Plan Review Notes
Plan Review Notes For Permit 06120074
Permit Number 06120074
Review Stop B
Sequence Number 1
Notes
Date Text
2007-01-11 12:09:23DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE VALUE APPEARS TO BE QUITE LOW FOR THE APPARENT
 SCOPE OF WORK. PLEASE INCREASE THE VALUE TO REFLECT THE
 SCOPE OF THE PROPOSED WORK.
  
 3) 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4)SPECIFY THE APPLICABLE CODES ON THE PLANS.
  
 5) SPECIFY THE WINDLOAD PRESSURES AT THE WINDOW
 OPENINGS ON THE PLANS.
  
 6) SUBMIT THE INSTALLATION INSTRUCTIONS WITH DESIGN
 PRESSURES FOR THE IMPACT WINDOWS. PROVIDE DOCUMENTATION
 THAT WINDOWS HAVE BEEN TESTED FOR LARGE MISSILE
 IMPACT.
  
 7) SUBMIT PRODUCT APPROVALS FOR THE WINDOW MULLIONS
 BETWEEN CASEMENT AND FIXED ARCHED WINDOWS.
  
 8)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 9) SPECIFY THE WINDOW SIZES ON THE PLANS.
  
 10) THE DEMO PLAN ON D-1.1 SHOWS SIX WINDOW OPENINGS
 AND NOTE 3.8 STATES REMOVE EXISTING CONCRETE WALL FOR
 WINDOW INSTALLATION. THE ELEVATION ON A1-1 SHOWS FOUR
 WINDOWS. THE WALL SECTION ON A-1.2 SPECIFIES WOOD
 FRAME. PLEASE CORRECT.
  
 11) PLEASE CLARIFY THE DRAWINGS ON A-1.2INDICATE WHAT
 IS EXISTING AND WHAT IS NEW. PROVIDE A WALL SECTION
 SHOWING THIS WALL IN ITS EXISTING CONDITION.
  
 12) IT APPEARS THAT THE SECOND FLOOR IS BEING BUILT
 OUT. INDICATE WHERE THE PROPERTY LINE IS IN RELATION TO
 THE EXTERIOR WALL AT THE SECOND FLOOR. THE SECOND FLOOR
 CAN NOT PROJECT OVER THE PROPERTY LINE.
  
 13)PROVIDE AN ELEVATION SHOWING THE HEADERS AND
 FRAMING DETAILS AT THE NEW WINDOW OPENINGS. SPECIFY
 STRAPPING AND CONNECTORS. PROVIDE PRODUCT APPROVALS FOR
 CONNECTORS.
  
 14)SPECIFY THE VAPOR RETARDER REQUIRED BY FBC 1403.3
 BEHIND THE NEW CULTURED BRICK VENEER.
  
 15) PROVIDE THE TECHNICAL DATA AND STANDARDS, INCLUDING
 FIRE RESISTANCE AND WINDLOAD INFORMATION , AS WELL AS
 THE INSTALLATION (ATTACHMENT) INFORMATION FOR THE OWENS
 CORNING CB-4054 BRICK VENEER.
  
 16)PROVIDE THE TECHNICAL DATA AND STANDARDS,
 INCLUDING FIRE RESISTANCE AND WINDLOAD INFORMATION , AS
 WELL AS THE INSTALLATION (ATTACHMENT) INFORMATION FOR
 THE LIGHTWEIGHT CORNICE, SILL, ROWLOCK COURSE AND ANY
 OTHER TRIM.
  
 17) THE TITLE BLOCK ON SHEET D-1.1 IS INCOMPLETE
 APPARANTLY DUE TO A PRINTING ERROR.
  
 18) THE PRINTED NAME OF THE PERSON SIGNING AND SEALING
 THE PLAN IS REQUIRED IN THE TITLE BLOCK BY FAC
 61G1-16.004.
  
 19) THERE ARE SOME NOTATIONS ON ONE OF THE PLANS IN RED
 PENCIL.
  
 20) DUE TO THE LACK OF INFORMATION ON THE PLANS AND
 SUBMITTALS, ADDITIONAL COMMENTS MAY RESULT WHEN THESE
 ITEMS ARE ADDRESSED.
  
 21) TO EXPEDITE PLAN REVIEW PLEASE RETURN ONE SET OF
 THE OLD PLANS ALONG WITH A RESPONSE LETTER.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  
  
  
  
  
  
  
  
  
  