2007-01-11 12:09:23 | DENIED BY BUILDING |
| |
| 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) THE VALUE APPEARS TO BE QUITE LOW FOR THE APPARENT |
| SCOPE OF WORK. PLEASE INCREASE THE VALUE TO REFLECT THE |
| SCOPE OF THE PROPOSED WORK. |
| |
| 3) 2004 FL. BLD CODE 1603.1.4 THE |
| FOLLOWING INFORMATION RELATED TO WIND |
| SHALL BE SHOWN ON THE CONSTRUCTION |
| DRAWINGS, |
| 1)- BASIC WIND SPEED, MPH |
| 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| CATEGORY |
| 3)- WIND EXPOSURE |
| 4)- INTERNAL PRESSURE COEFFICIENT, |
| 5)- COMPONENTS & CLADDING, THE DESIGN |
| WIND PRESSURES IN TERMS OF PSF. |
| |
| 4)SPECIFY THE APPLICABLE CODES ON THE PLANS. |
| |
| 5) SPECIFY THE WINDLOAD PRESSURES AT THE WINDOW |
| OPENINGS ON THE PLANS. |
| |
| 6) SUBMIT THE INSTALLATION INSTRUCTIONS WITH DESIGN |
| PRESSURES FOR THE IMPACT WINDOWS. PROVIDE DOCUMENTATION |
| THAT WINDOWS HAVE BEEN TESTED FOR LARGE MISSILE |
| IMPACT. |
| |
| 7) SUBMIT PRODUCT APPROVALS FOR THE WINDOW MULLIONS |
| BETWEEN CASEMENT AND FIXED ARCHED WINDOWS. |
| |
| 8)WPB ADMIN CODE 106.3* PRODUCT |
| APPROVALS. THOSE PRODUCT WHICH ARE |
| REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| 9) SPECIFY THE WINDOW SIZES ON THE PLANS. |
| |
| 10) THE DEMO PLAN ON D-1.1 SHOWS SIX WINDOW OPENINGS |
| AND NOTE 3.8 STATES REMOVE EXISTING CONCRETE WALL FOR |
| WINDOW INSTALLATION. THE ELEVATION ON A1-1 SHOWS FOUR |
| WINDOWS. THE WALL SECTION ON A-1.2 SPECIFIES WOOD |
| FRAME. PLEASE CORRECT. |
| |
| 11) PLEASE CLARIFY THE DRAWINGS ON A-1.2INDICATE WHAT |
| IS EXISTING AND WHAT IS NEW. PROVIDE A WALL SECTION |
| SHOWING THIS WALL IN ITS EXISTING CONDITION. |
| |
| 12) IT APPEARS THAT THE SECOND FLOOR IS BEING BUILT |
| OUT. INDICATE WHERE THE PROPERTY LINE IS IN RELATION TO |
| THE EXTERIOR WALL AT THE SECOND FLOOR. THE SECOND FLOOR |
| CAN NOT PROJECT OVER THE PROPERTY LINE. |
| |
| 13)PROVIDE AN ELEVATION SHOWING THE HEADERS AND |
| FRAMING DETAILS AT THE NEW WINDOW OPENINGS. SPECIFY |
| STRAPPING AND CONNECTORS. PROVIDE PRODUCT APPROVALS FOR |
| CONNECTORS. |
| |
| 14)SPECIFY THE VAPOR RETARDER REQUIRED BY FBC 1403.3 |
| BEHIND THE NEW CULTURED BRICK VENEER. |
| |
| 15) PROVIDE THE TECHNICAL DATA AND STANDARDS, INCLUDING |
| FIRE RESISTANCE AND WINDLOAD INFORMATION , AS WELL AS |
| THE INSTALLATION (ATTACHMENT) INFORMATION FOR THE OWENS |
| CORNING CB-4054 BRICK VENEER. |
| |
| 16)PROVIDE THE TECHNICAL DATA AND STANDARDS, |
| INCLUDING FIRE RESISTANCE AND WINDLOAD INFORMATION , AS |
| WELL AS THE INSTALLATION (ATTACHMENT) INFORMATION FOR |
| THE LIGHTWEIGHT CORNICE, SILL, ROWLOCK COURSE AND ANY |
| OTHER TRIM. |
| |
| 17) THE TITLE BLOCK ON SHEET D-1.1 IS INCOMPLETE |
| APPARANTLY DUE TO A PRINTING ERROR. |
| |
| 18) THE PRINTED NAME OF THE PERSON SIGNING AND SEALING |
| THE PLAN IS REQUIRED IN THE TITLE BLOCK BY FAC |
| 61G1-16.004. |
| |
| 19) THERE ARE SOME NOTATIONS ON ONE OF THE PLANS IN RED |
| PENCIL. |
| |
| 20) DUE TO THE LACK OF INFORMATION ON THE PLANS AND |
| SUBMITTALS, ADDITIONAL COMMENTS MAY RESULT WHEN THESE |
| ITEMS ARE ADDRESSED. |
| |
| 21) TO EXPEDITE PLAN REVIEW PLEASE RETURN ONE SET OF |
| THE OLD PLANS ALONG WITH A RESPONSE LETTER. |
| |