Notes |
Date |
Text |
2006-12-13 07:38:22 | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | 1} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT | | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE | | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS | | EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. | | | | 2} IF USING ARTICLE 220.30 TO CALCULATE THE LOAD FOR | | THIS SERVICE, THEN TABLE 220.32CANNOT BE USED. SEE | | CLARIFICATION OF USE IN 220.32(C). INDICATE WHICH IS | | BEING USED ON THE PLAN. | | NOTE: ALL ARTICLES COMMENTED ON ARE FROM THE 2002 | | NEC. | | | | 3} THE NOTE REGARDING 220.84 IS INCORRECT AND MUST BE | | CHANGED TO REFLECT THE CODE IN EFFECT AT TIME OF | | APPLICATION. | | | | 4} THE LAUNDRY CIRCUIT REQUIRED BY 220.16(B) WAS NOT | | INCLUDED IN THE CALCULATION. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW. | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|