOWS ARE LISTED ON THE
 PLANS PRECEDED BY FBC. THIS IS INCORRECT. THE NUMERALS
 SHOULD BE PRECEDED BY FL #. PLEASE CORRECT.
  
 6)HAVE A FLORIDA REGISTERED STRUCTURAL ENGINEER
 PERFORM A STRUCTURAL ANALYSIS OF THE EXISTING AND
 PROPOSED SOUTH WALL OF THE BUILDING AND EXISTING STUCCO
 AND WIRE LATH ATTACHMENT TO THE WOOD FRAME WALL. SUBMIT
 A SIGNED AND SEALED LETTER STATING THAT THE EXISTING
 WOOD FRAME STUCCO WALLS AND PARAPET ARE CAPABLE OF
 SAFELY SUPPORTING THE ADDITIONAL DEAD LOADS THAT WILL
 BE IMPOSED BY THE ADDITION OF THE CULTURED BRICK AND
 TRIM TO THE EXISTING FACADE AND RESIST THE LIVE LOADS
 OF A 140 MPH WINDLOAD.
  
 7) SPECIFY HOW THE CULTURED VENEER WILL BE ATTACHED TO
 THE EXISTING WALL. SEE THE ENCLOSED INSTALLATION
 INSTRUCTIONS.
  
 NOTE: INSTALLATION INSTRUCTIONS AND MSDS FOR THE
 CULTURED BRICK HAVE BEEN DOWNLOADED AND INSERTED INTO
 YOUR SUBMITTAL PACKAGE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  