2007-02-07 07:41:40 | DENIED BY BUILDING |
| |
| 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 3)SHEETS A5.1 AND A5.2 SPECIFY A MINIMUM SOIL BEARING |
| CAPACITY OF 2500 PSF. THE SOIL REPORT AND STRUCTURAL |
| PLANS SPECIFY THE MINIMUM SOIL BEARING CAPACITY AS 1500 |
| PSF. PLEASE CORRECT. |
| |
| 4) SUBMIT A DRAINAGE PLAN FOR THE LOT SHOWING |
| COMPLIANCE WITH R401.3. |
| SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS |
| TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO |
| DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE |
| GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM |
| OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048 |
| MM). |
| EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER |
| PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL |
| WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE |
| PROVIDED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. |
| |
| 5)ON SHEET A1.1 UNDER DESIGN CRITERIA SPECIFY THE |
| 2004 FBC. THE EXPOSURE CATEGORY OF B IS INCORRECTLY |
| SPECIFIED AS WIND CLASSIFICATION. PLEASE CORRECT. UNDER |
| GENERAL REQUIREMENTS, THE SOIL BEARING CAPACITY IS |
| SPECIFIED AS 2500 PSF. PLEASE CORRECT. |
| |
| 6)SHOW COMPLIANCE WITH R320.7 PROTECTION AGAINST |
| TERMITES AND DECAY. CONDENSATE LINES AND ROOF |
| DOWNSPOUTS SHALL DISCHARGE AT LEAST 1 FOOT AWAY FROM |
| THE STRUCTURE SIDEWALL, WHETHER BY UNDERGROUND PIPING, |
| TAIL EXTENSIONS OR SPLASH BLOCKS. GUTTERS WITH DOWN |
| SPOUTS ARE REQUIRED ON ALL BUILDINGS WITH EAVES OF LESS |
| THAN 6 INCHES HORIZONTAL PROJECTION EXCEPT FOR GABLE |
| END RAKES OR ON A ROOF ABOVE ANOTHER ROOF. |
| |
| 7) SHOW THE SCUPPERS AND DOWNSPOUTS ON THE |
| ELEVATIONS.R903.4 ROOF DRAINAGE. |
| UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF EDGES, ROOF |
| DRAINS SHALL BE INSTALLED AT EACH LOW POINT OF THE |
| ROOF. WHERE REQUIRED FOR ROOF DRAINAGE, SCUPPERS SHALL |
| BE PLACED LEVEL WITH THE ROOF SURFACE IN A WALL OR |
| PARAPET. THE SCUPPER SHALL BE LOCATED AS DETERMINED BY |
| THE ROOF SLOPE AND CONTRIBUTING ROOF AREA. R903.4.1 |
| WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT |
| PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR |
| PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4 |
| INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND |
| SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED |
| VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET |
| SCUPPERS . AN OVERFLOW SCUPPER SHALL BE SIZED IN |
| ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING . |
| |
| 8)THE EAST ELEVATION ON A3.2INDICATES GARAGE AT THE |
| PORTE-COCHERE. PLEASE CORRECT. |
| |
| 9)THE 7.6" DIMENSION ON STAIR SECTION 4/A5 IS THE |
