Plan Review Notes
Plan Review Notes For Permit 06120001
Permit Number 06120001
Review Stop E
Sequence Number 4
Notes
Date Text
2008-07-28 16:13:07 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC,2004 FBC CHAPTER
 1 AS AMENDED AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 REVISION DENIED
  
 1} SHEET E1.1 THE LOW VOLTAGE PANEL IN THE STAIRWELL OF
 THE CABANA DOES NOT COMPLY WITH THE CLEARANCE
 REQUIREMENTS OF 110.26.
  
 2} A SMOKE ALARM IS REQUIRED ".OUTSIDE EACH SEPARATE
 SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE
 BEDROOMS" THE STUDY IS BY DEFINITION.A BEDROOM. NFPA-72
 REQUIRES ALARMS OR DETECTORS WITHIN 20 FEET OF COOKING
 APPLIANCES BE SILENCING OR PHOTOELECTRIC. SEE
 11.8.3.5(4).
  
 3} THE RECEPTACLES ON THE COUNTERTOP ON EITHER SIDE OF
 THE RANGE ARE REQUIRED TO BE GFI PROTECTED PER
 210.8(A)(6). I HAVE REDLINED COMMENTS 2 & 3 ON THE
 PREVIOUS REVISION WHICH THE ARCHITECT PROBABLY WAS NOT
 AWARE.
  
 NOTE: SHEET E1.2 APPEARS TO BE COMPLIANT AND WILL NOT
 NEED TO BE RESUBMITTED.
  
 5} SHEET E2.1THE 350 MCM FEEDERS TO PANEL "DP" ARE NOT
 LARGE ENOUGH TO CARRY THE 393 AMP LOAD. SEE NOTE #4 FOR
 THE RISER DIAGRAM.SEE TABLE 310.15(B)(6).
  
 6} THE DISCONNECT "DP" IS RATED FOR 300 AMPS, NOT LARGE
 ENOUGH FOR THE LOAD.SEE NOTE #16, ALSO REVISE NOTE #3T
  
 7} THERE IS NO FEED FOR PANELS "C" AND "P" LISTED IN
 "DP PANEL SCHEDULE.NOTE #12 INDICATES PANEL "C" MAY BE
 FEEDING PANEL"P",CONTRARY TO NOTE #7, AND NOT SHOWN ON
 PANEL"C" SCHEDULE.
  
 8} PANEL "DP" IS LISTED AS 300 AMPS, SEE NOTE #19.
  
 9} THE ESTIMATED LOADS AT THE BOTTOM OF THE SCHEDULES
 IS RATED IN KVA. THE "TOTAL SERVICE FOR THE MAIN HOUSE
 AND CABANA" THE BOTTOM MIDDLE OF THE SHEET LISTS RATING
 IN AMPS "DP" AND "P" ARE INCORRECT. RECHECK ALL
 CALCULATIONS AND CORRELATE THE LOADS.
  
 10} THE TANKLESS HEATERS ON SHEET E1.1 ARE NOT ON ANY
 OF THE SCHEDULES, INDICATE IF THEY ARE GAS. IF THEY ARE
 ELECTRIC THEY WILL POSSIBLY LOAD THE SERVICE OVER 400
 AMPS.
  
 11} LOCATE PANEL "P" ON THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718