Plan Review Notes
Plan Review Notes For Permit 06120001
Permit Number 06120001
Review Stop M
Sequence Number 1
Notes
Date Text
2006-12-21 11:57:38*** DENIED ***
 1) RETURN AIR TRANSFER DUCT TO MASTER SUITE NEEDS TO BE
 16". BALANCED RETURN AIR MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 2) NOT ALL SUPPLY AND RETURN AIR DUCTS ARE SIZED SEE
 HIGH LIGHTED DUCTS ON PLANS PAGE M1.1 AND M1.2, PLEASE
 SIZE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.