2007-04-06 07:52:06 | DENIED BY BUILDING (2ND REVIEW) |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) SUBMIT A COPY OF THE PAID RECEIPT FOR THE IMPACT |
| FEES. |
| |
| 3) THE INSTALLATION DRAWINGS AND DESIGN PRESSURE TABLES |
| IN THE NOA 05-1018.01 SUBMITTED FOR THE PGT SINGLE HUNG |
| WINDOWS ARE ILLEGIBLE. |
| |
| 4)PAGE 5 OF 7 OF THE PRODUCT APPROVAL NOA FOR THE PGT |
| MULLIONS IS ILLEGIBLE. |
| |
| 5) SUBMIT PRODUCT APPROVALS FOR THE TRUSS CONNECTORS, |
| STRAPS HANGERS AND OTHER SPECIED STRUCTURAL ANCHORS. |
| SEE COMMENT #22 FROM FIRST REVIEW. |
| |
| 6) THE PAGES CONTAINING THE APPROVED ASSEMBLIES ARE |
| MISSING FROM THE PRODUCT APPROVAL NOA 03-0501.02 FOR |
| THE GAF MODIFIED ROOF SYSTEM. SPECIFY WHICH ONE OF THE |
| APPROVED ASSEMBLIES WILL BE INSTALLED. SPECIFY THE |
| FASTENING OPTION AND DESIGN PRESSURE FOR THE SYSTEM |
| (CIRCLE THE ITEMS ON THE PAGE OF THE APPROVED ASSEMBLY |
| SELECTED). ENHANCED FASTENING WILL BE REQUIRED FOR ROOF |
| ZONE3 (-89PSF) AND POSSIBLY ROOF ZONE 2 (-59.2) |
| DEPENDING ON THE SYSTEM THAT IS USED. NONE OF THE |
| ASSEMBLIES THAT HAVE GENERAL LIMITATION #9 WILL WORK |
| BECAUSE THIS LIMITATION DOES NOT ALLOW ENHANCED |
| FASTENING. THEREFORE, ONLY THE ASSEMBLIES WITH GENERAL |
| LIMITATION #7, WHICH ALLOWS THE DESIGN PRESSURE TO BE |
| INCREASED BY INCREASING THE FASTENER DENSITIES |
| CALCULATED BY USING ROOFING APPLICATION STANDARD 117 |
| CALCULATIONS. SUBMIT RAS 117 CALCULATIONS FOR THE |
| SELECTED ASSEMBLY. SEE ITEM # 23 FROM FIRST REVIEW. |
| |
| 7) SUBMIT PRODUCT APPROVALS FOR ARCH TOP WINDOWS. SEE |
| ITEM # 20 OF FIRST REVIEW. |
| |