Plan Review Notes
Plan Review Notes For Permit 06120001
Permit Number 06120001
Review Stop M
Sequence Number 3
Notes
Date Text
2008-04-21 08:52:28PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLANS
 *** DENIED ***
 1) COOLING LOAD CALCULATIONS ON FILE ARE CALLING FOR
 A/C SYSTEM 1 TO BE A TOTAL OF 36,423 COOLING BTU'S,
 REVISED MECHANICAL PLANS ARE SHOWING A TOTAL OF 48,500
 COOLING BTU'S. PER 2004 FBC 13-607.1.ABC.1.1 THE PLANS
 CAN ONLY CALL FOR 15% MORE THAN THE COOLING LOAD
 CALCULATIONS, PLEASE CORRECT.
  
 2) COOLING LOAD CALCULATIONS ON FILE ARE CALLING FOR
 A/C SYSTEM 2 TO BE A TOTAL OF 41,781 COOLING BTU'S,
 REVISED MECHANICAL PLANS ARE SHOWING A TOTAL OF 60,000
 COOLING BTU'S. PER 2004 FBC 13-607.1.ABC.1.1 THE PLANS
 CAN ONLY CALL FOR 15% MORE THAN THE COOLING LOAD
 CALCULATIONS, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]