Plan Review Notes
Plan Review Notes For Permit 06120027
Permit Number 06120027
Review Stop E
Sequence Number 1
Notes
Date Text
2006-12-13 07:38:22 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 2} IF USING ARTICLE 220.30 TO CALCULATE THE LOAD FOR
 THIS SERVICE, THEN TABLE 220.32CANNOT BE USED. SEE
 CLARIFICATION OF USE IN 220.32(C). INDICATE WHICH IS
 BEING USED ON THE PLAN.
 NOTE: ALL ARTICLES COMMENTED ON ARE FROM THE 2002
 NEC.
  
 3} THE NOTE REGARDING 220.84 IS INCORRECT AND MUST BE
 CHANGED TO REFLECT THE CODE IN EFFECT AT TIME OF
 APPLICATION.
  
 4} THE LAUNDRY CIRCUIT REQUIRED BY 220.16(B) WAS NOT
 INCLUDED IN THE CALCULATION.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]