Plan Review Notes
Plan Review Notes For Permit 06120001
Permit Number 06120001
Review Stop B
Sequence Number 1
Notes
Date Text
2007-02-07 07:41:40DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3)SHEETS A5.1 AND A5.2 SPECIFY A MINIMUM SOIL BEARING
 CAPACITY OF 2500 PSF. THE SOIL REPORT AND STRUCTURAL
 PLANS SPECIFY THE MINIMUM SOIL BEARING CAPACITY AS 1500
 PSF. PLEASE CORRECT.
  
 4) SUBMIT A DRAINAGE PLAN FOR THE LOT SHOWING
 COMPLIANCE WITH R401.3.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS
 TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE
 GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM
 OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048
 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 PROVIDED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
  
 5)ON SHEET A1.1 UNDER DESIGN CRITERIA SPECIFY THE
 2004 FBC. THE EXPOSURE CATEGORY OF B IS INCORRECTLY
 SPECIFIED AS WIND CLASSIFICATION. PLEASE CORRECT. UNDER
 GENERAL REQUIREMENTS, THE SOIL BEARING CAPACITY IS
 SPECIFIED AS 2500 PSF. PLEASE CORRECT.
  
 6)SHOW COMPLIANCE WITH R320.7 PROTECTION AGAINST
 TERMITES AND DECAY. CONDENSATE LINES AND ROOF
 DOWNSPOUTS SHALL DISCHARGE AT LEAST 1 FOOT AWAY FROM
 THE STRUCTURE SIDEWALL, WHETHER BY UNDERGROUND PIPING,
 TAIL EXTENSIONS OR SPLASH BLOCKS. GUTTERS WITH DOWN
 SPOUTS ARE REQUIRED ON ALL BUILDINGS WITH EAVES OF LESS
 THAN 6 INCHES HORIZONTAL PROJECTION EXCEPT FOR GABLE
 END RAKES OR ON A ROOF ABOVE ANOTHER ROOF.
  
 7) SHOW THE SCUPPERS AND DOWNSPOUTS ON THE
 ELEVATIONS.R903.4 ROOF DRAINAGE.
 UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF EDGES, ROOF
 DRAINS SHALL BE INSTALLED AT EACH LOW POINT OF THE
 ROOF. WHERE REQUIRED FOR ROOF DRAINAGE, SCUPPERS SHALL
 BE PLACED LEVEL WITH THE ROOF SURFACE IN A WALL OR
 PARAPET. THE SCUPPER SHALL BE LOCATED AS DETERMINED BY
 THE ROOF SLOPE AND CONTRIBUTING ROOF AREA. R903.4.1
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS . AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING .
  
 8)THE EAST ELEVATION ON A3.2INDICATES GARAGE AT THE
 PORTE-COCHERE. PLEASE CORRECT.
  
 9)THE 7.6" DIMENSION ON STAIR SECTION 4/A5 IS THE
 RISER HEIGHT NOT THE TREAD DEPTH AS INDICATED. PLEASE
 CORRECT.
  
 10) SECTION5/S8 SPECIFIES THE (F1) FOOTER WIDTH AS
 2'-0". THE SCHEDULE ON S10 SPECIFIES 2'-4" FOR THIS
 FOOTER. PLEASE CLARIFY.
  
 11) ON SHEETS S1, S2, AND S3 THERE ARE TAGS FOR
 SECTIONS ON S9A, HOWEVER, THERE IS NO SHEET S9A IN THE
 PLANS. PLEASE CORRECT.
  
 12) ON SHEET A0.0 THE DRAWING LIST IS INCORRECT FOR THE
 STRUCTURAL SHEETS. PLEASE CORRECT.
  
 13) SECTION 5/S5 SHOWS ONE 2 XLEDGER FOR L3 AND THE
 SCHEDULE ON S10 SPECIFIES TWO 2 X 12. PLEASE CLARIFY.
  
 14) INDICATE HOW THE RAIN WATER WILL BE DRAINED FROM
 THE SECOND FLOOR TERRACES WHICH APPEAR TO HAVE WALLS ON
 THEIR PERIMETERS.
  
 15) ON SECTION 4/S4 FIREBLOCKING IS REQUIRED BETWEEN
 THE FLOOR AND WALL CONCEALED SPACES. SEE R602.8.
  
 16) ON SECTION 6/S8 THE FOOTER HEIGHT IS ILLEGIBLE.
  
 17) THE CONNECTOR SCHEDULE ON S10 HAS NO ID NUMBERS TO
 CORRESPOND WITH THE NUMBERS ABOVE THE UPLIFTS ON THE
 ROOF FRAMING PLAN ON S3. PLEASE CLARIFY.
  
 18) ON SHEET S15 UNDER DESIGN DATAITEM 10 GIVES THE
 DESIGN LIVE LOADS FOR RETAIL AND THIS PROJECT IS
 RESIDENTIAL. PLEASE CORRECT.
  
 19)THE PRODUCT APPROVALS FOR THE PGT WINDOWS AND
 FRENCH DOORS ARE EXPIRED. PLEASE SUBMIT CURRECT PRODUCT
 APPROVAL WITH CURRENT FL COVERSHEETS.
  
 20) SUBMIT PRODUCT APPROVALS FOR THE ARCH TOP DOORS AND
 SINGLE HUNG ARCH TOP WINDOWS.
  
 21) SUBMIT PRODUCT APPROVALS FOR STRUCTURAL MULLIONS.
  
 22) SUBMIT PRODUCT APPROVALS FOR TRUSS CONNECTORS,
 STRAPS, HANGERS AND OTHER STRUCTURAL ANCHORS.
  
 23) ON THE PRODUCT APPROVAL FOR THE GAF MODIFIED ROOF
 SYSTEM, SPECIFY THE APPROVED SYSTEM THAT WILL BE
 INSTALLED. SPECIFY THE FASTENING OPTION AND MAXIMUM
 DESIGN PRESSURE THAT WILL BE USED. CIRCLE THE
 APPROPRIATE ITEMS ON THE NOA. IF ENHANCED FASTENING IS
 REQUIRED FOR THE PERIMETER AND CORNER AREAS,SUBMIT
 RAS 117 CALCULATIONS AS REQUIRED BY LIMITATION NUMBER
 7.
  
 24)SPECIFY WHICH ATTACHMENT METHOD WILL BE USED TO
 INSTALL THE CLAY ROOF TILES. CIRCLE THE APPROPRIATE
 ITEM ON THE NOA.
  
 25) SUBMIT A KEY PLAN AND INSTALLATION SCHEDULE FOR THE
 STORM PANELS. INDICATE THE OPENINGS ON WHICH THEY WILL
 BE INSTALLED. SPECIFY THE FASTENER TYPE AND SPACING,
 THE CONNECTION TYPE,THE SPANS, THE PRESSURES, ETC.
  
 26)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 NOTE: PLEASE REMOVE OLD SHEETS FROM THE PLANS AND
 INSERT THE NEW ONES. SUBMIT ONE SET OF THE OLD PLANS
 FOR REFERENCE TO HELP EXPEDITE REVIEWS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714