 REVISION DENIED
  
 1} SHEET E1.1 THE LOW VOLTAGE PANEL UNDER THE STAIR IS
 IN VIOLATION OF 110.26(A)(1), 3" MINIMUM CLEARANCE.
  
 2} SHEET E1.2 INCORRECTLY HAS REVISION #3 DATED
 FEBRUARY 9, 2009.REVISION #3 IN THE CITY'S FILE COPY IS
 DATED 6/21/08 ON THAT SHEET.
  
 3} THE REVISION ON SHEET E2.1 SHOWS A CONDUIT FROM
 PANEL "DP" TO PANEL "P" AND A FEED FROM PANEL "C" PER
 NOTE #12, YET NEITHER PANEL INDICATES A FEED TO PANEL
 "P" IN THE PANEL SCHEDULES.
  
 NOTE: A PLUMPING REVISION MUST BE SUBMITTED FOR THE
 ADDED SINK IN THE CABANA.
  