Plan Review Notes For Permit 06120022 |
Permit Number |
06120022 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-01-18 15:05:35 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE | | FBC2004 | | | | 1.)PROVIDE A PLAN SHOWING LOCATION OF ALL WORK | | PROPOSED, APPROXIMATE SQUARE FOOT AREA. | | | | 2.)ARE THE CABINETS TO BE REPLACED AN EXACT CHANGE | | OUT, SAME SIZE, SAME LOCATION?PERMIT IS NOT REQUIRED | | UNLESS THERE IS A CHANGE IN CONFIGURATION.EITHER | | REMOVE FROM SCOPE OF WORK OR PROVIDE A DEMO PLAN AND | | NEW FLOOR PLAN. | | | | 3.)NO PERMIT REQUIRED FOR FLOORING OR TRIM FOR R3. IF | | THIS IS NOT R3, DECLARE OCCUPANCY FBC CHAPTER 3. | | | | 4.)EVALUATION REPORT AND INSTALLATION INSTRUCTIONS | | REQUIRED IN ADDITION TO THE FLORIDA STATE PRODUCT | | APPROVAL SUBMITTED, DOOR. | | | | 5.)IMPACT PROTECTION REQUIRED FBC1609.1.4.INDICATE | | WHICH PRODUCT YOU ARE INSTALLING IF THERE IS MORE THAN | | ONE OPTION ON PAPERWORK SUBMITTED. | | | | 6.)IS THERE PLUMBING OR ELECTRIC WORK ASSOCIATED WITH | | THIS JOB?SEPARATE PERMITS WILL BE REQUIRED. | | |
|