2006-12-20 14:57:27 | DENIED BY BUILDING | | | | 1)SUBMIT TWO SETS OF SIGNED , SEALED AND DATED | | ENGINEERING FOR EACH PERMIT. THE ENGINEER IS REQUIRED | | TO SPECIFY THE WIND DESIGN DATA FOR THIS WORK. SEE FBC | | 1603.1.4. | | | | 2) THE ROOF PITCH OF THE NEW TRUSSES IS SPECIFIED AS | | 3/12. THIS IS INCORRECT. THE ACTUAL SLOPE IS 48/12 FOR | | THE MANSARD.PLEASE CORRECT. | | | | 3) THE TRUSS DRAWINGS SHOW THE TRUSSES IN A DIFFERENT | | ORIENTATION THAN THE DESIGN INDICATES.THE LOADING AND | | RESISTANCES WILL BE DIFFERENT WHEN INSTALLED AS | | SPECIFIED. PLEASE CORRECT. | | | | 4) THE TRUSS ENGINEER IS REQUIRED TO PERSONALLY SIGN | | THE TRUSS DRAWINGS. A SIGNATURE STAMP OR COPIED | | SIGNATURE IS NOT ACCEPTABLE. SEE FAC 61G15-23.002. | | | | 5) SUBMIT PRODUCT APPROVALS FOR THE TRUSS CONNECTORS. | | SEE FS 553.842 AND RULE 9B-72. | | | | 6)A RECORDED COPY OF THE NOTICE OF | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | PERMIT CAN BE ISSUED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|