| RISER HEIGHT NOT THE TREAD DEPTH AS INDICATED. PLEASE |
| CORRECT. |
| |
| 10) SECTION5/S8 SPECIFIES THE (F1) FOOTER WIDTH AS |
| 2'-0". THE SCHEDULE ON S10 SPECIFIES 2'-4" FOR THIS |
| FOOTER. PLEASE CLARIFY. |
| |
| 11) ON SHEETS S1, S2, AND S3 THERE ARE TAGS FOR |
| SECTIONS ON S9A, HOWEVER, THERE IS NO SHEET S9A IN THE |
| PLANS. PLEASE CORRECT. |
| |
| 12) ON SHEET A0.0 THE DRAWING LIST IS INCORRECT FOR THE |
| STRUCTURAL SHEETS. PLEASE CORRECT. |
| |
| 13) SECTION 5/S5 SHOWS ONE 2 XLEDGER FOR L3 AND THE |
| SCHEDULE ON S10 SPECIFIES TWO 2 X 12. PLEASE CLARIFY. |
| |
| 14) INDICATE HOW THE RAIN WATER WILL BE DRAINED FROM |
| THE SECOND FLOOR TERRACES WHICH APPEAR TO HAVE WALLS ON |
| THEIR PERIMETERS. |
| |
| 15) ON SECTION 4/S4 FIREBLOCKING IS REQUIRED BETWEEN |
| THE FLOOR AND WALL CONCEALED SPACES. SEE R602.8. |
| |
| 16) ON SECTION 6/S8 THE FOOTER HEIGHT IS ILLEGIBLE. |
| |
| 17) THE CONNECTOR SCHEDULE ON S10 HAS NO ID NUMBERS TO |
| CORRESPOND WITH THE NUMBERS ABOVE THE UPLIFTS ON THE |
| ROOF FRAMING PLAN ON S3. PLEASE CLARIFY. |
| |
| 18) ON SHEET S15 UNDER DESIGN DATAITEM 10 GIVES THE |
| DESIGN LIVE LOADS FOR RETAIL AND THIS PROJECT IS |
| RESIDENTIAL. PLEASE CORRECT. |
| |
| 19)THE PRODUCT APPROVALS FOR THE PGT WINDOWS AND |
| FRENCH DOORS ARE EXPIRED. PLEASE SUBMIT CURRECT PRODUCT |
| APPROVAL WITH CURRENT FL COVERSHEETS. |
| |
| 20) SUBMIT PRODUCT APPROVALS FOR THE ARCH TOP DOORS AND |
| SINGLE HUNG ARCH TOP WINDOWS. |
| |
| 21) SUBMIT PRODUCT APPROVALS FOR STRUCTURAL MULLIONS. |
| |
| 22) SUBMIT PRODUCT APPROVALS FOR TRUSS CONNECTORS, |
| STRAPS, HANGERS AND OTHER STRUCTURAL ANCHORS. |
| |
| 23) ON THE PRODUCT APPROVAL FOR THE GAF MODIFIED ROOF |
| SYSTEM, SPECIFY THE APPROVED SYSTEM THAT WILL BE |
| INSTALLED. SPECIFY THE FASTENING OPTION AND MAXIMUM |
| DESIGN PRESSURE THAT WILL BE USED. CIRCLE THE |
| APPROPRIATE ITEMS ON THE NOA. IF ENHANCED FASTENING IS |
| REQUIRED FOR THE PERIMETER AND CORNER AREAS,SUBMIT |
| RAS 117 CALCULATIONS AS REQUIRED BY LIMITATION NUMBER |
| 7. |
| |
| 24)SPECIFY WHICH ATTACHMENT METHOD WILL BE USED TO |
| INSTALL THE CLAY ROOF TILES. CIRCLE THE APPROPRIATE |
| ITEM ON THE NOA. |
| |
| 25) SUBMIT A KEY PLAN AND INSTALLATION SCHEDULE FOR THE |
| STORM PANELS. INDICATE THE OPENINGS ON WHICH THEY WILL |
| BE INSTALLED. SPECIFY THE FASTENER TYPE AND SPACING, |
| THE CONNECTION TYPE,THE SPANS, THE PRESSURES, ETC. |
| |
| 26)WPB ADMIN CODE 106.3* PRODUCT |
| APPROVALS. THOSE PRODUCT WHICH ARE |
| REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| NOTE: PLEASE REMOVE OLD SHEETS FROM THE PLANS AND |
| INSERT THE NEW ONES. SUBMIT ONE SET OF THE OLD PLANS |
| FOR REFERENCE TO HELP EXPEDITE REVIEWS. |
| |