Date |
Text |
2008-07-28 16:13:07 | |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| RESIDENTIAL BUILDING CODE, 2005 NEC,2004 FBC CHAPTER |
| 1 AS AMENDED AND FOUND NONCOMPLIANT WITH THE |
| FOLLOWING: |
| |
| REVISION DENIED |
| |
| 1} SHEET E1.1 THE LOW VOLTAGE PANEL IN THE STAIRWELL OF |
| THE CABANA DOES NOT COMPLY WITH THE CLEARANCE |
| REQUIREMENTS OF 110.26. |
| |
| 2} A SMOKE ALARM IS REQUIRED ".OUTSIDE EACH SEPARATE |
| SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE |
| BEDROOMS" THE STUDY IS BY DEFINITION.A BEDROOM. NFPA-72 |
| REQUIRES ALARMS OR DETECTORS WITHIN 20 FEET OF COOKING |
| APPLIANCES BE SILENCING OR PHOTOELECTRIC. SEE |
| 11.8.3.5(4). |
| |
| 3} THE RECEPTACLES ON THE COUNTERTOP ON EITHER SIDE OF |
| THE RANGE ARE REQUIRED TO BE GFI PROTECTED PER |
| 210.8(A)(6). I HAVE REDLINED COMMENTS 2 & 3 ON THE |
| PREVIOUS REVISION WHICH THE ARCHITECT PROBABLY WAS NOT |
| AWARE. |
| |
| NOTE: SHEET E1.2 APPEARS TO BE COMPLIANT AND WILL NOT |
| NEED TO BE RESUBMITTED. |
| |
| 5} SHEET E2.1THE 350 MCM FEEDERS TO PANEL "DP" ARE NOT |
| LARGE ENOUGH TO CARRY THE 393 AMP LOAD. SEE NOTE #4 FOR |
| THE RISER DIAGRAM.SEE TABLE 310.15(B)(6). |
| |
| 6} THE DISCONNECT "DP" IS RATED FOR 300 AMPS, NOT LARGE |
| ENOUGH FOR THE LOAD.SEE NOTE #16, ALSO REVISE NOTE #3T |
| |
| 7} THERE IS NO FEED FOR PANELS "C" AND "P" LISTED IN |
| "DP PANEL SCHEDULE.NOTE #12 INDICATES PANEL "C" MAY BE |
| FEEDING PANEL"P",CONTRARY TO NOTE #7, AND NOT SHOWN ON |
| PANEL"C" SCHEDULE. |
| |
| 8} PANEL "DP" IS LISTED AS 300 AMPS, SEE NOTE #19. |
| |
| 9} THE ESTIMATED LOADS AT THE BOTTOM OF THE SCHEDULES |
| IS RATED IN KVA. THE "TOTAL SERVICE FOR THE MAIN HOUSE |
| AND CABANA" THE BOTTOM MIDDLE OF THE SHEET LISTS RATING |
| IN AMPS "DP" AND "P" ARE INCORRECT. RECHECK ALL |
| CALCULATIONS AND CORRELATE THE LOADS. |
| |
| 10} THE TANKLESS HEATERS ON SHEET E1.1 ARE NOT ON ANY |
| OF THE SCHEDULES, INDICATE IF THEY ARE GAS. IF THEY ARE |
| ELECTRIC THEY WILL POSSIBLY LOAD THE SERVICE OVER 400 |
| AMPS. |
| |
| 11} LOCATE PANEL "P" ON THE PLAN. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561/805-6718 |