Plan Review Notes
Plan Review Notes For Permit 06120001
Permit Number 06120001
Review Stop P
Sequence Number 1
Notes
Date Text
2006-12-20 16:55:50DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PLEASE CLARIFY ON THE RESUBMITTED DRAWINGS EXACTLY
 WHAT IS EXISTING STRUCTURE AND WHAT IS THE PROPOSED
 ADDITION OR PROVIDE A LEGEND CLARIFYING THIS.
  
 2. THE DISHWASHER INDICATED ON SHEET P1.1 IS INDICATED
 WRONG ON THE SANITARY PLUMBING RISER DIAGRAM PER
 FBC-2004 PLUMBING, SECTION 802.1. PLEASE CORRECT ON THE
 RESUBMITTAL.
 (A) 802.1.6 DISCHARGE INTO A WYE-BRANCH FITTING ON THE
 TAILPIECE OF THE KITCHEN SINK OR THE DISHWASHER
 CONNECTION OF A FOOD WASTE GRINDER, NOT OFF THE WASTE
 ARM AS INDICATED.
  
 3. PER THE FLOOR PLAN ON SHEET A2.1 THE ISLAND SINK
 W/DISPOSAL IS MISSING ON THE SANITARY PLUMBING RISER
 DIAGRAM ON SHEET P1.1. PLEASE CORRECT ON THE
 RESUBMITTAL.
  
 4. THE WASHING MACHINE LAUNDRY STACK IS SIZED WRONG
 PER FBC-2004 PLUMBING, SECTION, 406.3.
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
  
 5. BATH #5 PER THE FLOOR PLAN ON SHEET A2.2 THE SHOWER
 IS INDICATED INCORRECTLY ON THE SANITARY RISER DIAGRAM
 ON SHEET P1.1 AS A TUB. PLEASE CORRECT ON THE
 RESUBMITTAL.
  
 6. SHEET P1.1, 2ND FLOOR SHOWER IN HIS BATH IS
 INDICATING AN "S" TRAP. "S" TRAPS ARE PROHIBITED PER
 FBC-2004 PLUMBING, SECTION 1002.3. PLEASE CORRECT ON
 THE RESUBMITTAL.
  
 7. SHEET A2.3 PLEASE PROVIDE THE FOLLOWING INFORMATION
 IN RELATION TO THE ROOFS PER FBC-2004 PLUMBING, SECTION
 1106.2 AND 1106.4.
 A} SQ. FT. OF FLAT ROOFS AND ADJOINING ROOFS THAT
 SPILL ON FLAT ROOFS.
 B} SQ. FT. OF VERTICAL WALLS.
 C} SIZE OF RAIN WATER LEADERS AND DOWNSPOUTS.
 D} PLEASE PROVIDE A DETAIL OF THESIZE AND LOCATION
 OF THE EMERGENCY OVERFLOW SCUPPERS.
  
 8. SHEET A3.2 PLEASE INDICATE THE RAIN LEADER,
 DOWNSPOUT AND SCUPPER LOCATIONS ON THE WEST FACADE.
  
 9. SHEET A3.3 PLEASE INDICATE THE RAIN LEADER,
 DOWNSPOUT AND SCUPPER LOCATIONS ON THE SOUTH FACADE.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  