Plan Review Notes
Plan Review Notes For Permit 06120001
Permit Number 06120001
Review Stop E
Sequence Number 1
Notes
Date Text
2006-12-19 15:28:48NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, METER
 ENCLOSURE, DISCONNECTS AND PANELS, SO THAT COMPLIANCE
 WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 2} THE EQUIPMENT GROUNDING CONDUCTOR MUST COMPLY WITH
 250.66. SEE NOTE #1 REGARDING THE SUM OF THE SERVICE
 ENTRANCE CONDUCTORS. MINIMUM #1/0 CU.( SHEET E2.1).
  
 3} PLEASE ADD A NOTE FOR HEXAGONAL #22, SHEET E2.1.
  
 4} PLEASE CORRECT NOTE #16, THE EQUUIPMENT BEING
 REFERENCED IS A DISCONNECT.
  
 5} PLEASE CORRECT PANEL "DP"LOAD CALC TOTAL.SEE SHEET
 E2.1.
  
 6} SMOKE ALARMS ARE REQUIRED INSIDE AND IMMEDIATLY
 OUTSIDE THE " PRIVATE READING ROOM" , WHICH IS A
 "BEDROOM" BY DEFINITION IN THE FBC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.