Plan Review Notes For Permit 06120001 |
Permit Number |
06120001 |
|
Review Stop |
E |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2009-03-09 14:59:39 | | | | | | | REVISION DENIED | | | | 1} SHEET E1.1 THE LOW VOLTAGE PANEL UNDER THE STAIR IS | | IN VIOLATION OF 110.26(A)(1), 3" MINIMUM CLEARANCE. | | | | 2} SHEET E1.2 INCORRECTLY HAS REVISION #3 DATED | | FEBRUARY 9, 2009.REVISION #3 IN THE CITY'S FILE COPY IS | | DATED 6/21/08 ON THAT SHEET. | | | | 3} THE REVISION ON SHEET E2.1 SHOWS A CONDUIT FROM | | PANEL "DP" TO PANEL "P" AND A FEED FROM PANEL "C" PER | | NOTE #12, YET NEITHER PANEL INDICATES A FEED TO PANEL | | "P" IN THE PANEL SCHEDULES. | | | | NOTE: A PLUMPING REVISION MUST BE SUBMITTED FOR THE | | ADDED SINK IN THE CABANA. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | | | |
|