Plan Review Notes
Plan Review Notes For Permit 06111068
Permit Number 06111068
Review Stop B
Sequence Number 1
Notes
Date Text
2006-12-20 14:57:27DENIED BY BUILDING
  
 1)SUBMIT TWO SETS OF SIGNED , SEALED AND DATED
 ENGINEERING FOR EACH PERMIT. THE ENGINEER IS REQUIRED
 TO SPECIFY THE WIND DESIGN DATA FOR THIS WORK. SEE FBC
 1603.1.4.
  
 2) THE ROOF PITCH OF THE NEW TRUSSES IS SPECIFIED AS
 3/12. THIS IS INCORRECT. THE ACTUAL SLOPE IS 48/12 FOR
 THE MANSARD.PLEASE CORRECT.
  
 3) THE TRUSS DRAWINGS SHOW THE TRUSSES IN A DIFFERENT
 ORIENTATION THAN THE DESIGN INDICATES.THE LOADING AND
 RESISTANCES WILL BE DIFFERENT WHEN INSTALLED AS
 SPECIFIED. PLEASE CORRECT.
  
 4) THE TRUSS ENGINEER IS REQUIRED TO PERSONALLY SIGN
 THE TRUSS DRAWINGS. A SIGNATURE STAMP OR COPIED
 SIGNATURE IS NOT ACCEPTABLE. SEE FAC 61G15-23.002.
  
 5) SUBMIT PRODUCT APPROVALS FOR THE TRUSS CONNECTORS.
 SEE FS 553.842 AND RULE 9B-72.
  
 6)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714