2009-04-15 08:28:49 | |
| |
| PERMIT #06120001 ELECTRICAL PLAN REVIEW |
| 290 BARCELONA ROAD 4/14/09 |
| WEST PALM BEACH, FL. |
| |
| |
| |
| |
| NOTE- ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS |
| OTHERWISE NOTED. |
| SHEET E2.1 |
| 1} PANEL "P" IS LISTED AS 150 AMP ON THE PANEL |
| SCHEDULE, SHOWN AS BEING FED FROM A 80 AMP BREAKER IN |
| PANEL "C" AND NOTE #13 LISTS IT AS A 80 AMP PANEL. |
| CORRELATE THESE NUMBERS TO INDICATE THE INTENDED |
| INSTALLATION. 408.4, AND RECALCULATE THE LOAD FOR PANEL |
| C PER 220. |
| |
| 2} NOTE #12 LISTS 3-#3 CU AS FEEDERS FOR PANEL P, THE |
| LOAD IS SHOWN AS 145.41 AMPS IN THE TOTAL SERVICE |
| CALCULATION (LISTED AS 145.21 KVA IN PANEL P ESTIMATED |
| DEMAND LOAD) ON THE PANEL SCHEDULE. SEE 310.16 FOR WIRE |
| SIZES AND ALLOWABLE AMPERAGES. |
| |
| 3} THE PANEL AMPERAGES IN THE TOTAL SERVICE CALCULATION |
| ARE LISTED IN AMPS AND AS KVA ON THE PANEL SCHEDULES, |
| PLEASE CORRECT. 408.4 |
| |
| 4} THE FEEDERS TO FOR DISCONNECT DP ARE ONLY RATED FOR |
| 350 AMPS AND THE LOAD IS LISTED AS 393.5 AMPS. SEE |
| 310.15(B)(6) FOR FEEDER SIZES. |
| |
| 5} THERE SHOULD NOT BE A GROUNDING ELECTRODE CONDUCTOR |
| ON PANEL "P". PANELS P AND C ARE ON THE SAME STRUCTURE, |
| P IS FED FROM C AND A GROUNDING ELECTRODE IS SHOWN |
| INSTALLED ON THAT PANEL PER 250.32. PANEL P SHOULD BE |
| GROUNDED FROM THE EQUIPMENT GROUND RAN WITH THAT |
| FEEDER. SEE 250.122 FOR SIZE. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |