 PERMIT #06120001 ELECTRICAL PLAN REVIEW
 290 BARCELONA ROAD 4/14/09
 WEST PALM BEACH, FL.
  
  
  
  
 NOTE- ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
 SHEET E2.1
 1} PANEL "P" IS LISTED AS 150 AMP ON THE PANEL
 SCHEDULE, SHOWN AS BEING FED FROM A 80 AMP BREAKER IN
 PANEL "C" AND NOTE #13 LISTS IT AS A 80 AMP PANEL.
 CORRELATE THESE NUMBERS TO INDICATE THE INTENDED
 INSTALLATION. 408.4, AND RECALCULATE THE LOAD FOR PANEL
 C PER 220.
  
 2} NOTE #12 LISTS 3-#3 CU AS FEEDERS FOR PANEL P, THE
 LOAD IS SHOWN AS 145.41 AMPS IN THE TOTAL SERVICE
 CALCULATION (LISTED AS 145.21 KVA IN PANEL P ESTIMATED
 DEMAND LOAD) ON THE PANEL SCHEDULE. SEE 310.16 FOR WIRE
 SIZES AND ALLOWABLE AMPERAGES.
  
 3} THE PANEL AMPERAGES IN THE TOTAL SERVICE CALCULATION
 ARE LISTED IN AMPS AND AS KVA ON THE PANEL SCHEDULES,
 PLEASE CORRECT. 408.4
  
 4} THE FEEDERS TO FOR DISCONNECT DP ARE ONLY RATED FOR
 350 AMPS AND THE LOAD IS LISTED AS 393.5 AMPS. SEE
 310.15(B)(6) FOR FEEDER SIZES.
  
 5} THERE SHOULD NOT BE A GROUNDING ELECTRODE CONDUCTOR
 ON PANEL "P". PANELS P AND C ARE ON THE SAME STRUCTURE,
 P IS FED FROM C AND A GROUNDING ELECTRODE IS SHOWN
 INSTALLED ON THAT PANEL PER 250.32. PANEL P SHOULD BE
 GROUNDED FROM THE EQUIPMENT GROUND RAN WITH THAT
 FEEDER. SEE 250.122 FOR SIZE.
  